Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Compilations of discovery responses

Files31

Text of ALLCO Set 3_COMBINED.pdf

Extracted from the file · 23 pages · 55,777 characters

Text of ALLCO Set 2_COMBINED.pdf

Extracted from the file · 38 pages · 81,182 characters

Text of ALLCO Set 1_COMBINED.pdf

Extracted from the file · 27 pages · 46,644 characters

Text of ALLCO Set 6_COMBINED.pdf

Extracted from the file · 9 pages · 18,340 characters

Text of AMTRAK Set 2_COMBINED.pdf

Extracted from the file · 2 pages · 3,025 characters

Text of AMTRAK Set 1_COMBINED.pdf

Extracted from the file · 5 pages · 4,881 characters

Text of AMTRAK Set 3_COMBINED.pdf

Extracted from the file · 34 pages · 101,991 characters

Text of CIEC Set 2_COMBINED.pdf

Extracted from the file · 1 page · 1,005 characters

Text of CIEC Set 1_COMBINED.pdf

Extracted from the file · 19 pages · 26,023 characters

Text of CIEC Set 3_COMBINED.pdf

Extracted from the file · 4 pages · 5,355 characters

Text of CLF-SC Set 1_COMBINED.pdf

Extracted from the file · 56 pages · 132,578 characters

Text of CLF Set 1_ COMBINED.pdf

Extracted from the file · 20 pages · 38,243 characters

Text of CLF-SC Set 2_COMBINED.pdf

Extracted from the file · 7 pages · 17,131 characters

Text of EOE Set 3_COMBINED.pdf

Extracted from the file · 11 pages · 23,418 characters

Text of EOE Set 2_COMBINED.pdf

Extracted from the file · 22 pages · 42,455 characters

Text of EOE Set 1_COMBINED.pdf

Extracted from the file · 200 pages · 332,382 characters

Text of EOE Set 4_COMBINED.pdf

Extracted from the file · 70 pages · 139,575 characters

Text of ICC Set 1_COMBINED.pdf

Extracted from the file · 30 pages · 51,093 characters

Text of OCC Set 13_COMBINED.pdf

Extracted from the file · 30 pages · 61,971 characters

  1. Page 11 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-522 Page 2 of 2 the carrying charge calculation with the manner in which comparable long-term assets are reflected for ratemaking purposes. Similarly, the WACC is the appropriate rate for calculating carrying charges on long-term funded regulatory assets because it reflects the Company’s actual cost of funding those customer “debts,” including storm restoration costs, over an extended period of time. Financing obligations – certainly obligations of this magnitude – cannot be supported exclusively through debt financing, whether short-term or long-term. Instead, the Company must balance its capital requirements through a reasonable mix of both debt and equity to ensure financial stability and continued access to reasonably priced capital. With respect to the appropriate carrying charge rate to utilize for the Storm Cost Recovery Adjustment Factor (“SCRAF”), the Company provided a thorough response to this question in response to LFE-031, in Docket No. 25-12-13. The Company is providing that response as OCC-522, Attachment 1. The analysis shows that: (1) necessary uses of cash routinely exceed available sources of cash, creating a persistent funding gap; (2) commercial paper is a tool to maintain liquidity, not to finance investments or deferred expenses; and (3) short-term borrowing capacity is limited, and the Company cannot plan to operate at or near its short-term debt capacity without putting its ability to operate the system in severe jeopardy. Given all of the considerations elucidated by Attachment 1, the Company recognizes that the appropriate treatment of carrying charges may vary based on the regulatory framework established within each jurisdiction. Different regulatory constructs reflect differing policy objectives and mechanisms designed to balance the Company’s financing needs with customer impacts. In establishing a going-forward framework for storm cost recovery, the Company agrees that it would be within PURA’s discretion to strike a balance between the Company’s costs of financing storm costs while ensuring that the Company is not ‘profiting’ on a force majeure event like a storm. This is the Company’s experience in Massachusetts, as well, where the MDPU has authorized a carrying charge rate that is different from and generally less than the Company’s WACC, but that still recognizes that the Company is using its longer-term capital resources to finance storm costs (not its shorter term commercial paper source of liquidity). Thus, the Company stated that “should PURA implement the SCRAF, which provides for more timely review and recovery of storm and pre-staging costs, the Company accepts the Prime rate from the date of cost incurrence, applied to the net balance of the storm fund and pre-staging reserve fund for storms occurring after March, 2025.”
  2. Page 12 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-523 Page 1 of 2 Date Filed: September 15, 2026 Witness: Donald J. Scacco Jr., Digaunto Chatterjee and Douglas P. Horton Request from: Office of Consumer Counsel Question: Leadership Panel Exhibit CLP-ELP-3 – Performance Incentive Mechanisms and Metrics Exhibit CLP-ELP-3, summarizes the Company’s proposed PBR performance portfolio. Please explain how the Company determined that the proposed set of PIMs represents the appropriate performance areas to which financial incentives and/or penalties should be attached during the PBMRP term. In your response, please identify the criteria the Company used to determine which performance measures warranted financial incentives or penalties and explain how those criteria were applied to the potential PIMs identified in the Performance Evaluation System adopted in the Proposed Final Decision in Docket No. 21-05-15RE02. Response: When developing its proposed performance metrics, the Company sought to ensure that its proposed metrics would provide meaningful insight into the Company’s performance in terms of service quality and customer service during the PBR term. The Company’s proposed PBR performance portfolio, including PIMs, is designed as a balanced portfolio of measurable performance outcomes that reflect the quality, reliability, accessibility and responsiveness of electric service provided to customers and over which the Company has meaningful operational influence. The approach is consistent with the broader evolution of performance-based regulations in the electric utility industry where reliability and customer service have traditionally been recognized as core service-quality areas appropriate for performance measurements and, in some jurisdictions, financial incentives or penalties. Similar to the proposed final decision in Docket No. 21-0515RE02, the Company has included system and customer reliability in its PIMs proposal, while also expanding the customer experience related PIMs to represent a more well-rounded and holistic measurement of customer-facing performance. The proposed PIMs address both system and customer reliability, customer service and customer experience. Collectively, these measures recognize that reliable electric service encompasses more than system wide outage performance. The measures also include the reliability experienced by individual customers and the quality, accessibility, timeliness and effectiveness of the Company’s interactions with customers.
  3. Page 13 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-523 Page 2 of 2 When determining whether a metric should include a financial penalty or incentive, the Company considered whether the metric (1) can be objectively measured; (2) has an established baseline against which performance can be measured; and (3) whether it will measure “performance” that is actually within the Company’s control. PIMs that lack these foundational elements could result in unintended consequences of penalizing a utility for performance that is not actually substandard, nor a product of the utility’s own efforts. The proposed PIM financial incentives and penalties are appropriate because the measures establish clear, objective and measurable expectations for outcomes that are important to customers and sustainably within the Company’s ability to influence through its operational practices, resource allocation and management decisions. The asymmetrical application of incentives and penalties is intended to promote sustained performance, providing an opportunity for the Company to earn an incentive when it exceeds established expectations while creating accountability when performance falls below expectations. Taken together, the PIMs provide a comprehensive framework that aligns the Company’s financial interests with customer interests while maintaining a balanced focus on reliability, affordability, customer service, efficiency, accessibility and the overall customer experience.
  4. Page 14 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-524 Page 1 of 2 Date Filed: September 15, 2026 Witness: Elli Ntakou and Lavelle A. Freeman Request from: Office of Consumer Counsel Question: Targeted System Performance Plan Exhibit CLP-TSP-1: Reliability PIMs The Company proposes a sliding penalty structure for each Blue-Sky SAIDI and Blue-Sky SAIFI PIM, with penalties beginning at one standard deviation above the five-year average and increasing through two standard deviations. a. Please explain how the Company developed this penalty structure and provide any analysis demonstrating how the proposed financial consequences are expected to maintain or improve reliability performance, consistent with the company’s stated goals. b. Were any other five-year periods considered for the five-year average threshold? If yes, explain why the period 2022-2026 was selected for the calculation of the five-year average. Response: a. The Company developed this penalty structure consistent with industry standards for nonsymmetrical PIMs and with considerations for yearly deviations of blue-sky SAIDI and blue-sky SAIFI. Major events are excluded from blue-sky reliability metrics because these events are significant outliers for the purposes of determining reliability. However, the reliability metrics maintain volatility because of the inclusion of impacts from the numerous minor storm events that occur across a year and that do not reach the exclusionary threshold. A well-designed PIM should base a penalty on the degree to which a value exceeds the threshold, and whether deviations are driven by factors within the Company’s control or exogenous factors. For example, slight deviations due to weather patterns should be penalized less or not at all, as compared to larger deviations indicative of influence by the Company’s own actions. Therefore, the Company’s proposal accounts for normal deviations by establishing a standard for performance and gradual penalties, starting at the threshold of “average plus one standard deviation” and full penalty for performance exceeding “average plus two standard deviations”. In addition, although, PIMs set standards for performance, the penalty structure does not drive reliability performance. The PIM objectives or deadbands set the expectation for what level of performance the Company should target; however, absent regulatory approval of
  5. Page 15 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-524 Page 2 of 2 a commensurate spending level that enables the Company to achieve the identified objectives, penalties alone, regardless of their size or structure, will not be able to drive performance relative to PIM objectives. b. No, the Company did not consider other 5-year periods. The 2022-2026 timeframe is the most recent complete 5-year data set at the time the PIMs and their penalties are expected to become applicable (i.e., 2027). Selecting a recent time period as a baseline has the benefit of incorporating the most recent system performance measures, with the associated standards and asset types. In contrast to resilience, where time periods further back may be needed in the baseline to capture major events that rarely occur, selecting the most recent time period for use as reliability baseline is necessary for a valid metric.
  6. Page 16 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-525 Page 1 of 2 Date Filed: September 15, 2026 Witness: Elli Ntakou and Lavelle A. Freeman Request from: Office of Consumer Counsel Question: Targeted System Performance Plan Exhibit CLP-TSP-1: Reliability PIMs The final RE02 Performance Evaluation System identifies a potential Customer Reliability PIM based on CEMI-5, the percentage of repeat CEMI-5 customers, CELID-6, and the percentage of repeat CELID-6 customers. The Company instead proposes to use the average count of repeat CEMI-5 and repeat CELID-6 customers. Please explain why the Company selected this methodology and how it is expected to better incentivize improved reliability for customers experiencing frequent or long-duration outages. Response: The Company’s proposed Customer Reliability PIM shares the same core purpose as the customer reliability PIM in the RE02 Proposed Final Decision, which is that this PIM should encourage the Company to reduce repeat customers that experience long-duration interruptions and/or frequent interruptions. As explained in Exh. CLP-TSP-1, at 81-83, the Company proposes that the customer reliability PIM be calculated as the total number of repeat CEMI-5 customers and repeat CELID-6 customers. This slightly deviates from the customer reliability PIM in the RE02 Proposed Final Decision to ensure that the PIM measures performance based on factors within the Company’s control and encourages the Company to reduce the repeat customers with long-duration interruptions and frequent interruptions. The RE02 Proposed Final Decision contemplated Customer Reliability PIM based on a composite of four sub-metrics: (1) total number of CEMI-5 customers; (2) the percent of repeat CEMI-5 customers; (3) total number of CELID-6 customers; (4) and the percent of repeat CELID-6 customers. The Company’s Customer Reliability PIM is focused on repeat customers because the frequency and/or duration of interruptions for CEMI-5 and/or CELID-6 customers in a particular year can be due to one-off events without repeat in a subsequent year. In other words, while CEMI-5 and CELID-6 represent edge cases of performance, isolated events that result in CEMI-5 or CELID-6 customers should not all be actionable as those events would drive investment to resolve largely isolated or infrequent events. However, customers that experience long duration or frequent service interruptions in multiple years should be addressed by the Company, since these situations are more likely to be due to systemic issues. Accordingly, the Company has designed the PIM to focus on repeat CEMI-5 and CELID-6 customers.
  7. Page 17 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-525 Page 2 of 2 In addition, the composite metric proposed in the RE02 Proposed Final Decision could have unintended consequences due to the disproportionate scale of the submetrics. The percent of repeat CEMI-5 and repeat CELID-6 are numerically much smaller than submetric (a) and do not meaningfully impact the value of the composite metric. Therefore, the proposed customer reliability PIM in the RE02 Proposed Final Decision would be driven by annual CEMI-5 and CELID-6 customers, rather than repeat customers. The Company’s historical data shows that annual CEMI-5 and CELID-6 customer counts are orders of magnitude higher than repeat CEMI5/CELID-6 customers, because of the isolated events discussed above. Also, Company data shows that annual CEMI-5 and CELID-6 customers have large year-to-year variability. Therefore, the customer PIM identified in the RE02 Proposed Final Decision could reward the Company for CEMI-5 and/or CELID-6 reductions driven by random events rather than driven by targeted investments to reduce repeat service interruptions, which is more tailored result that the Company’s proposed customer reliability PIM would achieve.
  8. Page 18 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-526 Page 1 of 3 Date Filed: September 15, 2026 Witness: Elli Ntakou and Lavelle A. Freeman Request from: Office of Consumer Counsel Question: Targeted System Performance Plan Exhibit CLP-TSP-1: Reliability PIMs Please provide any analysis comparing the Company’s proposed Customer Reliability PIM methodology with the methodology identified in RE02. In particular, please identify whether the Company could earn an incentive under its proposed methodology in a year in which: a.the total number or percentage of customers experiencing CEMI-5 increases; b.the total number or percentage of customers experiencing CELID-6 increases; or c.either measure worsens for particular customer groups or geographic areas. Response: As explained in response to OCC-525 i, the Company’s proposed Customer Reliability PIM methodology is intended to encourage the Company to reduce the number of repeat CEMI-5 and CELID-6 customers, while avoiding the unintended consequence of RE02 PIM, such as rewarding the Company for random events that impact the number of CEMI-5 or CELID-6 customers in a single year. a. Based on the Company’s proposed PIM, if the total number of CEMI-5 customers increases, but there are fewer repeat CEMI-5 customers, then the Company can earn an incentive, assuming all else remains equal. This is reasonable because increased CEMI-5 annual customers with reduced overlap with the previous year’s CEMI-5 customers means that the additional CEMI-5 customers are not due to long-term underperformance, which aligns with what a well-designed customer reliability PIM should target, per the RE02 Proposed Final Decision. However, under the RE02 PIM, an increase of CEMI-5 customers can also lead to the Company earning an incentive if the CELID-6 customer reduction is higher than the CEMI-5 customer increase. As explained in OCC-525, the reductions of these annual metrics are not necessarily tied to Company investments. The components of the proposed composite metric reflecting repeat customers in the RE02 Proposed Final Decision are mathematically insignificant to the calculated value of the metric. b. Based on the Company’s proposed PIM, if the total number of CELID-6 customers increases, while there are less repeat CELID-6 customers, then the Company can earn an incentive, assuming all else remains equal. This is reasonable; increased CELID-6 annual customers with reduced overlap with the previous year’s CELID-6 customers means that the additional CELID-6 customers are not due to long-term underperformance, which
  9. Page 19 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-526 Page 2 of 3 aligns with what a well-designed customer reliability PIM should target, per the RE02 Proposed Final Decision. However, under the RE02 PIM an increase of CELID-6 customers can also lead to the Company earning an incentive if the CEMI-5 customer reduction is higher than the CELID-6 customer increase. As explained in OCC-525, the reductions of these annual metrics are not necessarily tied to Company investments. The components of the proposed composite metric reflecting repeat customers in the RE02 Proposed Final Decision are mathematically insignificant to the calculated value of the metric. c. Yes, because both the Company’s proposed Customer Reliability PIM and the customer reliability PIM in the RE02 Proposed Final Decision are calculated for the Company’s territory and across all customers. As explained above, as a composite metric, both the Company’s proposed PIM and the RE02 PIM, could result in an incentive, in circumstances where performance under any one submetric worsens and performance in other submetrics significantly improves. The primary difference between the Company’s proposed Customer Reliability PIM and the RE02 Proposed Final Decision is under the Company’s proposed PIM, the Company cannot earn an incentive unless there is a reduction in either the repeat CEMI-5 or CELID-6 customers. Under the RE02 PIM, however, the Company could earn an incentive if there is an increase in repeat CEMI-5 and CELID-6 customers because the RE02 metric is driven by total number of CEMI-5 and CELID-6 customers. As discussed in response to OCC 525, the RE02 PIM can be influenced heavily by random events, rather than Company investments to reduce otherwise repeat CEMI-5 and CELID6 customers. Further, it is not clear what the phrase “particular customer groups and geographic areas” refers to. Customer reliability PIMs based on repeat CEMI-5 and CELID-6 should not be calculated more granularly than at the Company level and across all customers. Multiple PIMs per customer groups or small geographic areas would be largely impractical and inactionable, as circuits and projects to improve customer reliability include various customer groups and could span multiple geographic areas. PIMs also typically need large enough numbers to establish a baseline and a meaningful decrease. In other words, targeting to decrease single digits of customers is not conducive to PIMs and incentives. Prior Referenced Response: OCC-525 Question: Targeted System Performance Plan Exhibit CLP-TSP-1: Reliability PIMs The final RE02 Performance Evaluation System identifies a potential Customer Reliability PIM based on CEMI-5, the percentage of repeat CEMI-5 customers, CELID-6, and the percentage of repeat CELID-6 customers. The Company instead proposes to use the average count of repeat CEMI-5 and repeat CELID-6 customers. Please explain why the Company selected this methodology and how it is expected to better incentivize improved reliability for i
  10. Page 20 of 73

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-12 Date Issued September 01, 2026 OCC-526 Page 3 of 3 customers experiencing frequent or long-duration outages. OCC-525 Response: The Company’s proposed Customer Reliability PIM shares the same core purpose as the customer reliability PIM in the RE02 Proposed Final Decision, which is that this PIM should encourage the Company to reduce repeat customers that experience long-duration interruptions and/or frequent interruptions. As explained in Exh. CLP-TSP-1, at 81-83, the Company proposes that the customer reliability PIM be calculated as the total number of repeat CEMI-5 customers and repeat CELID-6 customers. This slightly deviates from the customer reliability PIM in the RE02 Proposed Final Decision to ensure that the PIM measures performance based on factors within the Company’s control and encourages the Company to reduce the repeat customers with long-duration interruptions and frequent interruptions. The RE02 Proposed Final Decision contemplated Customer Reliability PIM based on a composite of four sub-metrics: (1) total number of CEMI-5 customers; (2) the percent of repeat CEMI-5 customers; (3) total number of CELID-6 customers; (4) and the percent of repeat CELID-6 customers. The Company’s Customer Reliability PIM is focused on repeat customers because the frequency and/or duration of interruptions for CEMI-5 and/or CELID-6 customers in a particular year can be due to one-off events without repeat in a subsequent year. In other words, while CEMI-5 and CELID-6 represent edge cases of performance, isolated events that result in CEMI-5 or CELID-6 customers should not all be actionable as those events would drive investment to resolve largely isolated or infrequent events. However, customers that experience long duration or frequent service interruptions in multiple years should be addressed by the Company, since these situations are more likely to be due to systemic issues. Accordingly, the Company has designed the PIM to focus on repeat CEMI-5 and CELID-6 customers. In addition, the composite metric proposed in the RE02 Proposed Final Decision could have unintended consequences due to the disproportionate scale of the submetrics. The percent of repeat CEMI-5 and repeat CELID-6 are numerically much smaller than submetric (a) and do not meaningfully impact the value of the composite metric. Therefore, the proposed customer reliability PIM in the RE02 Proposed Final Decision would be driven by annual CEMI-5 and CELID-6 customers, rather than repeat customers. The Company’s historical data shows that annual CEMI-5 and CELID-6 customer counts are orders of magnitude higher than repeat CEMI-5/CELID-6 customers, because of the isolated events discussed above. Also, Company data shows that annual CEMI-5 and CELID-6 customers have large year-to-year variability. Therefore, the customer PIM identified in the RE02 Proposed Final Decision could reward the Company for CEMI-5 and/or CELID-6 reductions driven by random events rather than driven by targeted investments to reduce repeat service interruptions, which is more tailored result that the Company’s proposed customer reliability PIM would achieve.

Text of OCC Set 11_COMBINED.pdf

Extracted from the file · 48 pages · 62,469 characters

Text of OCC Set 10_COMBINED.pdf

Extracted from the file · 51 pages · 90,368 characters

Text of OCC Set 5_COMBINED.pdf

Extracted from the file · 46 pages · 88,105 characters

Text of OCC Set 4_COMBINED.pdf

Extracted from the file · 159 pages · 268,038 characters

Text of OCC Set 3_COMBINED.pdf

Extracted from the file · 93 pages · 113,517 characters

Text of OCC Set 2_COMBINED.pdf

Extracted from the file · 68 pages · 113,929 characters

Text of OCC Set 1_COMBINED.pdf

Extracted from the file · 139 pages · 225,320 characters

Text of OCC Set 14_COMBINED.pdf

Extracted from the file · 66 pages · 143,197 characters

As listed on the current system

Corres. 09/29/2026 [26-05-10] (Keegan Werlin LLP) - Compilations of discovery responses

This filing on the current system (opens in a new tab)