The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 37 of 106 1 you to provide the heating validation model to show 2 performance at cold temperatures on the system. 3 you did so as GKJ-15C. And Does this all ring a bell? 4 WITNESS JONES: Yep. 5 COMMISSIONER GILMAN: So I just wanted to 6 confirm a few things. So it looks like what you had 7 provided in GKJ-15C -- and it is confidential. 8 don't need to pull it up. 9 provided was one hydraulic model for the entire 10 mountains, which would be like the complements of all 11 of those. 12 three of these things we have painfully been 13 through -- their connection. We But it looks like what you I think the mountains technically is all So is that accurate? 14 WITNESS JONES: That is correct. 15 COMMISSIONER GILMAN: Okay. Is there any 16 more granular validation that the Company has done 17 specific to the Eastern Mountain Gas System rather 18 than the entire mountain system at large? WITNESS JONES: 19 No. So we modeled those 20 three systems because of the interplay between them. 21 That null point can shift as demand grows on our 22 system. 23 from the west, it makes for a more comprehensive 24 model if we evaluate them all together. 25 And because we are physically receiving gas That being said, so the results of what we 37Page 38 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 38 of 106 1 showed, showed that the percent variation was less 2 than 5 percent, which is incredibly good. 3 thing that we do is we look at every single major 4 pressure point to also validate that, which is done 5 within the model, kind of. 6 and a pressure within the model. 7 paper, necessarily. 8 isn't any large variance at any point. The other We have like a reference So it's not a work But also, to confirm that there So all of that to say you can infer that a 9 10 good model match on the entire mountains also 11 included a really detailed modeled match on every 12 single point within that system including the Eastern 13 Mountain Gas System. COMMISSIONER GILMAN: 14 How many points are 15 there like within the Eastern Mountain Gas System 16 that would kind of -- I got kind of conflicting 17 information on this in the past. 18 actual points are there where you have granular flow 19 data that you can reference then to validate? WITNESS JONES: 20 I mean, how many That's a great question. 21 I do not have the number off the top of my head. 22 if I had to guess, I would think doing some mental 23 math -COMMISSIONER GILMAN: 24 25 dozens? Is it once? But Is it Is it hundreds? 38Page 39 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 39 of 106 1 WITNESS JONES: Dozens, yeah. 2 COMMISSIONER GILMAN: So we are in the 3 ballpark. I just want to understand like the scale 4 of what you can actually validate. 5 And then within that GKJ-15C validation 6 that you provided, the temperatures that were used 7 for that validation, both from 2023, were at negative 8 7 degrees Farenheit and negative 15 degrees 9 Farenheit. Does that sound right? 10 WITNESS JONES: 11 COMMISSIONER GILMAN: 12 13 That sounds correct. Do you know where that temperature was modeled or was observed? WITNESS JONES: That would have correlated 14 to the Dillon station, which correlates to the 15 station that is used as part of our design day 16 methodology. 17 COMMISSIONER GILMAN: Okay. And is there 18 any recording as to the temperatures in other 19 portions of the mountains, or it's just a single 20 point temperature? 21 WITNESS JONES: There may be other 22 recordings in SCADA. But the reason we use a Dillon 23 temperature as kind of like our honing in temperature 24 is because that is what we calibrate the model to for 25 our negative 39 design day temperature. 39Page 40 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 40 of 106 1 So it is important speaking 2 apples-to-apples so that when we scale it to a design 3 day temperature, it is still accurate 4 COMMISSIONER GILMAN: And then curious, do 5 you have any data for validation that's closer to the 6 design day temperature? 7 and negative 15 degrees Farenheit are kind of a world 8 apart from negative 39 degrees Farenheit to like 9 understand if the behavior is still predictable. 10 I mean, clearly negative 7 So just wanted to understand what you have 11 for validation that might be closer to the design 12 temperature. 13 WITNESS JONES: So typically when we pick 14 a temperature, it has to be a temperature that 15 occurred, obviously, because we are comparing it to 16 observed field data. 17 is my recollection that the coldest temperature was 18 that negative 7 -- am I saying the right number? 19 20 21 So for that particular year, it COMMISSIONER GILMAN: Negative 7 and negative 15, I think. WITNESS JONES: Thank you. So negative 15 22 was the coldest temperature that occurred at that 23 Dillon station in that year. 24 done every single year. 25 would have been what is the coldest temperature that That being said, it's So the next heating season 40Page 41 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 41 of 106 1 occurred that heating season. COMMISSIONER GILMAN: 2 Okay, okay. And I 3 think Mr. Skluzak pointed to an occurrence that is 4 negative 26 degrees Farenheit? 5 yesterday. 6 comparative SCADA data and actual hydraulic 7 performance for that event. So I was wondering if the Company has any WITNESS JONES: 8 I think we heard that We are actually in the 9 middle of model verification. As you know, it is 10 annual. 11 we are currently doing our model verification for the 12 mountain system. 13 believe in the Settlement Agreement, we agreed to 14 provide updated hydraulic results every single year, 15 and so that's certainly something that's reasonable 16 to provide as part of that. And since that happened last heating season, So nothing to report today. COMMISSIONER GILMAN: 17 Okay. But I I think that 18 would be very helpful to kind of continue to get 19 updates here, especially as we like progress this 20 discussion. 21 You are probably aware, a lot of the 22 critiques that came in during answer testimony are 23 not around the negative 7 degree temperature range. 24 It is around the, you know, colder than negative 13, 25 colder than negative 15, is it still linear 41Page 42 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 42 of 106 1 2 performance? And so hard to say with data that is still 3 in like a pretty normal cold range, honestly. 4 understood you have to see the temperature, but the 5 whole argument for negative 39 is you have seen the 6 temperature, right? 7 But So, ideally -- WITNESS JONES: Right. That temperature 8 definitely was observed. That is a probability that 9 it could occur again. 10 other line of questions on design day methodology, so 11 maybe I'll save my comments there. And I'm sure we have a whole 12 COMMISSIONER GILMAN: We will get to that. 13 So just curious, like in the recent past, 14 understanding -- so for 2023, it seems like the 15 coldest you had was negative 7, negative 15. 16 the rest of kind of the recent past, what is the 17 closest you've got on model validation that would 18 bring us far closer to the design temperature to 19 really deal with some of these critiques that we 20 could see atypical growth or performance in the use 21 of gas past some of these certain somewhat reasonable 22 -- once we get into very unreasonable cold 23 temperatures? 24 25 WITNESS JONES: But in I think the reason Mr. Skluzak -- well, I can't speak for him -- but 42Page 43 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 43 of 106 1 points out that negative 26 number is it's a pretty 2 cold temperature and one of the coldest that we have 3 experienced in the recent heating season. So like I said, I don't have the model 4 5 validation in front of me today, but I do think that 6 we are -- not excited, but we are looking forward to 7 seeing the results of that negative 26 because, like 8 you said, it is much closer to negative 39 than, say, 9 negative 15 was. 10 that soon. 11 So we should have model results on COMMISSIONER GILMAN: Okay. Excellent. 12 So for snow melt loads -- and just to be clear, I 13 just want to make sure, does everyone understand what 14 we are talking about when we talk about snow melt? 15 WITNESS JONES: Yes. 16 COMMISSIONER GILMAN: Okay. Boiler, tubes 17 underground, like how it would heat your house, but 18 there is no house. 19 WITNESS JONES: Right. 20 COMMISSIONER GILMAN: So for snow melt, 21 Mr. Takahashi indicated that the building codes in 22 many cases actually require a cold weather cutoff to 23 stop snow melt from running at such extreme 24 temperatures due to the potential for kind of like 25 immediate cause of brand new ice. 43Page 44 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 44 of 106 1 And I was just curious if the Company has 2 any further insights or modeling validation into the 3 performance of that like as a specific end use? WITNESS JONES: 4 We don't have any modeling 5 for snow melt. And I might invite either witness 6 Klemm or Mann to help me with the second part of this 7 question. But as part of the potential study, we did 8 9 do a disaggregation of end use, which was in that 10 GKJ-2 that was just pulled up. 11 was determined that the design day peak hour gas 12 demand impact of snow melt is pretty low, which 13 would, you know, support that it is not necessarily a 14 major end use during design day conditions. 15 COMMISSIONER GILMAN: And I believe that it And can I just ask 16 you -- and that was largely based upon the survey of 17 the mountain -- of what was called the mountains, 18 which is different than the Eastern Mountain Gas 19 System? WITNESS JONES: 20 Maybe -- Jordan, would you 21 mind just confirming for me that that was based on 22 the survey results, or was it something else? WITNESS MANN: 23 Yeah. So there is a few 24 pieces. One is the survey that we conducted. And we 25 found that for residential customers, very few have 44Page 45 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 45 of 106 1 snow melt systems based on our survey results. 2 commercial sector did have more snow melt than 3 residential as a percent of our survey respondents. 4 The But given the concerns around refreeze 5 both in codes and manufacturer specifications in snow 6 melt systems, they tend to not operate at very low 7 temperatures. 8 measure that had potential. 9 And so they were screened out as a We did consider that something that could 10 be explored from a demand response perspective for 11 commercial customers. 12 potential reduction, it's not a measure that we did a 13 deep analysis on to include in the NPA measure set. 14 But given the low amount of COMMISSIONER GILMAN: So you are saying 15 you screened them out as a measure because the 16 presumption, especially from kind of building code 17 argument and your understanding of the control 18 system, is that they already lock out, at least in 19 some part, at these extreme cold temperatures? 20 WITNESS MANN: That's correct. 21 COMMISSIONER GILMAN: There may not be 22 like an incremental reduction. But wouldn't that 23 mean -- you know, given the Company's methodology or 24 understanding that essentially load just continues -- 25 or I should say demand just continues to increase 45Page 46 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 46 of 106 1 linearly as the ambient temperature decreases, if you 2 believe that the controls and temperature cutout is a 3 fairly prevalent thing, wouldn't that mean that those 4 particular loads actually do not continue to increase 5 linearly as the ambient temperature decreases but 6 actually fall away to zero at some point? WITNESS MANN: 7 My understanding based on 8 looking at manufacturer specifications is that the 9 lockout temperature is around zero degrees Farenheit. 10 So there should be some data available below that 11 temperature. Additionally, the majority -- vast 12 13 majority of the load that is observed for the peak 14 hour conditions comes from space heating. 15 there might be some component of it that is 16 nonlinear, but the vast majority of the consumption 17 is going to be coming from the heating of space and 18 not sidewalks. COMMISSIONER GILMAN: 19 And so In a broader sense, 20 according to your survey results -- if the proportion 21 of snow melt in your survey results is accurate, 22 right? 23 WITNESS MANN: 24 COMMISSIONER GILMAN: 25 Yep, that's fair. Okay. And then did you do any -- I think the answer is no, but I just 46
As listed on the current system
Question(s) Answered 11 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 08/27/2026