The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 41 of 106 1 occurred that heating season. COMMISSIONER GILMAN: 2 Okay, okay. And I 3 think Mr. Skluzak pointed to an occurrence that is 4 negative 26 degrees Farenheit? 5 yesterday. 6 comparative SCADA data and actual hydraulic 7 performance for that event. So I was wondering if the Company has any WITNESS JONES: 8 I think we heard that We are actually in the 9 middle of model verification. As you know, it is 10 annual. 11 we are currently doing our model verification for the 12 mountain system. 13 believe in the Settlement Agreement, we agreed to 14 provide updated hydraulic results every single year, 15 and so that's certainly something that's reasonable 16 to provide as part of that. And since that happened last heating season, So nothing to report today. COMMISSIONER GILMAN: 17 Okay. But I I think that 18 would be very helpful to kind of continue to get 19 updates here, especially as we like progress this 20 discussion. 21 You are probably aware, a lot of the 22 critiques that came in during answer testimony are 23 not around the negative 7 degree temperature range. 24 It is around the, you know, colder than negative 13, 25 colder than negative 15, is it still linear 41Page 42 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 42 of 106 1 2 performance? And so hard to say with data that is still 3 in like a pretty normal cold range, honestly. 4 understood you have to see the temperature, but the 5 whole argument for negative 39 is you have seen the 6 temperature, right? 7 But So, ideally -- WITNESS JONES: Right. That temperature 8 definitely was observed. That is a probability that 9 it could occur again. 10 other line of questions on design day methodology, so 11 maybe I'll save my comments there. And I'm sure we have a whole 12 COMMISSIONER GILMAN: We will get to that. 13 So just curious, like in the recent past, 14 understanding -- so for 2023, it seems like the 15 coldest you had was negative 7, negative 15. 16 the rest of kind of the recent past, what is the 17 closest you've got on model validation that would 18 bring us far closer to the design temperature to 19 really deal with some of these critiques that we 20 could see atypical growth or performance in the use 21 of gas past some of these certain somewhat reasonable 22 -- once we get into very unreasonable cold 23 temperatures? 24 25 WITNESS JONES: But in I think the reason Mr. Skluzak -- well, I can't speak for him -- but 42Page 43 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 43 of 106 1 points out that negative 26 number is it's a pretty 2 cold temperature and one of the coldest that we have 3 experienced in the recent heating season. So like I said, I don't have the model 4 5 validation in front of me today, but I do think that 6 we are -- not excited, but we are looking forward to 7 seeing the results of that negative 26 because, like 8 you said, it is much closer to negative 39 than, say, 9 negative 15 was. 10 that soon. 11 So we should have model results on COMMISSIONER GILMAN: Okay. Excellent. 12 So for snow melt loads -- and just to be clear, I 13 just want to make sure, does everyone understand what 14 we are talking about when we talk about snow melt? 15 WITNESS JONES: Yes. 16 COMMISSIONER GILMAN: Okay. Boiler, tubes 17 underground, like how it would heat your house, but 18 there is no house. 19 WITNESS JONES: Right. 20 COMMISSIONER GILMAN: So for snow melt, 21 Mr. Takahashi indicated that the building codes in 22 many cases actually require a cold weather cutoff to 23 stop snow melt from running at such extreme 24 temperatures due to the potential for kind of like 25 immediate cause of brand new ice. 43Page 44 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 44 of 106 1 And I was just curious if the Company has 2 any further insights or modeling validation into the 3 performance of that like as a specific end use? WITNESS JONES: 4 We don't have any modeling 5 for snow melt. And I might invite either witness 6 Klemm or Mann to help me with the second part of this 7 question. But as part of the potential study, we did 8 9 do a disaggregation of end use, which was in that 10 GKJ-2 that was just pulled up. 11 was determined that the design day peak hour gas 12 demand impact of snow melt is pretty low, which 13 would, you know, support that it is not necessarily a 14 major end use during design day conditions. 15 COMMISSIONER GILMAN: And I believe that it And can I just ask 16 you -- and that was largely based upon the survey of 17 the mountain -- of what was called the mountains, 18 which is different than the Eastern Mountain Gas 19 System? WITNESS JONES: 20 Maybe -- Jordan, would you 21 mind just confirming for me that that was based on 22 the survey results, or was it something else? WITNESS MANN: 23 Yeah. So there is a few 24 pieces. One is the survey that we conducted. And we 25 found that for residential customers, very few have 44Page 45 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 45 of 106 1 snow melt systems based on our survey results. 2 commercial sector did have more snow melt than 3 residential as a percent of our survey respondents. 4 The But given the concerns around refreeze 5 both in codes and manufacturer specifications in snow 6 melt systems, they tend to not operate at very low 7 temperatures. 8 measure that had potential. 9 And so they were screened out as a We did consider that something that could 10 be explored from a demand response perspective for 11 commercial customers. 12 potential reduction, it's not a measure that we did a 13 deep analysis on to include in the NPA measure set. 14 But given the low amount of COMMISSIONER GILMAN: So you are saying 15 you screened them out as a measure because the 16 presumption, especially from kind of building code 17 argument and your understanding of the control 18 system, is that they already lock out, at least in 19 some part, at these extreme cold temperatures? 20 WITNESS MANN: That's correct. 21 COMMISSIONER GILMAN: There may not be 22 like an incremental reduction. But wouldn't that 23 mean -- you know, given the Company's methodology or 24 understanding that essentially load just continues -- 25 or I should say demand just continues to increase 45Page 46 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 46 of 106 1 linearly as the ambient temperature decreases, if you 2 believe that the controls and temperature cutout is a 3 fairly prevalent thing, wouldn't that mean that those 4 particular loads actually do not continue to increase 5 linearly as the ambient temperature decreases but 6 actually fall away to zero at some point? WITNESS MANN: 7 My understanding based on 8 looking at manufacturer specifications is that the 9 lockout temperature is around zero degrees Farenheit. 10 So there should be some data available below that 11 temperature. Additionally, the majority -- vast 12 13 majority of the load that is observed for the peak 14 hour conditions comes from space heating. 15 there might be some component of it that is 16 nonlinear, but the vast majority of the consumption 17 is going to be coming from the heating of space and 18 not sidewalks. COMMISSIONER GILMAN: 19 And so In a broader sense, 20 according to your survey results -- if the proportion 21 of snow melt in your survey results is accurate, 22 right? 23 WITNESS MANN: 24 COMMISSIONER GILMAN: 25 Yep, that's fair. Okay. And then did you do any -- I think the answer is no, but I just 46Page 47 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 47 of 106 1 want to confirm. Given especially that Breckenridge 2 is kind of the most acute shortage and issue to find, 3 do you think that the amount of snow melt found in 4 aggregate in the rest of the mountains is 5 representative of the proportion that would be found 6 in Breckenridge, specifically? WITNESS MANN: 7 We did not specifically 8 disaggregate Breckenridge from the rest of the group. 9 The number was low enough -- I think it was less than 10 2 percent on the residential side -- that even if the 11 number were higher in Breckenridge by a factor of 2, 12 it may still not be consequential. 13 a follow-up separate analysis or survey for 14 Breckenridge specifically, no. COMMISSIONER GILMAN: 15 But we did not do Okay. Are you 16 familiar with some of the statements from the 17 Mountain Community Coalition that they believe snow 18 melt is significantly more prevalent, especially in 19 Breckenridge, than what is represented? 20 WITNESS MANN: I believe -- 21 COMMISSIONER GILMAN: 22 WITNESS MANN: Amongst residential. I am familiar with those 23 comments. I believe that they also did acknowledge 24 the lockout temperature issue that might result in 25 annual savings being available, but peak hour gas 47Page 48 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 48 of 106 1 saving potentially not being available. COMMISSIONER GILMAN: 2 3 I went on a snow melt tangent. 4 WITNESS MANN: 5 COMMISSIONER GILMAN: 6 Okay. No worries. A couple questions on LDCs and kind of the relationship. So based on your supplemental direct 7 8 response, as I understand it, there are just two LDC 9 receipt points in the Eastern Mountain Gas System, 10 Tungsten -- did I say that right? 11 Hill, and Blue River, both of which serve Colorado 12 Natural Gas; is that accurate? 13 WITNESS JONES: 14 COMMISSIONER GILMAN: Tungsten, Dory Correct. And the Company 15 responded -- because I think I had requested sales 16 and design day peak hour demand growth over the 17 five-year period that is kind of being referred to as 18 the growth period that caused the need for the 19 project. 20 have sales and design day peak hour demand growth for 21 that period, or I think at all. 22 And the Company responded that it does not WITNESS JONES: Is that accurate? Right, we did not approve 23 any MDQ, which is the contractual amount, during that 24 five-year previous period 25 COMMISSIONER GILMAN: So the contracted 48Page 49 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 49 of 106 1 maximum daily quantity has remained constant over 2 that time; is that correct? 3 WITNESS JONES: That is correct. 4 COMMISSIONER GILMAN: Okay. I think it 5 was a little confusing to me because it seemed, in 6 part, in the direct case like part of the reasoning 7 was some growth in LDC load, but it sounds like there 8 was no requested growth in the LDC load over that 9 time period. Is that fair? WITNESS JONES: 10 So I can clarify. So we 11 did not approve any incremental maximum daily 12 quantity values for LDCs in the previous five years. 13 In our hydraulic analysis, we did assume 14 some incremental LDC growth. And the reason that we 15 did that is because, while we didn't approve it, we 16 did recognize that there could be a future need for 17 LDCs to increase their maximum daily quantity. 18 we wanted to understand how that would impact the 19 overall Mountain Energy Project. And That being said, in my rebuttal testimony, 20 21 we ultimately removed that load because we haven't 22 heard from any LDC customers that they are interested 23 in MDQ increases at this time. 24 know, do a thorough analysis, we would remove it from 25 rebuttal. So I thought to, you 49Page 50 of 106
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued August 13, 2026 CLF-011 Attachment 20 Page 50 of 106 COMMISSIONER GILMAN: 1 Okay. That was my 2 next question. Have you heard from any of them if 3 they want more? No. Do you have any knowledge as to their 4 5 actual infrastructure, if they could accept more, if 6 it is that simple, or if they have actual 7 infrastructure upgrades that would have to be made to 8 even accept more quantity? 9 WITNESS JONES: I don't have any 10 information about their infrastructure. 11 was more like a nod that we appreciate the fact that 12 the backbone of our system is the only way that they 13 have currently to transport gas to their system. 14 so there is a future in which they could potentially 15 need additional MDQ in order to serve their 16 customers. COMMISSIONER GILMAN: 17 Okay. I think it And And so it 18 sounds like with the settlement, the concept of 19 charging LDCs served by the system for increases in 20 contract capacity on a going forward basis is still 21 alive. 22 That is still the rough plan, right, is 23 that if an LDC served off the Eastern Mountain Gas 24 System were to come and ask for an increase in their 25 capacity, then they would be charged a portion of 50