Interrogatory responses
Answers to questions 26, 28, 29, 33, 34, 37, 38, 40
Files10
BETP-026_Final.pdf
PDF · 174 KB · 5 pagesText searchable
Download BETP-026_Final.pdfRead the text of BETP-026_Final.pdf
BETP-028_Final.pdf
PDF · 125 KB · 2 pagesText searchable
Download BETP-028_Final.pdfRead the text of BETP-028_Final.pdf
BETP-029_Final.pdf
PDF · 100 KB · 2 pagesText searchable
Download BETP-029_Final.pdfRead the text of BETP-029_Final.pdf
BETP-033_Final.pdf
PDF · 81 KB · 1 pageText searchable
Download BETP-033_Final.pdfRead the text of BETP-033_Final.pdf
BETP-033 Attachment 1.pdf
PDF · 930 KB · 7 pagesText searchable
Download BETP-033 Attachment 1.pdfRead the text of BETP-033 Attachment 1.pdf
BETP-034_Final.pdf
PDF · 84 KB · 1 pageText searchable
Download BETP-034_Final.pdfRead the text of BETP-034_Final.pdf
BETP-037_Final.pdf
PDF · 80 KB · 1 pageText searchable
Download BETP-037_Final.pdfRead the text of BETP-037_Final.pdf
BETP-038_Final.pdf
PDF · 79 KB · 1 pageText searchable
Download BETP-038_Final.pdfRead the text of BETP-038_Final.pdf
BETP-038 Attachment 1.pdf
PDF · 1.8 MB · 31 pagesText searchable
Download BETP-038 Attachment 1.pdfRead the text of BETP-038 Attachment 1.pdf
BETP-040_Final.pdf
PDF · 96 KB · 1 pageText searchable
Download BETP-040_Final.pdfRead the text of BETP-040_Final.pdf
Text of BETP-033_Final.pdf
Extracted from the file · 1 page · 1,388 characters
Text of BETP-033 Attachment 1.pdf
Extracted from the file · 7 pages · 14,274 characters
Text of BETP-034_Final.pdf
Extracted from the file · 1 page · 1,700 characters
Text of BETP-037_Final.pdf
Extracted from the file · 1 page · 999 characters
Text of BETP-038_Final.pdf
Extracted from the file · 1 page · 1,030 characters
Page 15 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 15 of 31 Step 4: Develop Risk Problem Statements In Step 3, specific information was collected on the threat, vulnerability, and consequence of select Risk Scenarios—hypothetical situations involving specific threats to specific energy infrastructure assets or systems. For each Risk Scenario, this information may be summarized using the Risk Assessment Template (see Exhibit 3) to develop a Risk Problem Statement that clearly describes and details the threat, vulnerability, and consequence of the Risk Scenario. An example of a Risk Problem Statement is presented in Exhibit 5 below. Risk Problem Statements should be developed for each of the Risk Scenarios evaluated as part of the Risk Assessment.Page 16 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 16 of 31 Exhibit 5. Example Risk Problem Statement Risk Scenario A: 2-foot Flooding /Big State City Substations THREAT VULNERABILITY CONSEQUENCE RISK The Big State River in the southern district of Big State City has flooded three times over the past 20 years, including twice in the past 5 years with river levels reaching as high as 1.5 feet above flood stage during the 2021 flood event. Flooding has occurred more frequently in recent years due to new developments impacting stormwater drainage in Big State City and due to more frequent high-precipitation rainfall events. According to current climate projections, heavy rainfall events are expected to occur more frequently in the future, increasing the threat to assets located in the floodplain. Current flood prevention measures at Big State Utility’s electric power substations in the southern district of Big State City are sufficient to prevent flooding when river levels are up to 2 feet above flood stage. Beyond 2 feet, existing flood prevention measures would be insufficient to protect the facility, which would be severely damaged if fully inundated. Repairs to inundated substation infrastructure would likely take several weeks to fully repair. Big State Utility estimates that 5 of its high-voltage substations (69-kV+) are potentially exposed to the flood threat and that these substations serve a total of approximately 100,000 customers in the southern district of Big State City. Simultaneous loss of all 5 substations would leave about 25% of Big State City without power, including the downtown commercial district and Big State City Hospital, which is the largest of three hospitals in Big State City. Big State City Hospital has an emergency backup generator capable of serving critical facility loads, but this generator can only operate for approximately 48 hours before refueling. If flooding along the Big State River exceeds 2 feet, existing flood protections could be exceeded at approximately five Big State Utility high-voltage substations that serve the southern district of Big State City, potentially disrupting power supply to the downtown commercial district, including Big State City Hospital.Page 17 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 17 of 31 Step 5: Calculate Risk Scores The final step in Risk Assessment is to develop ranks, scores, or tiered ratings for each Risk Scenario using information detailed in the Risk Problem Statements. Calculating Risk Scores allows Risk Scenarios to be compared with one another on a consistent basis, which may help inform the Risk Mitigation Approach and other planning activities. While there are many ways to calculate Risk Scores or ratings, it is important that whatever method used be consistently applied across Risk Scenarios. This guidebook provides a simple approach that: • • • Assesses a relative score/rating to each of the three risk components that make up the Risk Assessment formula (threat, vulnerability, and consequence) for each Risk Scenario. Calculates a total Risk Score for each Risk Scenario by multiplying the component scores in the Risk Assessment formula (see Exhibit 1 in the chapter on Risk Assessment Framework). Compares the total Risk Scores for each Risk Scenario in a table or Risk Matrix. This approach may be expanded to include additional risk components, utilize different rating scales or component weightings, or other adjustments that take state-specific situations and priorities into account. For example, some states may choose to expand the consequence component into separate direct and indirect consequence components. Whatever the choice of methodology, any factors, scales, or weightings used should be clearly explained when Documenting the Risk Assessment. ASSESSING COMPONENT SCORES Assigning scores for each of the key risk components requires the use of clearly defined scales that relate to underlying quantitative metrics (e.g., annual event probability) or qualitative descriptors. Risk scales can correspond to the underlying metrics in various ways, including uniform scales, adjusted uniform scales, and “rough order of magnitude” scales. Examples of three different 5-point threat scales based on underlying annual threat probabilities are shown in Exhibit 6, and the various methods for scaling are discussed below the exhibit. The scales presented in this chapter correspond to underlying metrics, many of which may be difficult to assess with precision. Given the inherent uncertainty in this activity, this guidebook suggests using scales that group Risk Scenarios into tiers that correspond to wide ranges in the underlying metrics. Exhibit 6. Threat Probability Assessment Using Different Quantitative Scaling Options Category Annual Threat Probability (% per year) Score Tier Uniform Scale Adjusted Uniform Scale Rough Order of Magnitude Scale 1 Low 0%-20% 0%-10% <1% 2 Med-Low 20%-40% 10%-20% 1%-5% 3 Medium 40%-60% 20%-30% 5%-15% 4 Med-High 60%-80% 30%-40% 15%-35% 5 High 80%-100% >40% >35%Page 18 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 18 of 31 In Exhibit 6 the uniform scale is perfectly scaled to the maximum value of 100% with each 20% increase in the annual threat probability associated with a one-point or one-level increase on the threat scale. The adjusted uniform scale shown in the exhibit is similar to the uniform scale except the levels are set to allow for more differentiation at lower probabilities (in this case, below 40%), reflecting where the majority of the underlying data lies. How to adjust a uniform scale to fit the underlying data is a matter of judgement. The third approach shown in the exhibit is the rough order of magnitude approach, which uses uneven changes in the threat probability between threat levels. For example, in Exhibit 6, the interval is 1% for Low-Low (<1%), 4% for Medium-Low (1%-5%), 10% for Medium (5%15%), 20% for Med-High (15%-35%), and 65% for High (>35%). The rough order of magnitude approach is often helpful when the underlying data are hard to estimate precisely (large statistical error bars) or in situations where subject matter experts feel more comfortable providing general “ballparks” given inherent uncertainty of the values being estimated. Note that relative risk scales have the effect of reducing the difference between the high and low ends of the scale. For example, a threat with a 50% annual probability would by definition occur 100 times more often than a threat with a 0.5% annual probability but would have a threat score only 3 times as high using the uniform scale in Exhibit 6 and 5 times as high using the adjusted uniform or rough order of magnitude scales. Example assessment scales for vulnerability and consequence are presented in Exhibit 7 and Exhibit 8. Vulnerability scores are expressed in terms of the duration of the infrastructure outage. Consequence scores in Exhibit 8 are expressed in terms of the percentage of state supply or customers experiencing service disruptions. Exhibit 7. Vulnerability Assessment Using Different Quantitative Scaling Options Category Vulnerability (Duration) Score Tier Uniform Scale (Days) Adjusted Uniform Scale (Days) Rough Order of Magnitude Scale 1 Low 0-1 <1 Minutes 2 Med-Low 1-2 1-3 A few hours 3 Medium 2-3 3-7 ~1 day 4 Med-High 3-4 7-14 Several days 5 High 5+ 14+ 1 week+Page 19 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 19 of 31 Exhibit 8. Consequence Assessment Using Different Quantitative Scaling Options Category Consequence (Share of State Supply or Customers) Score Tier Uniform Scale Adjusted Uniform Scale Rough Order of Magnitude Scale 1 Low 0%-20% 0%-10% <1% 2 Med-Low 20%-40% 10%-20% 1%-5% 3 Medium 40%-60% 20%-30% 5%-15% 4 Med-High 60%-80% 30%-40% 15%-35% 5 High 80%-100% >40% >35% If using a quantitative consequence scale as in Exhibit 8, it may be necessary to adjust the scale or add weightings for different energy types, recognizing that different forms of energy will have different indirect impacts on society. For example, the loss of customer electric power service is likely to have a larger immediate impact on society than the loss of petroleum fuels. Alternatively, states may choose to employ a qualitative scale that takes both direct and indirect consequences into account. Exhibit 9 provides an example qualitative scale for consequence scoring that provides descriptions of consequences that account for the extent of the disruption (widespread versus localized) and secondary consequences, such as impacts of the loss of energy supply on lifeline 2 sectors, vulnerable populations, and the economy. Exhibit 9 provides consequence descriptions for each of the main energy types—electricity, liquid fuels, and natural gas. Electricity is further divided between consequences that involve service outages, typically caused by damage to the transmission and distribution lines, and electricity shortages that may involve generation outages or demand spikes that put grid reliability at risk and that may result in rolling blackouts or even grid collapse. The consequence tiers in Exhibit 9 build on one another in that descriptions of consequences in lower tiers carry up to the higher tiers, unless superseded by text in the higher tier descriptions. For example, if “below-average inventories” are mentioned in the tier 3 box, then below-average inventories are also included for tier 4 events even if not explicitly listed in the tier 4 box. States using any of the example assessment scales presented in this guidebook (particularly Exhibit 9) should adapt these scales to reflect state-specific situations and priorities. It may be difficult for stakeholders to precisely predict the consequences of a specific Risk Scenario. What matters more than precision is consistently grouping Risk Scenarios into 2 A lifeline enables the continuous operation of critical government and business functions and is essential to human health and safety or economic security Community Lifelines | FEMA.gov. Lifeline sectors include safety and security; food, hydration, and shelter; health and medical; energy; communications; transportation; hazardous materials; and water systems. See Appendix B for further information on key dependencies and interdependencies between the energy subsectors (electricity, petroleum, and natural gas) and other lifeline sectors.Page 20 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 20 of 31 specific tiers. For consequences that have some elements of a higher tier and some elements of a lower tier, partial scoring may be applied (e.g., 2.5 or 3.5).Page 21 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 21 of 31 Exhibit 9. Consequence Assessment Using Qualitative Scaling. Note impact may be a result of a natural hazard or human made (cyber or physical attack). Score Electricity Liquid Fuels Natural Gas 1) Low • Service Disruption: Grid is damaged in places but customers remain supplied as contingency actions allow power to be rerouted to avoid disruption in service. • Any resulting supply loss offset by storage • Any resulting supply loss offset by storage assets 2) Med-Low • Service Disruption: Localized power outages. • Supply loss offset by storage assets but prices see notable increase. • Supply loss offset by storage assets but prices see 3) Medium • Service Disruption: Widespread but temporary power outages affecting a major metropolitan area or region of the state. • Lifeline sectors largely maintained with backup generators. • Electricity Shortage: Loss of generation leads to significant reduction in operating reserves, but reserves remain above thresholds for emergency action. • Sporadic fuel outages and delivery delays impacting end users (e.g., gas stations, heating customers) as supply and distribution do. • Infrastructure struggles to keep up with sudden spike in demands. • Localized supply shortages at bulk terminals. Distributors begin loading trucks at terminals further away to meet customer needs. • Local or regional fuel inventories fall near or below the bottom of previous five-year range. • Major transmission pipeline issues Operational Flow Orders (OFOs) to avoid system strain. Usually driven by high-demand cold periods or infrastructure outages or constraints. • High local or regional prices versus U.S. benchmarks may indicate issues. • High prices in affected markets lead to voluntary fuel switching for power sector and industrial customers with the ability to switch. 4) Med-High • Service Disruption: Widespread power outages affecting a major metropolitan area or region of the state. • Lifeline sectors experience temporary or intermittent disruptions as backup generator fuel is exhausted and awaits replenishment. • Vulnerable groups that rely on electricity moved to shelters or provided backup generators as needed. • Electricity Shortage: Grid operators issue emergency alerts for critical conservation and to maximize generation and transmission resource availability. Sharp price spikes across balancing areas. • Widespread run-outs and/or delivery delays for end users and bulk terminals as suppliers cannot meet all demands. • Typically associated with extended outage of one or more critical supply assets. • Sharp declines in local or regional fuel inventories to well below previous five-year lows. • Sharp price spreads versus U.S. or international benchmarks may indicate significant regional issues. • A major transmission pipeline has an extended unplanned outage during a (local or regional) peak demand period. • Some gas is rerouted into the region on alternate pipelines, but due to capacity constraints, supply is interrupted to power plants and other customers with non-firm contracts. • Local distribution companies (LDCs) urge customers to conserve gas use. • Gas supply disruptions to power generators reduce available generation resources, forcing grid operators to issue emergency advisories or alerts. 5) High • Service Disruption: Widespread power outages affecting a major metropolitan area or region of the state. • Lifeline sectors, including Emergency Response, experience severe impacts from difficulty refueling vehicles and backup generators due to impact of power outages on liquid fuels supply chains. • Electricity Shortage: Grid operators initiate rolling blackouts to preserve grid stability. Typically associated with large-scale loss of generation resources due to power plant operational outages or power plant fuel shortages. • Fuel unavailable or inaccessible to most end users as widespread power outage or other common event renders retail outlets and critical supply infrastructure inoperable. • Lifeline sectors, including Emergency Response, have difficulty finding supply, impacting provision of essential services. • Vulnerable groups that rely on propane/heating oil moved to shelters. • Severe outage/damage or supply shortage forces assets across the transportation and delivery system. Minimal impact to pricing. across the transmission and delivery system. Minimal impact to pricing. notable increase. • • • • transmission pipelines and LDCs to interrupt supply to firm customers. Loss of pressure in the gas distribution system causes gas to be shut off to firm customers (residential and commercial) Restoring service is time-consuming, as the LDC must relight each customer’s pilot light. Vulnerable groups dependent on gas heating moved to shelters. Loss of gas-fired generation leads to severe regional electricity shortages. Grid operators initiate rolling blackouts to preserve grid stability.Page 22 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 22 of 31 CALCULATING RISK SCORES Once component scores have been assessed for each of the Risk Scenarios under evaluation, these scores may be multiplied using the risk formula to produce a total Risk Score. Exhibit 10 presents an example of the Risk Assessment calculation using 5-point numeric scales for threat, vulnerability, and consequence values, where 1 is the lowest value and 5 is highest value. Note that the scores and calculations presented in this exhibit are for explanatory purposes only. Exhibit 10. Relative Risk Formula Example: 2-foot Flooding /Big State City Substations In Exhibit 10, the threat score (3) indicates a medium probability event—in this case one that occurs once every 10 years; the vulnerability score (5) indicates high expected damage to the infrastructure asset or system (in this case an outage lasting more than a week); and the consequence score (4) indicates that the loss of the energy asset would have a mediumhigh impact on society, including outages affecting 25% of Big State City, including impacts to a major hospital. Multiplying each of these components together produces a total Risk Score of 60. This score can then be compared to similarly constructed Risk Scores for other Risk Scenarios to understand relatively which risks are larger or smaller. Exhibit 11 presents an example of risk calculations for various Risk Scenarios using different component (threat, vulnerability, and consequence) scores. Note that these scores and calculations are presented for explanatory purposes only. Exhibit 11. Risk Score Calculations for Various Risk Scenarios Risk Scenario (Threat/Infrastructure) Threat Vulnerability Consequence Risk A. 2-foot Flooding /Big State City Substations 3 5 4 60 B. Cat. 3 Hurricane/Big State Transmission Lines 1 4 5 20 C. 8.0 M Earthquake/Big State Petroleum Pipeline 1 5 3 15 D. Wildfire/Big State Gas Storage Facility 2 2 1 4 E. Extreme Cold/Big State Basin Oil & Gas Wells 3 3 3 27Page 23 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 23 of 31 Exhibit 11 shows a range of Risk Scores with Scenario A resulting in the highest overall risk score (60). The risk scores in this table can be compared with one another on a relative basis—for example, Scenario A is relatively three times as large as Scenario B and four times as large as Scenario C. GRAPHICAL RISK MATRIX Graphical presentation of the Risk Assessment results through charting or mapping is a useful way to analyze risk results and recognize trends and patterns to help draw Risk Assessment conclusions. One method of analyzing and visualizing risk is to develop a Risk Matrix (sometimes called a heat map) to show how Risk Scenarios compare to one another along two key variables: threat (probability) and “impact” (a combination of vulnerability and consequence). Exhibit 12 presents an example of a Risk Matrix. Exhibit 12. Illustrative Risk Matrix with Risk Scenarios Plotted 5 (High) Medium Risk High Risk Extreme Risk Very High Risk Threat 4 (Med-High) 3 (Medium) E 2 (Med-Low) D 1 (Low) Low Risk 1-5 (Low) 6 - 10 (Med-Low) A C B 11 - 15 (Medium) 16 - 20 (Med-High) 21 - 25 (High) Impact (Vulnerability x Consequence) The example Risk Matrix in Exhibit 12 plots the impact score—comprised of the vulnerability score multiplied by the consequence score—on the x-axis and the threat score—associated with probability—on the y-axis. In this example, the x-axis is rated on a scale of 1 to 25 and the y-axis is rated on a scale of 1 to 5, but more granular rating scales may be applied. Generally, scenarios that are plotted closer to the upper right-hand corner of the Risk Matrix will have the higher risk scores. The color-coding of the cells in the Risk Matrix indicate fivePage 24 of 31
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 06, 2026 BETP-038 Attachment 1 Page 24 of 31 risk categories based on the intersection of the threat and impact scores: extreme, very high, high, medium, and low, with each risk category covering a range of Risk Scores. The example Risk Matrix in Exhibit 12 plots the five Risk Scenarios from Exhibit 11. Note that these scores are presented for explanatory purposes only. DOCUMENTING THE RISK ASSESSMENT The results of the SESP Risk Assessment should be documented in the SESP. An example outline for documentation is provided in Exhibit 13. Exhibit 13. Risk Assessment Outline Section Content 1. Risk Assessment Approach • List of reports, datasets, and other resources utilized • List of key stakeholders consulted • Documentation of risk scoring methodology, including any formulas, rating scales, and weightings used 2. Inventory of Risk Problem Statements 3. Risk Assessment Results • See Exhibit 3. Risk Assessment Template • Table of Risk Score calculations (see Exhibit 11) • (Optional) Graphical Risk Matrix (see Exhibit 12)
Text of BETP-040_Final.pdf
Extracted from the file · 1 page · 1,141 characters
As listed on the current system
Question(s) Answered 26, 28, 29, 33, 34, 37, 38, 40 (The Connecticut Light and Power Company) Date Filed: 10/26/2026