  1. Page 22 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 22 of 52 SPC-ARM-002 MATERIAL SPECIFICATION Figure 2 – 5.75” X 7.75” X 21’ – 4 Pin Arm, NH Figure 3 – 5.75” X 7.75” X 24’ 6” – 0 Pin Arm, NH Revision 1
  2. Page 23 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 23 of 52 This pin shall meet all applicable requirements of ANS C135.22-1988 with the exception that longitudinal load be toward the rigid steel pole and the pin mounted as show below in the TEST ASSEMBLY. STANDARD 1” LEAD THREAD 9/16” 1-3/8” A A 1-7/8” SECTION A-A MAX 10º DEFLEC 32” 6 ” ADAPTER PLATE 3 “X 6” X 1/2” WELDED ACROSS LEGS OF CHANNEL 1200 LB LOAD 5-1/2” ADAPTER PLATE 3” 11/16” DIAMETER HOLE 8-1/2” RIGID STEEL POLE 5” 1/2” FILLER PLATE 1” 11/16” X 1-1/2” SLOT ORIGINAL PIN – POLE TOP – 32” 08/16/76 APPROVED 12/12/22 EVERSOURCE ENERGY CONSTRUCTION STANDARD SPC-P-351 5
  3. Page 24 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 24 of 52 STRUCTURE LIMIT A3 STRUCTURE LIMIT A5 Note For the vise top insulator the range in feet of pull of a corner when installing a conductor in the top position is as follows: 1/0 ACSR bare and covered, 0-9; 477 Kcmil bare and covered, 0-5. STRUCTURE LIMIT A6 STRUCTURE LIMIT A6 Notes 1. Refer to DTR 04.047 for secondary and neutral attachment heights. 2. Install double deadends with a pole top pin for single phase extensions with a change in wire size. 3. Select straight strain clamps from DTR 07.035. ORIGINAL 05/24/89 APPROVED 12/02/24 35 KV MGY AND BELOW ARMLESS CONSTRUCTION SINGLE-PHASE TANGENT THROUGH DEAD END EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 10.027 7
  4. Page 25 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 25 of 52 Construction Standard Variation A A3 CONST 35KV 1PH 24 IN POLE TOP PIN COV AL/BAR WIRE B Intentionally Left Blank C A3 CONST 35KV 1PH 36 IN POLE TOP PIN COV AL/BAR WIRE D Intentionally Left Blank E A5 CONST 35KV 1PH LARGE CORNER AL/ACSR COV - CT/MA F A5 CONST 35KV 1PH LARGE CORNER AL/ACSR COV - NH G A5 CONST 35KV 1PH LARGE CORNER AL/ACSR BAR - CT/MA H A5 CONST 35KV 1PH LARGE CORNER AL/ACSR BAR - NH I A5 CONST 35KV 1PH LARGE CORNER COPPER WIRE - CT/MA J A6 CONST 23KV 1PH SINGLE DEADEND - CT/MA K A6 CONST 35KV 1PH SINGLE DEADEND - NH L A6 CONST 35KV 1PH DOUBLE DEADEND ANGLE - CT/MA M A6 CONST 35KV 1PH DOUBLE DEADEND ANGLE - NH M L K J I H G F E 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 D C 1 B A 2 2 1 1 2 1 2 Construction Reference Document DTR10.027.5A --DTR10.027.5C --DTR10.027.4E DTR10.027.4F DTR10.027.4G DTR10.027.4H DTR10.027.4I DTR10.027.4J DTR10.027.4K DTR10.027.4L DTR10.027.4M U= Capital Item M= Standard Item L = Lobby UM Item Description Item Number EA PIN INSULATOR POLE TOP EPOXY/FG 1 IN THRD 36 IN M 526298 EA BOLT EYE GS 5/8 X 16 IN W/SQ NUT L 601629 EA BOLT MACHINE GS 5/8 X 14 IN SQ HEAD W/SQ NUT L 536259 EA CLAMP ANGLE AL 1/0-556 BARE WIRE L 514905 EA CLAMP ANGLE G 4-4/0 CU,19#8 AW,0000127 AWA L 514906 EA EYELET STD LONG G FOR 5/8 IN BOLT L 520214 EA INSULATOR VISE TOP 35 KV 1 IN PIN POLY COMPOSITE L 605137 EA INSULATOR SUSP POLYMER SILC 35 KV 10M CLV FIT 18-20 IN L 522669 EA LINK EXTENSION G 10 IN CLV/EYE ENDS 9MLB L 551508 EA PIN INSULATOR POLE TOP G 1 IN THRD 24 IN L 526306 EA WASHER SQUARE CURVED GS 3 IN 13/16 H L 539280 EA WASHER SQUARE FLAT GS 2-1/4 IN 13/16 H L 539282 Revision: 5 Page: 1 of 1
  5. Page 26 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 26 of 52 STRUCTURE LIMIT C1 Notes 1. Refer to DTR 07.011 Structure Limits. 2. Select guy strain insulator and associated material from Section 06. 3. Use 3.5 inch square washers, Item #539295, on the top of the crossarms when installing any insulator to avoid fracturing the composite arm. 35 KV MGY AND BELOW – FIBERGLASS CROSSARM CONSTRUCTION – THREE-PHASE – TANGENT AND SMALL CORNER APPROVED ORIGINAL 05/13/14 10/30/24 EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 10.421 1
  6. Page 27 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 27 of 52 Construction Standard Variation A C1 CONST 35KV FG 3PH TAN/SMALL COR 8 FT-COVER AND BARE WIRE B Intentionally Left Blank C C1 CONST 35KV FG 3PH TAN/SMALL COR 10 FT- COVER AND BARE WIRE D Intentionally Left Blank E F G H I J K L M M L K J I H G F E D C 1 4 3 2 1 4 4 2 B A 1 4 3 2 1 4 4 2 Construction Reference Document DTR10.421.3A --DTR10.421.3C --- U= Capital Item M= Standard Item UM Item Description EA CROSSARM FIBERGLASS 3-5/8 X 4-5/8 IN 8 FT 6H TAN W/BKT EA CROSSARM FIBERGLASS 3-5/8 X 4-5/8 IN 10 FT 8H TAN W/BKT EA BOLT MACHINE GS 5/8 X 14 IN SQ HEAD W/SQ NUT EA INSULATOR VISE TOP 35 KV 1 IN PIN POLY COMPOSITE EA PIN INSULATOR 1 IN THREAD 7.75 IN SHANK 8 IN HGT GALV EA PIN INSULATOR POLE TOP G 1 IN THRD 24 IN EA WASHER SQUARE FLAT GS 3-1/2 IN FOR 5/8 BOLT EA WASHER SQUARE CURVED GS 3 IN 13/16 H EA WASHER SPRING 5/8 IN GALV Revision: 3 L = Lobby Item Number M 501024 M 501025 L 536259 L 605137 L 526300 L 526306 L 539295 L 539280 538784 L Page: 1 of 1
  7. Page 28 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 28 of 52 DISTRIBUTION SYSTEM ENGINEERING MANUAL Overhead General Doc Number: Issued Date: 06.201 19-Dec-25 DSEM Category: Revision: Applicability: Overhead Design Approved by: Signature on File David Gladey Vice President, Distribution Engineering 2 Date: ALL 15-Dec-25 Rev No. Description Date 2 Added new Section 4.0 “pole set spacing”. Updated Section 8.0 (previously) 7.0 for latest conductor practices. Remove Section 8.2.1 Bare Conductor. Section 6.7 Remove PAGS and Adding PoleForeman December 19, 2025 1 Updated Section 5.1 for Pole Class Requirements. 0 Revised to new format. Updated Table 1. July 9, 2024 September 27, 2022
  8. Page 29 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 29 of 52 Table of Contents Section Page 1.0 Scope ........................................................................................................................................3 2.0 Reference Documents...............................................................................................................3 3.0 General .....................................................................................................................................3 4.0 Pole Set Spacing .......................................................................................................................4 5.0 Pole Heights ..............................................................................................................................4 6.0 Pole Class Size .........................................................................................................................4 7.0 Guying .......................................................................................................................................6 8.0 Conductor & Pole Top Construction ..........................................................................................6 9.0 Primary Risers...........................................................................................................................8 10.0 Secondary .................................................................................................................................8 11.0 Neutrals .....................................................................................................................................9 12.0 Eversource Owned All Self-Supporting (ADSS) Cable ..............................................................9 13.0 Transformer...............................................................................................................................9 14.0 Arresters..................................................................................................................................10 15.0 Cutouts ....................................................................................................................................10 16.0 Grounding ...............................................................................................................................10 17.0 Guy Insulators .........................................................................................................................10 18.0 Animal Guards ........................................................................................................................10 19.0 Basic Impulse Insulation Level (BIL) .......................................................................................10 06.201 Page 2 of 10 Rev 2
  9. Page 30 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 30 of 52 1.0 Scope These Construction Guidelines state basic philosophies, preferences, and standards with respect to the construction of overhead primary distribution facilities. . 2.0 Reference Documents DTR Section 04 Clearances DTR Section 07 General Information DTR Section 15 ADSS Fiber Optics Cable DTR Section 16 Arresters & Grounds DTR Section 18 Cutout and Solid Blade Disconnects DTR Section 67 Risers DSEM 06.231 Clearances DSEM 06.241 Conductor Attachment DSEM 06.301 Pole Attachment DSEM Section 06 Overhead Design DSEM Section 09 Arresters DSEM Section 14 Transformer General DSEM Section 15 Overhead Service and Secondaries 3.0 DER 84−7 Tree Wire Burndown – Causes and Mitigation WMS 08.06 Wildlife Guards General These Eversource Energy Distribution Construction Standards are based upon and are in compliance with the following: 3.1.1 The National Electrical Safety Code (NESC) 3.1.2 Regulations of Connecticut state agencies. 3.1.3 Commonwealth of Massachusetts Regulations, Section 220. 3.1.4 The New Hampshire Public Utilities Commission Rules and Regulations for Electric Service, PUC300. These guidelines apply to most overhead primary distribution construction. Additional information or exceptions to these guidelines may be found in specific sections of the Standards. 06.201 Page 3 of 10 Rev 2
  10. Page 31 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 31 of 52 4.0 Pole Set Spacing Pole set spacing must maintain minimum clearances to allow ample space to work on and around the pole without obstruction. Minimum set distance for adjacent structures without equipment on them is to be no less than 15 feet. This accounts for both poles having no equipment being set on them. Minimum set spacing for adjacent structures with equipment installed on them is to be no less than 25 feet. This spacing is required when one or both structures have equipment installed 5.0 Pole Heights Selection is dependent on the amount of pole−top space that is required for the type of construction that is being used. Specific Construction Standards indicate the amount of pole space that is required. In general, 45 foot poles shall be the minimum height used for circuit backbones and 40 foot poles shall be the minimum height used for single- & three- phase lateral construction. Secondary attachments should be positioned near the bottom of the allotted pole space and care shall be taken to provide adequate clearances in the span as shown in DTR Section 04. 35-foot poles shall only be used for the following applications: 5.4.1 Stub poles used for guying purposes. 5.4.2 Service and streetlighting poles with secondary cable only on the pole. 5.4.3 Poles installed on private property and in rights of way that will only support secondary conductors; 40-foot poles shall be used if it is determined that primary conductors may be installed in the future. 5.4.4 In NH, solely owned line extensions where it appears reasonable that sole ownership will remain beyond three years. When proper clearances may be obtained on existing poles that are involved in line rebuilds, economics dictate that poles in good condition remain in use. See DSEM 06.241. 6.0 Pole Class Size The minimum pole class size installed on the backbone shall be Class 2. For rebuilds do not replace existing poles if the poles meet minimum loading requirements. Refer to Table 1 for more detail on minimum pole class requirements. New poles installed in Eversource three-phase lines in distribution Rights−of−Way are to be direct embedded self−weathering steel poles, class and height to be determined by Engineering. Pole options other than steel will require approval from managers or above in Operations and Engineering. The use of steel poles in other situations such as single-phase lines, jointly owned facilities, or other special situations is by exception only and requires approval from managers, or above, in Operations and Engineering. Steel poles shall not be used for service poles. 06.201 Page 4 of 10 Rev 2
Words on different pages
Words on different pages

Text of NECTA-132 Attachment 3.pdf

Extracted from the file · 8 pages · 10,921 characters

Text of NECTA-132 Attachment 4.pdf

Extracted from the file · 8 pages · 11,115 characters

As listed on the current system

Question(s) Answered 132 (The Connecticut Light and Power Company) Date Filed: 11/05/2026

This filing on the current system (opens in a new tab)