  1. Page 9 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 9 of 52 MATERIAL SPECIFICATION SPC-ARM-001 3.3 Revision 1 Strength 3.3.1 Crossarms shall meet the vertical and horizontal loads shown in Table 1 per the latest version of ASTM D8019. Vertical and Horizontal Strength Ratings Fiberglass Crossarm Min Vertical Load per Side 3 5/8’’ x 4 5/8’’ x 5' 7" Tangent Crossarm 4,000 lbs. 3 5/8’’ x 4 5/8’’ x 8’ Tangent Crossarm 3,500 lbs. 3 5/8’’ x 4 5/8’’ x 10’ Tangent Crossarm 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Heavy Duty Crossarm (BROWN) EMA 3 5/8’’ x 4 5/8’’ x 13’ Tangent Crossarm 2,750 lbs. 5,400 lbs. 2,100 lbs. Fiberglass Crossarm Min Horizontal Load (2 Wires per Arm) 4 5/8’’ x 3 5/8’’ x 8’ Dead-end Crossarm 14,700 lbs. 4 5/8’’ x 3 5/8’’ x 10’ Dead-end Crossarm 12,250 lbs. Tangent Alley Fiberglass Crossarm Min Vertical Load per Side 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Alley Arm 4,000 lbs. 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Alley Arm 3,000 lbs. Table 1 – Vertical and Horizontal Strength Ratings 3.4 3.5 Treatment 3.4.1 An abrasion resistant external coating is required to prevent UV degradation of the resin. 3.4.2 A thermally bonded external coating must be applied to the fiberglass to prevent the material from blooming. 3.4.3 A coating must be able to meet a minimum of 10,000 hours exposure in a UV test chamber. Treatment shall be tested according to the latest version of ASTM G154-12a. Steel Characteristics 3.5.1 Galvanizing shall be performed in accordance with the applicable requirements of ASTM A123, A153, and/or F2329. 3.5.2 All bolts, nuts, and threaded rods shall conform to IEEE C135.80. Page 3 of 12
  2. Page 10 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 10 of 52 MATERIAL SPECIFICATION SPC-ARM-001 Revision 1 A. In addition, all bolts shall conform to SAE J429 Grade 5. 3.6 3.5.3 All eye nuts shall conform to ANSI C135.80. 3.5.4 All mounts, washers, and other steel hardware shall conform to ASTM A36. 3.5.5 All holes in steel shall be added prior to galvanizing Flammability Test 3.6.1 Crossarms shall be tested in compliance with the latest version of ASTM D3801 and ASTM D365 (ANSI/UL 94). 4.0 Dimensions and Drilling 4.1 Drilling Specifications 4.1.1 Dimensions and drilling shall be accordance with the drawings of this specification. All holes shall be 11/16’’ in diameter, unless otherwise noted on drawings, with a +/- 1/32’’ tolerance. Drawings are not to scale. 4.1.2 All drilling holes shall be done prior to treatment. 4.1.3 Drilling tolerances shown in Table 2. Tolerance (+/-) Pin to Pin 1/8’’ From end of arm to first pin 1/4’’ Table 2 – Tolerance in This Table Apply to All Figures in This Standard 4.2 Ground Wire Drilling Specification 4.2.1 3/16” pilot holes shall be drilled on the underside of the crossarm for possible insertion of wire holders to support a ground wire. See drawings for exact spacing per crossarm. 5.0 Marking and Packing 5.1.1 Crossarms shall be identified on the end caps using the manufacture’s name and model. Page 4 of 12
  3. Page 11 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 11 of 52 MATERIAL SPECIFICATION SPC-ARM-001 Revision 1 5.1.2 Reasonable care shall be taken to avoid damage to the crossarms during handling and transportation. 5.1.3 Crossarms shall be stacked and packaged in quantities capable of forklift handling. 6.0 Drilling Requirements Figure Description 1 3 5/8’’ x 4 5/8’’ x 5' 7", Fiberglass Tangent Crossarm 2 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Tangent Crossarm 3 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Tangent Crossarm 4 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Tangent Crossarm (BROWN) NH 5 6 3 5/8’’ x 4 5/8’’ x 13’, Fiberglass Tangent 4 5/8’’ x 3 5/8’’ x 8’, Fiberglass Dead-end Crossarm 7 4 5/8’’ x 3 5/8’’ x 10’, Fiberglass Dead-end Crossarm 8 4 5/8’’ x 3 5/8’’ x 10’, Fiberglass Dead-end Crossarm (BROWN) NH 9 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Heavy Duty Crossarm (BROWN) EMA 10 3 5/8’’ x 4 5/8’’ x 21’, Bare Fiberglass Arm 11 12 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Alley Arm 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Alley Arm Page 5 of 12
  4. Page 12 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 12 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 1 – 3 5/8’’ x 4 5/8’’ x 5' 7", Fiberglass Tangent Crossarm Page 6 of 12
  5. Page 13 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 13 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 2 – 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Tangent Crossarm Figure 3 – 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Tangent Crossarm Page 7 of 12
  6. Page 14 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 14 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 4 – 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Tangent Crossarm (BROWN) NH ONLY Figure 5 – 3 5/8’’ x 4 5/8’’ x 13’, Fiberglass Tangent Crossarm Figure 6 – 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Dead-end Crossarm Page 8 of 12
  7. Page 15 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 15 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 7 – 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Dead-end Crossarm Figure 8 – 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Dead-end Crossarm (BROWN) NH ONLY Page 9 of 12
  8. Page 16 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 16 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 9 – 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Heavy Duty Crossarm (BROWN) Figure 10 – 3 5/8’’ x 4 5/8’’ x 21’’, Bare Fiberglass Crossarm Page 10 of 12
  9. Page 17 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 17 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 11 – 3 5/8’’ x 4 5/8’’ x 8’, Fiberglass Alley Arm Page 11 of 12
  10. Page 18 of 52

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-132 Attachment 1 Page 18 of 52 SPC-ARM-001 MATERIAL SPECIFICATION Revision 1 Figure 12– 3 5/8’’ x 4 5/8’’ x 10’, Fiberglass Alley Arm Page 12 of 12
Words on different pages
Words on different pages

Text of NECTA-132 Attachment 3.pdf

Extracted from the file · 8 pages · 10,921 characters

Text of NECTA-132 Attachment 4.pdf

Extracted from the file · 8 pages · 11,115 characters

As listed on the current system

Question(s) Answered 132 (The Connecticut Light and Power Company) Date Filed: 11/05/2026

This filing on the current system (opens in a new tab)