The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 21 of 30 Platform Cutout (TYP.) Panel (TYP.) CONDUCTORS DTR 20.360 Number of wires: three (3) 477 AAC – 150 mil XLPE Covering Tension: 500 lb. each (slack span) Span: 80 feet Pull: 4.2 feet at 80 foot span (3 degrees) Page 9 of 11 Rev 2Page 22 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 22 of 30 Design Option 3 – No conductor tension. Platforms offset to the side of the circuit. Platform Cutout (TYP.) Regulator (TYP.) Platform Platform Panel (TYP.) CONDUCTORS DTR 20.360 Number of wires: None Tension: 0 lb. each Span: 0 feet Pull: 0 feet at 0 foot span (0 degrees) Page 10 of 11 Rev 2Page 23 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 23 of 30 Regulator (TYP.) Cutout (TYP.) Panel (TYP.) CONDUCTORS DTR 20.360 Number of wires: None Tension: 0 lb. each Span: 0 feet Pull: 0 feet at 0 foot span (0 degrees) Page 11 of 11 Rev 2Page 24 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 24 of 30 ***This Document Supersedes DTR 20.404*** STRUCTURE LIMIT C1 SELECT POLE TOP FROM SECTION 10 34.5” – 25kV 43.5” – 35kV 168” ORIGINAL 08/09/94 APPROVED 09/11/26 35 KV MGY & BELOW – THREE REGULATORS INSTALLATION EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 20.361 ALL 8Page 25 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 25 of 30 ***This Document Supersedes DTR 20.404*** STRUCTURE LIMIT C1 Notes 1. For secondary and neutral attachment point refer to DTR 04.047. 2. Arresters must be mounted at both load and source side bushings. 3. Poles shall be minimum Class 1. Refer to DTR 20.360 which provides guidance on methods of setting poles associated with platform installations. Refer to DTR 05.303 which provides guidance on methods of steel casing foundation for distribution poles. 4. Mount the platform to the poles with three quarter inch bolts. Install the platform per dimension which takes into account the overall height of the regulators. The following table includes regulators that are platform mounted. Regulator Voltage 2,500 7,620 14,400 19,920 kVA 333 333 416 432 576 667 833 400 833 5. Install a super extra heavy-duty platform for regulators weighing up to 7,266 lbs. each. Install a super extra heavy-duty pole kit for regulators weighing above 7,266 lbs. each. Refer to Section 06 for typical regulator weights. 6. Ensure that animal guards are installed on all regulator and arrester bushings. 7. CAUTION: Regulators must always have their tap changers in the neutral position before they are put on or taken off an energized line; otherwise, a violent regulator failure could occur. If the tap changer cannot be placed in the neutral position, the circuit must be de−energized prior to taking the regulator off the line. Refer also to DTR 20.051 which provides a guide regards to bypass switch sequence of operations. 8. Platform ground and neutral conductor shall be the same size as or larger than the system neutral. 9. For minimum vertical clearances refer to Section 04. Consider the platform as a Category 1 conductor. 10. CAUTION: Minimum distance from the top of the control box to the lowest point of the platform or supporting braces shall be a minimum eight feet. An alternate location for mounting the control boxes is on a separate structure. 11. Care should be taken to install platform structures in locations where their visibility to the public is minimized. 12. See DTR 16.201 for overhead grounding and bonding guide. Refer to DTR 16.711 for platform mounted regulator grounding and DTR 16.311 for control grounding. Connect all grounds before connecting taps to an energized circuit. 13. Refer to DTR 20.115, Figure 4 for regulator connections. ORIGINAL 08/09/94 APPROVED 09/11/26 35 KV MGY & BELOW – THREE REGULATORS INSTALLATION EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 20.361 ALL 8Page 26 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 26 of 30 Construction Standard Variation A REGULATOR PLATFORM 15-25 KV REG UP TO 7,266 LBS B REGULATOR PLATFORM 35 KV REG UP TO 7,266 LBS C CENTER BRACE F / REGULATOR PLATFORM OVER 21,798 LBS TOTAL D 35 KV SUSPENSION INSULATOR E F G H I J K L M M L K J I H G F E D C B 1 A 1 3 3 3 3 9 6 2 2 9 6 2 2 75 24 75 24 72 8 72 8 14 3 14 1 2 3 3 2 2 2 2 Construction Reference Document DTR20.361.6A DTR20.361.6B DTR20.361.6C DTR20.361.5D U= Capital Item M= Standard Item L = Lobby UM Item Description Item Number EA PLATFORM EQUIPMENT 18' X 4' MAX WT 7,266 LBS PER POSITION U 566849 EA SWITCH OTDR AIR HKO DSCQ RGBP UHG 25KV 600A U 531317 U EA SWITCH OTDR AIR HKO DSCQ RGBP UHG 38KV 600A 531322 M EA CROSSARM FIBERGLASS 21 FT 3-5/8 X 4-5/8 IN SQ HDW/HOLES 566485 566319 EA POLE KIT EXTRA F/2EHD PLATFORMS M EA SHIELD POLE RISER PVC 2 IN X 10 FT M 529240 EA BOLT MACHINE GS 3/4 X 14 IN W/SQ NUT L 536268 EA BOLT MACHINE GS 5/8 X 20 IN L 516039 EA BOLT MACHINE GS 5/8 X 24 IN SQ HEAD W/SQ NUT L 536261 L EA BOLT MACHINE GS 3/4 X 16 IN SQ HEAD W/SQ NUT 536269 L FT CABLE COVERED EPR TAP CU 4/0 37 STR SD 513408 L EA CONN BAR CU 6 TO 250 KCMIL 516327 L EA INSULATOR SUSP POLYMER SILC 35 KV 522669 L EA LINK STRAIGHT G 3-1/4 X 5/8 IN 40M 551441 EA SCREW DRIVE 0.25 IN 2.5 IN LG GAL HEX HEAD W/NEO WSHR L 538042 EA SCREW LAG TD PPT G 1/2 X 4 IN L 538046 EA WASHER LOCK DCS GS 4/4 IN L 538785 EA WASHER SQUARE FLAT GS 2-1/4 IN 13/16 H L 539282 L EA PLATE,BASE FOR 38 KV REGULATOR BYPASS SWITCH 589085 Revision: 6 Page: 1 of 1Page 27 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 27 of 30 ***This Document was Supersedes DTR 20.372 & 20.373*** 34.5” – 25 kV 43.5” – 35 kV FOR MINIMUM VERTICAL CLEARANCES SEE NOTE 8 8’ MIN NOTE 9 NOTE 11 ORIGINAL 08/09/94 APPROVED 09/04/26 35 KV DELTA/UGY & BELOW – TWO OR THREE REGULATORS INSTALLATION EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 20.371 ALL 8Page 28 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 28 of 30 ***This Document was Supersedes DTR 20.372 & 20.373*** FOR MINIMUM VERTICAL CLEARANCES SEE NOTE 8 8’ MIN NOTE 9 NOTE 11 ORIGINAL 08/09/94 APPROVED 09/04/26 35 KV DELTA/UGY & BELOW – TWO OR THREE REGULATORS INSTALLATION EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 20.371 ALL 8Page 29 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 29 of 30 ***This Document was Supersedes DTR 20.372 & 20.373*** Notes 1. Arresters must be mounted at both load and source side bushings. Select arresters, if necessary, from Section 16. 2. Poles shall be minimum Class 1. Refer to DTR 20.360 which provides guidance on methods of setting poles associated with platform installations. Refer to DTR 05.303 which provides guidance on methods of steel casing foundation for distribution poles. 3. Mount the platform to the poles with three quarter inch bolts. 4. Install a super extra heavy-duty platform for regulators weighing up to 7,266 lbs. each. Install a super extra heavy-duty pole kit for regulators weighing above 7,266 lbs. each. Refer to Section 06 for typical regulator weights. 5. Install animal guards on all regulator and arrester bushings. 6. CAUTION: Regulators must always have their tap changers in the neutral position before they are put on or taken off an energized line; otherwise, a violent regulator failure could occur. If the tap changer cannot be placed in the neutral position, the circuit must be de−energized prior to taking the regulator off the line. Refer also to DTR 20.051 which provides a guide regards to bypass switch sequence of operations. 7. Platform grounds shall be #2 copper. 8. For minimum vertical clearances refer to Section 04. Consider the platform as a Category 1 conductor. 9. CAUTION: Minimum distance from the top of the control box to the lowest point of the platform or supporting braces shall be a minimum eight feet. An alternate location for mounting the control boxes is on a separate structure. 10. Care should be taken to install platform structures in locations where their visibility to the public is minimized. 11. See DTR 16.201 for overhead grounding and bonding guide. Refer to DTR 16.711 for platform mounted regulator grounding and DTR 16.413 for control grounding. Connect all grounds before connecting taps to an energized circuit. 12. For two regulators on a three-phase system, refer to DTR 20.116, Figure 2 for regulator connections. For three regulators on a three-phase system, refer to DTR 20.116, Figure 3 for regulator connections. ORIGINAL 08/09/94 APPROVED 09/04/26 35 KV DELTA/UGY & BELOW – TWO OR THREE REGULATORS INSTALLATION EVERSOURCE ENERGY CONSTRUCTION STANDARD DTR 20.371 ALL 8Page 30 of 30
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 14, 2026 NECTA-133 Attachment 1 Page 30 of 30 Construction Standard Variation A REGULATOR PLTFRM 2XHD 15-25KV 2-REG UP TO 9,334 LBS EA B REGULATOR PLTFRM 2XHD 35KV 2-REG UP TO 9,334 LBS EA C REGULATOR PLTFRM 2XHD 15-25KV 3-REG UP TO 9,334 LBS EA D REGULATOR PLTFRM 2XHD 35KV 3-REG UP TO 9,334 LBS EA E SUSP INS FOR 2-PHASES F SUSP INS FOR 3-PHASES G CENTER BRACE FOR REGULATOR PLATFORM OVER 9,334 LBS H I J K L M M L K J I H G F E D 25 1 C 25 1 3 B 25 1 A 25 1 2 3 3 3 2 3 3 6 2 2 6 2 2 6 2 2 6 2 2 25 75 24 25 75 24 25 50 16 25 50 16 8 4 8 4 8 4 8 4 14 3 14 14 2 14 1 2 3 3 2 4 2 2 2 Construction Reference Document DTR20.371.3A DTR20.371.3B DTR20.371.3C DTR20.371.3D DTR20.371.3E DTR20.371.0F DTR20.371.0G U= Capital Item M= Standard Item L = Lobby UM Item Description Item Number FT CABLE BARE CU #2 7 STR SD F/GRD U 503602 EA PLATFORM EQUIPMENT 18' X 4' MAX WT 9,334 LBS PER POS U 566849 EA SW OTDR AIR HKO DSCG RGBP UHG 25KV 600A U 531317 EA SW OTDR AIR HKO DSCG RGBP UHG 38KV 600A U 531322 EA CROSSARM FIBERGLASS 21 FT 3-5/8 X 4-5/8 IN NO HDW/HOLES M 566485 PR POLE KIT EXTRA F/2EHD PLATFORMS M 566319 EA BOLT MACHINE GS 3/4 X 14 IN W/SQ NUT L 536268 EA BOLT MACHINE GS 5/8 X 20 IN L 536260 EA BOLT MACHINE GS 5/8 X 24 IN SQ HEAD W/SQ NUT L 536261 EA BOLT MACHINE GS 3/4 X 16 IN SQ HEAD W/SQ NUT L 536269 FT CABLE BARE CU MHD #2 7 STR L 513340 FT CABLE COV EPR TAP CU 4/0 37 STR SD L 513408 EA CONN BAR CU 6 TO 250 MCM L 516327 EA INSULATOR SUSP POLYMER SILC 35 KV 10M CLV FIT 18-20 IN L 522669 EA LINK STRAIGHT G 3-1/4 X 1 X 5/8 IN 40M L 551441 EA SCREW LAG TD PPT G 1/2 X 4 IN L 538046 EA WASHER LOCK DCS GS 5/8 IN L 538784 EA WASHER LOCK DCS GS 3/4 IN L 538785 EA WASHER SQUARE FLAT GS 2-1/4 IN 13/16 H L 539282 EA PLATE,BASE FOR 38 KV REGULATOR BYPASS SWITCH L 589085 Revision: 3 Page: 1 of 1
As listed on the current system