Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Interrogatory responses

Answers to questions 590, 594

Files10

Search terms highlighted
Eversource rate increase is on 7 pages across 3 files of the text below, highlighted. Go to the first matchClear highlighting
Words on different pages
1 page match
Words on different pages

Text of OCC-590 Attachment 2.pdf

Extracted from the file · 1 page · 7,906 characters

Text of OCC-590 Attachment 2.xlsx

Sheet names, column headings and text cells; numbers left out

Text of OCC-590 Attachment 3.pdf

Extracted from the file · 14 pages · 27,306 characters

Text of OCC-594_Final.pdf

Extracted from the file · 4 pages · 7,909 characters

Text of OCC-594 Attachment 1.pdf

Extracted from the file · 1 page · 3,879 characters

Text of OCC-594 Attachment 1.xlsx

Sheet names, column headings and text cells; numbers left out

Scanned pages and machine-read text of OCC-594 Attachment 2 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 1 of 1 of OCC-594 Attachment 2 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 9, 2026 OCC-594 Attachment 2 REDACTED Page 1 of 1
    PROJECT_NUMBERPROJECT_DESCRIPTIONSubstationCircuitDIVISIONDISTRICTScopeTotal Cost ($k)Labor Cost ($k)Outside Services Cost ($k)Material Cost ($k)Removals Cost ($k)Other Cost ($k)Indirect subtotal ($k)Contingency ($k)Study YearISDMaximum Capacity MVA ExceedanceMaximum Capacity AMPS ExceedanceNormal Rating AMPS
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor278.411.794.847.521.01.8101.60.020256/1/20280.082375
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor & Reconfiguration1,594.066.7542.4272.1120.40.0545.210.620236/1/20281.1045460
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor & Reconfiguration1,450.860.7493.8247.7109.60.0529.39.620246/1/20280.9640421
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration455.419.1155.077.834.40.0166.13.020256/1/20281.8074511
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration280.211.795.447.821.21.9102.20.020256/1/20280.229580
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration352.114.7119.860.126.60.0128.52.320256/1/20280.4117235
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor695.729.1236.8118.852.64.6253.80.020256/1/20283.7093490
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration146.36.149.825.011.11.053.40.020256/1/20280.8738395
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor1,064.091.2120.3384.025.00.0440.03.620236/1/20272.1086440
    [redacted][redacted][redacted][redacted][redacted][redacted]New Feeder2,952.7123.61,005.0504.2223.20.01,077.219.620246/1/20272.00842092
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration1,000.041.9340.4170.775.60.0364.80.020246/1/2027440
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration129.65.444.122.19.80.947.30.020246/1/20272.89121440
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration544.922.8185.593.041.20.0198.83.620246/1/20270.3816440
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor1,594.2285.645.6201.838.00.0878.20.020266/1/20271.4664480
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration301.312.6102.551.422.82.0109.90.020246/1/20271.1450373
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration400.316.8136.268.330.32.7146.00.020266/1/20270.208604
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconfiguration236.09.980.340.317.80.086.11.620256/1/20271.1047460
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor630.245.3139.3160.150.90.0234.60.020266/1/20270.328130
    [redacted][redacted][redacted][redacted][redacted][redacted]Equipment Replacement450.976.456.047.863.30.0205.91.420266/1/20271.1228450
    [redacted][redacted][redacted][redacted][redacted][redacted]Equipment Replacement498.484.561.952.970.00.0227.61.520266/1/20271.6742450
    [redacted][redacted][redacted][redacted][redacted][redacted]Reconductor & Reconfiguration4,405.1570.2390.8904.0118.727.12,394.40.020236/1/20273.1980490

As listed on the current system

Question(s) Answered 590, 594 (The Connecticut Light and Power Company) Date Filed: 09/28/2026

This filing on the current system (opens in a new tab)