The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 110 of 297 5.44.13.2 Three Phase Recloser Classifications Controller Type Three Phase Reclosers Hydraulic Contacts in Vacuum Electronic Contacts in Oil Contacts in Vacuum Contacts in Oil X Type 6H X V6H X W X WE X VW E X Rating Max Cont. Int Rating Sym 100 2,000 200 2,000 560 10,000 560 * 10,000 560 * 12,000 560 * 8,000 VW VE27 X 560 12,000 NOVA27 X 630 * 12,500 WVE27 X WVE38X 560 8,000 VW VE38X X 560 * 12,000 VSO12 X 560 12,000 NOVA38 X 630 * 12,500 Centurian 27 X 630 12,500 * 800 A. Available with Accessory 6.44 Recloser Maintenance Instructions Before You Begin 1. Ensure that all employees are properly trained and qualified to perform this work; and all appropriate PPE and safety requirements are met, including but not limited to those defined within the following documents: • TD 211, “When to Wear FR Clothing” • Eversource Employee Safety & Health Handbook Procedure S/S Reclosers – SCADA Monitored/Controlled Check and Inspection – Energized – Monthly 1. Make a visual inspection of the recloser: • Check the ground integrity • Check for oil leaks, if applicable. • Check the condition of the bushings to ensure they are not blow or badly chipped, when practical. • Check to ensure animal guards are present, correctly installed and in good condition.Page 111 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 111 of 297 2. 3. • Check the control cable for damage from animals, vandalism, etc. Record the operations counter reading. Inspect the control cables and connectors for damage and for water intrusion into the connectors to the extent possible. CAUTION: Some recloser controls must be removed from service before you can replace their batteries. See Appendix 1 for instructions on replacing batteries for the different types of reclosers. 4. Check the date on the battery sticker and replace the batteries (as a set) based on their age as follows: • • • • • • • • 5. 6. 7. 8. 9. Form 2, 3, 3A controls – replace every 5 years Form 4C controls – replace every 3 years Siemens controls – replace every 3 years Form 6 controls – replace every 4 years Nu-Lec/Schneider Electric Recloser – replace every 3 years VXE controls – replace every 6 years G&W Viper Reclosers with SEL 351R/651R (SCADA) – replace every 10 years G&W Viper Reclosers with SEL 351R/651R (NON-SCADA) – replace every 6 years Check the battery terminal voltage. Test the battery with a dummy load. This can be done with an internal test program, if the recloser is so equipped, or by using an external load device. •A 3 – 4 volt drop is normal. A larger drop in voltage indicates the batteries are worn and due for replacement. For VIPER Reclosers, check the Enable Supply Light: •GREEN = OK •OFF – Notify Supervisor For VIPER Reclosers, check the Battery Problem Light: •OFF = OK •RED – Notify Supervisor Check the heaters and the AC supply to the battery charger. S/S Reclosers – Non-SCADA ELECTRONIC Check and Inspection – Energized 1. 2. 3. 4. Record the operations counter reading. Check all metering and indicating devices and inspect all control switches for normal position or electronic indication. Inspect the control cables and connectors for damage and for water intrusion into the connectors to the extent possible. Make a visual inspection of the recloser: •Check the ground integrity.Page 112 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 112 of 297 •Check for oil leaks, if applicable. •Check the condition of the bushings to ensure they are not blown or badly chipped, when practical. •Check the control cable for damage from animals, vandalism, etc. •Check to ensure animal guards are present, correctly installed and in good condition. CAUTION: Some recloser controls must be removed from service before you can replace its batteries. See Appendix 1 for instructions on replacing batteries for the different types of recloser 5. 6. 7. 8. 9. 10. Check the date on the battery sticker and replace the batteries (as a set) based on their age as follows: • Form 3A controls – replace every 5 years • Form 4C controls – replace every 3 years • Siemens controls – replace every 3 years • Form 6 Controls – replace every 4 years • Nu-Lec/Schneider Electric Recloser – replace every 3 years VXE controls – replace every years • G&W Viper Reclosers with SEL 351R/651R (SCADA) – replace every 10 years • G&W Viper Reclosers with SEL 351/651R (NON-SCADA) – replace every 6 years Check the battery terminal voltage. For VIPER Reclosers, check the Enable Supply Light: •GREEN = OK •OFF – Notify Supervisor For VIPER Reclosers, check the Battery Problem Light: •OFF = OK •RED – Notify Supervisor Test the battery with a dummy load. This can be done with an internal test program, if the recloser is so equipped, or by using an external load device. •A 3 – 4 volt drop is normal. A larger drop in voltage indicates the batteries are worn and due for replacement. Check the heaters and the AC supply to the battery charger. S/S Reclosers – Non-SCADA HYDRAULIC Check – EnergizedPage 113 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 113 of 297 1. 2. 3. Make a visual inspection of the recloser. Record the operations counter reading. Check for the following: •Ensure there are no oil leaks. •Check to ensure animal guards are present, correctly installed and in good condition. •Ensure that lightning arresters are present and in good condition. •Ensure the Trip / Close lever is in its normal position. Pole–Top Reclosers – SCADA Check and Inspection – Energized 1. 2. 3. 4. Make a visual inspection of the recloser: •Check the ground integrity. •Check to ensure lightning arresters are present and in good condition. •Check for oil leaks, if applicable. •Check the condition of the bushings to ensure they are not blown or badly chipped, when practical. •Check the control cable for damage from animals, vandalism, etc. •Check to ensure animal guards are present, correctly installed and in good condition. Perform touch potential testing on all controls or components that may be accessible to the public. Record the counter reading. Inspect the control cables and connectors for damage and for water intrusion into the connectors to the extent possible. CAUTION: Some recloser controls must be removed from service before you can replace its batteries. See Appendix 1 for instructions on replacing batteries for the different types of reclosers. 5. Check the date on the battery sticker and replace the batteries (as a set) based on their age as follows: (Instructions for changing batteries are at the end of this section.) • Form 3A controls - replace every 5 years • Form 4C controls - replace every 3 years • Siemens controls - replace every 3 years • Form 6 controls - replace every 4 years • Nu-Lec/Schneider Electric Recloser – replace every 3 years VXE controls – replace every 6 years. • G&W Viper Reclosers with SEL 351R/651R (SCADA) – replace every 10 years.Page 114 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 114 of 297 • 6. 7. 8. 9. 10. G&W Viper Reclosers with SEL 351R/651R (NON-SCADA) – replace every 6 years. Check the battery terminal voltage. Test the battery with a dummy load. This can be done with an internal test program, if the recloser is so equipped, or by using an external load device. For VIPER Reclosers, check the Enable Supply Light: •GREEN = OK •OFF – Notify Supervisor For VIPER Reclosers, check the Battery Problem Light: •OFF = OK •RED – Notify Supervisor Check the heaters and the AC supply to battery charger. Pole-Top Reclosers – Non-SCADA ELECTRONIC Check - Energized 1. 2. 3. 4. Record the operations counter reading. Check all metering and indicating devices and inspect all control switches for normal position or electronic indication. Inspect the control cables and connectors for damage and for water intrusion into the connectors to the extent possible. Make a visual inspection of the recloser: • Check the ground integrity. • Check to ensure lightning arresters are present and in good condition. • Check for oil leaks, if applicable. • Check the condition of the bushings to ensure they are not blown or badly chipped, when practical. • Check the control cable for damage from animals, vandalism, etc. • Check to ensure animal guards are present, correctly installed and in good condition. CAUTION: Some recloser controls must be removed from service before you can replace its batteries. See Appendix 1 for instructions on replacing batteries for the different types of reclosers. 5. 6. Perform touch potential testing on all controls or components that may be accessible to the public. Check the date on the battery sticker and replace the batteries (as a set) based on their age as follows:Page 115 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 115 of 297 • • • • • • 7. 8. 9. 10. 11. Form 3A controls – replace every 5 years Form 4C controls – replace every 3 years Siemens controls – replace every 3 years Form 6 controls – replace every 4 years Scweitzer SEL-651R controls replace every 3 years. Nu-Lec/Schneider Electric recloser – replace every 3 years. VXE controls – replace every 6 years. • G&W viper Reclosers with SEL 351R/651R (SCADA) – replace every 10 years. • G&W Viper Reclosers with SEL 351R/651R (NON-SCADA) – replace every 6 years. Check the battery terminal voltage. For VIPER Reclosers, check the Enable Supply Light: • GREEN = OK • OFF – Notify Supervisor For VIPER Reclosers, check the Battery Problem Light: • OFF = OK • RED – Notify Supervisor Test the battery with a dummy load. This can be done with an internal test program, if the recloser is so equipped, or by using an external load device. Check the heaters and the AC supply to battery charger. Pole-Top Reclosers – Non-SCADA HYDRAULIC Check – Energized – Annually 1. 2. 3. 4. Make a visual inspection of the recloser. Record the operations counter reading. Perform touch potential testing on all controls or components that may be accessible to the public. Ensure that all metering and indicating devices are in their normal positions. Recloser – All – Major Maintenance – De-Energized While most Major Maintenance for reclosers is performed at a maintenance shop, some is performed on-site. Perform the following steps: 1. Remove the unit from service. 2. Measure contact resistance to provide an indication of contact condition as well as loose current carrying parts. Use of a micro-ohmmeter is the recommended method. 3. Perform an insulation test (utilizing an insulation tester), phase-to-Page 116 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 116 of 297 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. phase, and phase-to-ground. Inspect and dress the main and control contacts, if necessary. Perform visual inspections on the interrupting chambers. Check clearance and adjust them to manufacturer’s specifications for that recloser model. Check all electrical and mechanical connections for correct tightness. Thoroughly clean all internal mechanisms and tanks, and remove all carbon. Check for traces of tracking on all insulating parts and moisture absorption of the bottom of the tank liner. Check all gaskets. •Replace the main tank gasket, as necessary. •Replace the tank liners, as necessary. •Replace bushing gaskets, as necessary. Check and adjust the component parts of the operating mechanism, if required. Use an electronic control unit to operate the recloser before it goes back into service. Thoroughly clean the exterior of the recloser. Inspect the exterior of the recloser for • • 14. 15. 16. 17. 18. 19. Cracked, chipped, or broken bushings. Replace as necessary. Paint scratches or other mechanical damage. Repaint as necessary to prevent corrosion. Refer to the Manufacturer’s manual for maintenance requirements specific to the recloser model you are servicing. Perform a dielectric test of the oil. Filter the oil and perform a second dielectric test to act as the as-left reading. Change lightning arresters, as required. Verify the recloser and its lightning arrester are the correct voltage for the planned installation. For hydraulically controlled reclosers, operate the recloser manually to lockout, verifying minimum pickup and time current characteristics. Vacuum Under Oil Device (Perform these steps and appropriate work activities outlined under Major Maintenance.) 1. 2. Perform an AC high potential test on each interrupter in accordance with manufacturer’s instructions or NU specifications. Perform this test carefully as it provides the best means for verifying the condition of the interrupter. If the manufacturer has provided a scribe mark for monitoring contact erosion, check the reference dimension to measure wear. Solid Dielectric Vacuum Recloser (Siemens and Cooper NOVA Reclosers and G&W Viper)Page 117 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 117 of 297 No user maintenance of the recloser mechanism is required. The recloser should be considered for refurbishment or retired if the mechanical duty or breaking duty on any phase is less than (5%). This can be determined this by checking the Operator Control Panel. Further details on maintenance on the recloser and control cubicle are located in the Siemens or Cooper instruction book. POLE-TOP SECTIONALIZERS AND VOLTAGE SWITCHES (VS) Sectionalizer and VS – Check – Energized 1. Perform a visual inspection and record the operations counter. 2. Perform touch potential testing on all controls or components that may be accessible to the public. Sectionalizer and Voltage Switch IR Survey Inspection 1. Perform an Infrared test during a Distribution IR Survey or as required. Sectionalizer and VS Major Maintenance – De-Energized Note: Sectionalizers that have problems may be replaced and taken back to the shop for inspection/maintenance. 1. Perform a power factor test to measure contact resistance to provide an indication of contact condition as well as loose carrying parts. 2. Perform an insulation resistance test (utilizing a micro-ohm meter), phase-to phase, and phase-to-ground. 3. Test for proper operation on the Sectionalizer. 4. Inspect and dress the main and control contacts, if necessary. 5. Inspect interrupting chambers for both mechanical and electrical conditions. 6. Check all electrical and mechanical connections for tightness. 7. Thoroughly clean and remove carbon from the internal mechanism and tanks. 8. Check for traces of tracking on all insulating parts and moisture absorption of the bottom of the tank liner. 9. Check and adjust the component parts of the operating mechanism, if required. 10. Check all gaskets. 11. Ensure the tap wires are properly tightened. 12. Paint, where necessary. 13. Test Oil (Color and dielectric strength); filter and/or replace as necessary.Page 118 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 118 of 297 Appendix 1 – Recloser Battery Replacement Cooper Form 6 Controls IMPORTANT: Disconnect switches for AC sensing and power connections are necessary to isolate the Form 6 control for testing and servicing. 1. Enable GND TRIP BLOCKED to allow for ground trip to be disabled when reenergized. a) Press the CHANGE button on the Operator Panel to enter the CHANGE mode. b) Press the GND TRIP BLOCKED button within ten seconds after entering the CHANGE mode. NOTE: If the GND TRIP BLOCKED button is not pressed within ten seconds, the function is not activated. 2. Disconnect the old battery and replace it with a new one. Siemens CAUTION The batteries supplied with the Recloser can deliver high discharge currents. This may result in personal injury or damage to equipment. Do not reverse polarity when making battery connections. Immediately replace any frayed leads or damaged connectors. 1. Turn off the battery circuit breaker. 2. Unplug the batteries and replace them with new ones. 3. Confirm the battery polarity is correct. 4. Turn on the battery circuit breaker. 5. Verify that “Battery Normal Status” displays.Page 119 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 119 of 297 Appendix 1 – Battery Replacement Cooper Form 2, Form 3 and Form 3A Controls