  1. Page 131 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 131 of 297 Appendix 1 – Battery Replacement Cooper Form 4C Power Supply Replacement
  2. Page 132 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 132 of 297 Appendix 1 – Battery Replacement Replacing the Cooper Form 6 Battery 1. 2. 3. 4. Remove the control from service as follows: Enable GND TRIP BLOCKED to allow for ground trip to be disabled when reenergized. a) Press the CHANGE button on the Operator Panel to enter the CHANGE mode. b) Press the GND TRIP BLOCKED button within ten seconds after entering the CHANGE mode. Note: If the GND TRIP BLOCK button is not pressed within ten seconds, the function is not activated. Disconnect the battery. Remove the control AC sensing and power connections from the control using a separate disconnect switch. WARNING: Hazardous voltage. If the recloser is energized while the control cable is disconnected, the CT secondaries can generate high voltages. Contact with high voltage can cause severe personal injury or death. CAUTION: Equipment misoperation. Disconnect all control power sources prior to disconnecting the control cable from the control. Failure to comply can result in recloser misoperation at the time of disconnection or reconnection of the control cable to the control. 5. Disconnect the control cable from the control. Note: Do not disconnect any of the three recloser cables from the Reclosers or junction box unless all of the above steps have been completed. CAUTION: Hazardous voltage. Cable conductors attached to NOVA Reclosers will remain at 53VDC potential after disconnection of source power to the recloser. Contact with any pins at the end of cables directly or indirectly connected to a NOVA recloser can result in personal injury or equipment damage. 6. 7. 8. 9. 10. Remove any control input and status output wiring from TB1, TB3, and TB4. Disconnect any serial communications ports and IRIG-B timing connections. Disconnect the ground from the control. Disconnect and remove the battery. Install the replacement battery. CAUTION: Equipment misoperation. Do not connect this control to an energized recloser until all control settings have been properly programmed and verified. 11. 12. Reconnect the ground cable to the control. Ensure the cable is properly connected and supported. 13. Plug in the control battery.
  3. Page 133 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 133 of 297 Note: The Form 6-TS recloser control will not power up until AC power is applied. CAUTION: Equipment misoperation. Verify that the 120/240 VAC selector switch is correctly set for incoming voltage. Failure to comply may cause misoperation (unintentional operation) of the control and/or equipment damage resulting in personal injury. 14. 15. 16. Verify the selector switch on the Power Supply / Battery Charger Board is set to the correct position based on the incoming power supply: • For 120 VAC incoming power, the selector switch must be set to the 115V position. • For 240 VAC incoming power, the selector switch must be set to the 230V position. Apply AC power to the control. Disable GND TRIP BLOCKED. a) Press the CHANGE button on the Operator Panel to enter the CHANGE mode. b) Press the GND TRIP BLOCKED button within ten seconds after entering the CHANGE mode. Note: Once selected (or after ten seconds), the control returns to normal operation. 17. Verify the control clock is set to the current time after AC power has been reapplied. Note: The control clock may require resetting if the operating power has been disconnected for more than 30 days. Refer to the manufacturer’s technical manual for details.
  4. Page 134 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 134 of 297 APPENDIX 10 INSPECTION, TREATMENT, RESTORATION AND REPLACEMENT GUIDELINES DISTRIBUTION SYSTEM WOOD POLES
  5. Page 135 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 135 of 297 5.61 Wood Poles General Description This procedure establishes a uniform approach for distribution wood pole inspection, treatment, restoration and replacement. It defines the schedule, inspection, and reporting requirements for these facilities. This applies to all wood distribution poles within the custodianship or the maintenance responsibility of Eversource Energy. It shall include push braces and guying stub poles as well as line poles scheduled for the given year. Facilities/Equipment • Wood Poles 5.61.1 Inspection and Maintenance Activity Schedules 5.61.1.1 Table 1 – Wood Poles Maintenance Intervals Wood Poles All Maintenance Schedule PM Task Condition Monitoring N/A Time-Directed Routine Inspection 15Y (Notes 1 & 2) Condition-Based Priority Reject Schedule repairs or replacement. (Note 3) A/R (Note 4) Failure Finding Corrective Maintenance A/R In Table 1, the intersection of the row and column indicate the age-based inspection or maintenance interval for wood poles based on the preservation treatment listed in the column heading. For example, the age requirement for a Routine Inspection is 15Y (or 15 Years). The abbreviations used for the intervals are: Y = Year, i.e. 2Y = 2 Years A/R = As Required N/A = Not Applicable Note 1 = 15 years is the minimum requirement for pole inspection. This interval may be changed due to contractual requirements with joint owners. Note 2 = The type of inspection performed shall be determined by the age of the pole and its type of treatment, as shown in the following table:
  6. Page 136 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 136 of 297 Inspection Type Visual Sound & Bore Ground Line Evacuate Creosote, Penta, all others 0 to 9 years old 10 to 14 years old 15 years old and older CC 0 to 19 years old 20 years old and older If decay is indicated by Sound & Bore Note 3 = Check the pole within 48 hours and make the pole safe within 5 working days. Note 4 = Complete the repair or replacement within one year of determination of need following inspection 5.61.2 Maintenance Categories 5.61.2.1 Routine Inspection – Time Directed 1. Routine inspection activities are detailed in EMP Instruction 6.61. 5.61.2.2 Priority Reject Poles 1. Priority reject pole activities are detailed in EMP Instruction 6.61. 5.61.2.3 Normal Reject Poles 1. Normal reject pole activities are detailed in EMP Instruction 6.61. 5.61.3 Evaluation of Restorable Poles 1. The evaluation activities for restorable poles are detailed in EMP Instruction 6.61A. 5.61.4 Failure Finding 1. Failure finding activities are detailed in EMP Instructions 6.61 and 6.61A. 5.61.5 Research/Background Publications and other reference materials from these organizations were used in the development of this program. • National Electric Safety Code, as directed by section DER 0701 “Wood Poles – Aging Infrastructure” • TD 953 – “Inspection, Treatment, Restoration and Replacement Guidelines for Dist Sys Wood Poles” 5.61.6 Wood Poles - Maintenance Basis Documentation The maintenance activities and their schedules are based on industry experience, manufacturer’s recommendations, feedback from the service technicians, and the subject matter expert, who in this case, is a Senior Engineering Technologist for Distribution Engineering Design.
  7. Page 137 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 137 of 297 Basis Requirement Routine Inspection at 15Y Interval Inspection required by the NESC - The National Electrical Safety Code requires that poles are inspected as often as experience shows it necessary to maintain the strength required for the pole to remain in service. According to charts developed by Osmose on National averages, the percentage of reject poles starts to rise between ten and fifteen years. However, because Eversource is mostly in a "Moderate Deterioration" zone (National Wood Preservers Association Book of Standards) we could expect better than average results from an inspection program. Eversource's experience finds that a fifteen year inspection and treating program keeps the reject rate reasonable. NOTE: Eversource's line mechanics are taught to visually inspect and sound any pole before climbing it. The 15 year inspection is required, but it is acknowledged that PSNH has an existing contract to perform their inspections at a 10 year interval. EMP 6.61 - Routine Inspection Visual A visual (only) inspection is to be performed on: •CCA Treated Poles -----------------------------------0 – 19 years old •Creosote, Penta, and all other poles--------------0 – 9 years old This shall be the first step for inspecting each pole, and shall include a thorough observation of the above-ground portion of each pole and all attachments. Record any findings into the system appropriate for the activities being performed. 1. Visually inspect the pole for the following defects: • Pole top split or deteriorated • Crossarm damaged or decayed • Broken or damaged insulator • Broken or damaged spacer • Buried anchor guy • Broken guy wire • Leaning pole 2. Check to see if the pole is set shallow. The following table indicates the correct distance from the ground-line to the bottom of the pole brand: Length of Pole (in feet) 25 Groundline Distance To Butt To Brand 5 5 30 5.5 4.5 35 40 6 6 4 4 45 6.5 3.5 50 7 3 55 7.5 6.5
  8. Page 138 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 138 of 297 •Measure the distance from the ground line to the bottom of the pole brand. If the distance is more than 6 inches greater than the value in the 3rd column of the above table: a. Attach an aluminum pole tag letter “S” just below the bottom of the pole brand. b. Record the information into Cascade or into the appropriate inspection record. •Do not record this pole as set shallow if there is an “R” tag attached to the pole just below its brand, as this indicates the presence of enough rock to support the pole. 3. Install a reflector on all wood poles located within six feet (6 FT) of any roadway if no guard rail is present. The reflector shall be installed on the wood pole in accordance with DTR 05.091 and in the direction of travel. If unable to install, no follow-up action is required. Sound & Bore Inspection Pole in Ground A Sound & Bore Inspection is performed on: •CCA treated poles---------------------------20 years old and older •Creosote, Penta, and all other poles----10 – 14 years old. 1. Sound the pole all around, listening for hollow sounds that may indicate decay or insect damage. • Strike the pole firmly (not hard) with a hammer from the ground line upward to as high as you can reach, approximately 8 feet above the ground line. • Striking intervals shall be 2” to 3” apart at ground line and where ever decay or insect damage is suspected. • Above the ground line, use 12” intervals. 2. Pull back the soil at ground line on two sides of the pole, giving pullback priority to any suspicious sounding areas or visually suspect areas. •Each pullback should be approximately shovel’s depth and 6” wide. 3. Bore a 3/8” hole into the pole at a 45 degree angle from the ground line to the center of the pole, and wherever there were any suspicious areas detected by sounding, in order to detect insect damage or damage due to decay. • If no insect damage or decay is detected, do not treat the pole. 4. Evacuate any voids found within the pole • If the pole passes inspection, fill the void and coat the outside with the appropriate treatments. 5. Plug all bored holes with 7/16” treated dowels (2” to 3” long), and tamp the pulled-back soil neatly into place. Sound & Bore Inspection – Poles In Pavement This includes those poles that are surrounded by pavement, or that have riser pipes or other obstructions that prevent excavation.
  9. Page 139 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 139 of 297 A Sound & Bore inspection is performed on: • CCA treated poles ------------------------------20 years old and older • Creosote, Penta, and all other poles--------10 - 14 years old Bore each pole with the 3/8 inch x 18 inch or 24 inch inspection bit at a 45 degree angle from above ground line to below ground line to look for decay or insect damage. 2. Evaluate decay as specified in the Circumference Measurement section on page 5. 3. Treat the pole. If the pole exhibits some decay, but still passes inspection, internally treat the pole with: • “WOODFUME” if there are no internal voids • “Hollow Heart” if there are internal voids. • MITC-FUME/MP400-EXT/OSMOSHIELD as appropriate Ground Line Inspection A ground line inspection is performed on: • Creosote, Penta and all other poles---------15 years old and older 1. NOTE: Do not excavate a pole set shallow until Division Operations advises that the situation has been corrected. 1. 2. 3. 4. 5. 6. 7. 8. 9. Excavate each pole all around to a depth of 18 inches, leaving at least 4 inches of radial clearance at the bottom of the excavation. Use a wire brush to clean the below-ground portion of the pole and use a check scraper to locate any exterior decay. Sound the pole all around. Bore a 3/8” hole into each pole at a 45 degree angle from the ground line to the center of the pole and wherever decay or insect damage is suspected. Plug all bored holes with a 7/16” preservative treated wood dowel (2” – 3” long). Use a shell thickness indicator to measure voids and the thickness of the outer shell. Remove by chipping, all loose weathered wood and wood overhanging deteriorated wood to at least 6 inches above ground line. See the following section on Circumference Measurements. Remove all exterior wood from the pole surface to be treated using care not to remove any sound wood unless that is essential to inspection/treatment. Remove all chipped wood debris from the hole and properly dispose of it away from the site. Circumference Measurement Evaluate a pole if its effective ground line circumference has been reduced by decay or insect pockets, hollow heart, mechanical damage or has had exterior decayed wood removed by chipping prior to ground line treatment. Calculate the percentage of the remaining pole strength based on the effective ground line circumference and the existing conductor and attachment load. Remove from service, any corner (angle) poles,
  10. Page 140 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 140 of 297 dead end poles, guy stubs and push braces with less than 80% of their original ground line circumference. Circumference measurements for new poles are listed below in the following table. Length of Pole or Feet From Top Minimum Dimension (in Inches) 0’ Class H-2 H-1 1 2 3 4 5 Diameter Circumference 9.9 31.0 9.2 29.0 8.6 27.0 8.0 25.0 7.3 23.0 6.7 21.0 6.0 19.0 2’ Diameter Circumference 10.2 31.9 9.5 29.8 8.8 27.8 8.2 25.8 7.5 23.7 6.9 21.7 6.3 19.7 5’ Diameter Circumference 10.6 33.2 9.9 31.1 9.3 29.1 8.6 27.0 7.9 24.9 7.3 22.8 6.6 19.7 10’ Diameter Circumference 11.3 35.4 10.6 33.2 9.6 30.0 8.9 28.0 8.3 26.0 7.7 24.0 7.0 22.0 15’ Diameter Circumference 12.0 37.6 11.2 35.3 9.9 31.0 9.2 29.0 8.6 27.0 8.0 25.0 7.3 23.0 20’ Diameter Circumference 12.7 39.8 11.9 37.4 10.7 33.5 10.0 31.5 9.4 29.5 8.8 27.5 8.1 25.5 25’ Diameter Circumference 13.4 42.0 12.6 39.5 11.6 36.5 10.9 34.0 10.2 32.0 9.5 29.5 8.7 27.5 30’ Diameter Circumference 13.8 43.5 13.2 41.5 12.4 39.0 11.6 36.5 10.9 34.0 10.0 31.5 9.2 29.0 35’ Diameter Circumference 14.6 46.0 13.8 43.5 13.1 43.5 12.3 38.5 11.5 36.0 10.7 33.5 9.9 31.0 40’ Diameter Circumference 15.4 48.5 14.5 45.5 13.7 43.0 12.8 40.5 11.9 37.5 11.1 35.0 10.3 32.5 45’ Diameter Circumference 16.1 50.5 15.1 47.5 14.3 45.0 13.3 42.0 12.0 39.0 11.7 36.5 50’ Diameter Circumference 16.6 52.0 15.8 49.5 14.7 46.5 13.8 43.5 12.9 40.5 Ground line (diameter or circumference) dimensions for a pole are measured at 5 feet from the bottom of the pole. Reject Poles Priority Poles Reject all priority poles. A priority pole is one which is in imminent danger of falling because it is completely decayed across the grain, or it has a hollow heart with sound wood in the outer shell of one inch thickness or less. • Use the C-aluminum pole tag which measures 2 inches high and 21/2 inches wide. It has a clear aluminum arrow with an “X” inscribed in a circle imposed on the shaft of the arrow on a red background.
Words on different pages

Text of OCC-890_Final.pdf

Extracted from the file · 1 page · 553 characters

Words on different pagesRead the text of OCC-890_Final.pdf

As listed on the current system

Question(s) Answered 888, 889, 890 (The Connecticut Light and Power Company) Date Filed: 10/09/2026