Interrogatory responses
Answers to questions 888, 889, 890
Files5
OCC-888_Final.pdf
PDF · 101 KB · 1 pageText searchable
Download OCC-888_Final.pdfRead the text of OCC-888_Final.pdf
OCC-888 Attachment 1.pdf
PDF · 1.0 MB · 1 pageText searchable
Download OCC-888 Attachment 1.pdfRead the text of OCC-888 Attachment 1.pdf
OCC-888 Attachment 2.pdf
PDF · 8.4 MB · 297 pagesText searchable
Download OCC-888 Attachment 2.pdfRead the text of OCC-888 Attachment 2.pdf
OCC-889_Final.pdf
PDF · 75 KB · 1 pageText searchable
Download OCC-889_Final.pdfRead the text of OCC-889_Final.pdf
OCC-890_Final.pdf
PDF · 74 KB · 1 pageText searchable
Download OCC-890_Final.pdfRead the text of OCC-890_Final.pdf
Page 211 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 211 of 297 7. 8. 9. 10. 11. 12. For cases where multiple network transformers exist in a vault, it will generally not be possible to de-energize all of those units for a variety of reasons. Therefore, prior to working on a network transformer, where multiple network transformers exist in a vault, maintenance records shall be reviewed for major deficiencies and/or major maintenance completion within the maintenance cycle per the Eversource Maintenance Program prior to working in the vault. • If records indicate that major maintenance for all transformers within the vault is up-to-date, and that there are no major deficiencies, then work may proceed. • If major deficiencies or major maintenance was not completed, management will jointly work with employees for the appropriate steps to follow. With the exception of the commissioning of a new network unit, 480V/277V network units shall have major maintenance completed with the primary deenergized. 216V/125V network units may be worked on with the primary energized as long as no oil work (i.e. oil sampling, topping off and/or retrofilling) is being performed. • Network major maintenance that includes any oil work (i.e. primary equipment oil sampling, topping off or the like) shall only be completed with the primary equipment de-energized Job Setup: Work zones, requirements for various jobs, switching requirements. All arrangements should be completed or setup prior to beginning the job. These include cones, signage, and police or traffic control. Check holes prior to entry for cleaning needs, i.e. pumping water, debris, contaminates, visible oil, and providing samples for lab analysis. Review the manufacturer’s manuals for all safety notations (Danger, Warnings, and Cautions), as needed. These may be in sections of the manual other than with the instructions. Supervision shall ensure the assigned workers have primer, paint, and any additional material needed for cleaning and preservation of the exterior of the network protector prior to departing the work center. Prepare the vault for entry. a. Check for dangerous atmospheric conditions before entering the vault using company-approved atmospheric sampling equipment b. Ventilate the vault, if required, in accordance with the Eversource Employee Safety Manual. c. Remove any standing water or debris from the vault in accordance with ENVIROWI-0105 or company-specific requirements, as required. This is located in the Environmental and Facility Procedures section of the Distribution Engineering Standards Bookshelf.Page 212 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 212 of 297 Network Protector Tools The following fully insulated tools are available and may be useful for Network Protector Service: Tool Description NU Stock Code Wrench, Torque, 1/2” drive 0441650 Wrench, Socket, extension bar, 1/2” drive, 12” long 0441649 Socket size 3/4”, 1/2” drive, 6 pt. 0441652 Socket size 9/16”, 1/2” drive, 6 pt. 0441651 Wrench, Socket, T Handle, 33” long, 9/16” socket 0441646 Wrench, Socket, T Handle, 33” long, 3/4” socket 0441647 Wrench, Socket, T Handle, 33” long, 7/8” socket 0441648 Test Probe 0441607 ETI Relay Programmer 0400188 MPCV Relay Programmer 0445902 The above listed wrenches may be available in other lengths by special order. The insulation from the time of original manufacture has been increased at the request of Eversource and stock code revisions will reflect “FI” for “Fully Insulated”. NOTE: The orange surface insulation on these tools has a yellow undercoat. If yellow is detected on the surface due to cuts or punctures, the surface insulation has been compromised and the tool should be retired. Rolling Out and Isolating the Protector Reminder: Although it is not shown in some of the following figures, proper PPE must be worn while performing maintenance and testing on all Network Protectors. NOTE: The MG8/9 Network Protectors are live-front, bolted-in-place devices requiring the handling of energized links and/or fuses. Because of this, it is imperative that they be out on the rails and isolated from the energized bus work of the enclosure before any work or testing is done. The MG8/9 requires the following procedure for its removal from the housing. 1. 2. 3. Prior to operating the network protector handle, vent the protector cabinet as follows: a) Loosen the enclosure cover bolts on the side opposite from the operating handle in order to vent the protector. Operate the network protector handle while standing to the side of the enclosure or as far away as possible from the front of the enclosure. Leave the handle in the “open” position. Verify that the network protector mechanism is in the open position as follows:Page 213 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 213 of 297 a) Inspect the network protector position indicator through the network protector enclosure window to ensure the Positive indicator reads OPEN. b) Use a clamp or rope style current transformer (CT) around the conductors of each phase, verify that the current on each phase is zero. (Zero current may indicate that the breaker position is open or the network protector fuses or cable limiters are blown.) c) Record the secondary voltages. CAUTION: If the protector contacts do not open, stop all work and place the network protector in a safe condition and contact your supervisor. 4. Ensure that there are adequate clearances between energized parts and the ground and that the top housing and bottom barriers are in place. • Install temporary boards as necessary to provide adequate Clearances. CAUTION: The following steps require the use of a Company-approved insulated wrench and that you use wear the appropriate PPE. 5. For top-connected protectors: • Remove the fuses without disturbing the fuse connecting blocks. See Figure 1. • Remove the fuse connecting blocks and the screws securing the protector unit to the low voltage transformer bushing. See Figure 1. Fuse connecting block Fuse Figure 1 – Fuse Connecting Block and FusePage 214 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 214 of 297 For protectors above 1875 amperes: • Remove the fuses at the top of the protector. • Remove the disconnect links at the bottom of the protector unit. CAUTION: On Network Protectors with the transformer bus on the bottom, remove the transformer links first to allow the removal of the fuse nuts. 6. 7. 8. Store all fuses, fuse nuts, and links on the inside door ledge of the Network Protector. Loosen the 4 bolts that fasten the rollout unit to the housing. Install the rail extensions, ensuring they are locked in place, and move the rollout unit from the housing. Breaker Mechanical Inspection: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Record the counter reading. Check for broken or damaged barriers on breaker and housing. Check for any signs of liquid entry into enclosure, transformer throat, etc. Check for indication of overheating, including discoloration of the bus or barrier boards or greenish brown paraffin like substance in the bottom of the enclosure and area as this may indicate degradation of insulation backboards. Use a drop of oil on all mechanism pins. Inspect and clean the motor housing race. a) Inspect the motor and brushes for wear. b) Check the torque brake for absence of grease or oil and for wear on the drum and shoe surfaces. c) Check the gear reducer oil level. Inspect for loose wiring at control components: • Motor control relay • Resistors • Terminals • Auxiliary switches Check for frayed, cracked, or damaged control wire. Asbestos coated wiring or older wire harness may require an additional dielectric test to determine if it has reached its useful life. See Dielectric Testing. Check for loose hardware. Check the door gasket to ensure it is in good condition. Fuse Inspection: (See Figure 2.) a) For the Y and Z fuses: o Examine the fuse element to ensure that no visible cracks are present in the element and there are no signs of slow melt. b) For the alloy fuses: o Examine the fuse element to ensure that no visible cracks are present in the element and there are no signs of slow melt. o Place the fuse flat on the top surface of the housing door.Page 215 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 215 of 297 o Ensure that the fuses rock. Discard any alloy fuses that are annealed flat, thus eliminating the required spring action. NOTE: 480Y/277 Voltage units alloy fuses (shown on left) require the extended arc horn and addition barrier to properly clear the phase. Fuses are embossed with the style number that correlates to ampere and curve characteristics. Extended Arc Horns Figure 2 – Fuses 12. 13. 14. Remove and inspect the arc chutes and contacts. CAUTION: Some arc chutes are made from asbestos. Use hazardous material handling procedures for these and do not clean them. Replace them instead. • Arc chutes must be free and clear of any carbon buildup. Clean as necessary. • Inspect contacts for excessive pitting and dress the contacts as necessary. Check the cross bar insulation and ensure that no buildup is on the backboard between the phases. Check for melted paraffin in the bottom of the enclosure which indicates possible deterioration of the backer board. Testing Sequence: The next section is a series of tests defined to ensure proper operation at normal condition and at fault duty. It is important to perform the following tests in this order: Test 1 Manual Breaker Operation Test Test 2 Insulation Resistance Testing (Megger) Test 3 Micro-Ohm Test (Ductor) Test 4 Mechanical Electrical Test (Voltage Only Testing)Page 216 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 216 of 297 Test 5 Relay Tests Test 6 Ground Fault Test (480V Unit Only) Test 1 – Manual Breaker Test 1. Operate the breaker manually while it is on rails using an external closing prop on the handle. Close and trip the breaker 5 times to verify proper mechanical operation. At least one of these operations should be performed with the protector in the enclosure with the fuses removed. Test 2 – Insulation Resistance Test (Megger) The GE MG8/9 breaker is constructed upon a common insulated back board and requires periodic insulation integrity checks to ensure proper isolation. In addition, the breaker construction relies upon an insulated cross bar on the breaker. This ties all 3 phases together and must be periodically checked to ensure compliance. 1. 2. 3. Remove all potential leads from the breaker bus. Remove A, B, and C Links to isolate the resistance circuit. Using at least a 1,000 VDC Megger, complete the 9-point test outlined in the chart below: An acceptable value is 10 Meg Ohms or greater for a 1 minute time duration. Reading Location Inspection Value Reading Location Inspection Value Reading Location Inspection Value Backboard Insulation Breaker Position OPEN N1 to T1 N2 to T2 N3 to T3 Crossbar Insulation Breaker Position CLOSED N1 to GND N2 to GND N3 to GND Crossbar Insulation Breaker Position CLOSED N1 to N2 N2 to N3 N3 to N1 Test 3 – Micro-Ohm Test (Ductor) Perform an as-found and then after cleaning, a final ductor test. The maximum acceptable value for ductor testing is 25 micro-ohms or less, using a 100 Amp ductor.Page 217 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 217 of 297 1. 2. With the breaker closed, connect the micro-ohm test leads to the network protector. Test and record the value. • If the contact resistance (micro-ohm reading) is greater than 25 microohms: Open the breaker and clean the contact surface with Scotch Brite. Re-test and record the “as-left” value. Test 4 – Mechanical – Electrical Test (Voltage Only Testing) Mechanical testing is defined as a “voltage only test” without the use of any network relays (electro-mechanical, solid state or digital). This testing is defined in the IEEE standard for Network Protectors C57.12.44. The basis for this type of testing is the minimum trip and close criteria required. 1. 2. Remove all Network Relays. • The phasing relay Terminal Points 1 & 2 (wires No. 6-6A) must be jumped. Connect the Test Set according to the manufacturer’s instruction manual and local system operating conditions (phasing). CAUTION! - Failure to connect the leads in the correct sequence will cause damage to the Network Protector Test Set. Reminder: Proper PPE must be worn while attaching leads to an energized bus. MIN CLOSE TESTING 1. Apply full system voltage to ensure closing operation when the CLOSE button is pressed on the TEST SET. 2. Trip the breaker with the trip lever. 3. Apply 73% of the L-L system voltage. See Table 1. The breaker should NOT close at this level. If the breaker closes, the motor control relay will need adjustment. The Motor Control Relay is located below the mechanism. To make adjustments: a) Remove the steel guard. b) Use 3/8” wrenches to hold the bottom fixed nut and adjust the upper nut. o Compress the spring for a higher value. o Lengthen the spring for a lower value. 4. Apply 80% of the L-L system voltage. See Table 1. The breaker should close.Page 218 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 218 of 297 Table 1 Test Values Test a) Minimum Trip b) Minimum Motor Close Voltage c) No Pickup (Motor Relay) d) Min Pickup (Motor Relay) % 7.5% 73% 73% 80% 125/216V 16.2V or Less 158V or Less 158V or Less 160V – 173V 277/480V 36.0V or Less 350V or Less 350V or Less 354V – 384V Mechanical – Electrical Test (continued) MIN TRIP TESTING 1. 2. With the breaker closed, apply 7.5% of system voltage. See Table 1. Press the TRIP button on the test set. • If the protector does not trip at this level, then a sensitivity adjustment is needed on the shunt trip level assembly. The shunt trip assembly and adjustment screw are located on the upper left side of the mechanism. NOTE: To initially set this device, perform the following: a) Manually close the breaker. b) Adjust this screw upward until the breaker opens. c) Turn the screw back down 1 turn after the opening. d) Tighten the lock nut. e) Re-test the min level to determine if this adjustment fits the trip range. TRIP FREE TEST NOTE: During Trip Free operation, verify that the main contacts do not close. Perform the following at full system voltage. 1. 2. With the breaker open, hold the trip latch and hold the “close” button on the protector test set. After two or three operations, release the trip latch. The protector should close on the next close operation. Test 5 – Relay Tests Electro-Mechanical Relay Tests 1. Perform the Master Relay Overvoltage test and adjust the relay as necessary in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector InstructionsPage 219 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 219 of 297 2. 3. 4. Perform the Phasing Relay Overvoltage test and adjust the relay as necessary in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions Perform the Reverse Current Limiting Trip test and adjust the relay as necessary in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions If a BN relay is installed, perform the Timing test and adjust the relay as necessary in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions Test 5 - Relay Tests (continued) Solid State / Microprocessor Relays 1. 2. 3. Perform an Overvoltage test and adjust the relay in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions Perform a Reverse Current Trip test in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions If a Time Delay is used, perform a Time Delay test in accordance with the following documents. Record the As-Found and As-Left values. • Network Protector Test Set Instructions • Relay Instructions • Network Protector Instructions Test 6 – Ground Fault Test (480V units only) The ground fault protection circuit between the protector and the customer main service is owned and maintained by the customer. Testing the lock out may call for all protectors to trip. An up-to-date drawing must be made available and reviewed to determine those steps which must be taken to prevent tripping of all protectors.Page 220 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 220 of 297 Verify trip from lockout and block the close of the protectors on all units having a ground fault scheme. NOTES: 1) 2) The Ground Fault system is typically Customer-owned, and the Lockout is typically Eversource Owned. It is important to have an up-to-date print of the scheme prior to performing a test. This test is only to be performed on those units equipped with a ground fault system. GE MG8/9 Re-install Procedure Reminder: Proper PPE must be worn while performing the following steps. CAUTION: A misaligned operating handle can result in the network protector mechanisms remaining in the “Automatic” position with the network protector operating handle in the “Open” position. 1. Check the operating handle alignment before rolling the protector back into its housing. Ensure the base of the handle is aligned with the slot into which it will fit. See Figure 3. Shaft dog flats fit into this slot in the Operating Handle Gear Shaft Dog Flats Figure 3 – Operating Handle Alignment Before the Protector is Reinstalled 2. Roll the unit back into the housing to its installed position. Proper alignment of the shaft dog is assured when the two flat surfaces of the shaft dog are fully engaged in the slot on the enclosure’s geared operating handle. See Figure 4.
Text of OCC-890_Final.pdf
Extracted from the file · 1 page · 553 characters
As listed on the current system
Question(s) Answered 888, 889, 890 (The Connecticut Light and Power Company) Date Filed: 10/09/2026