Interrogatory responses
Answers to questions 888, 889, 890
Files5
OCC-888_Final.pdf
PDF · 101 KB · 1 pageText searchable
Download OCC-888_Final.pdfRead the text of OCC-888_Final.pdf
OCC-888 Attachment 1.pdf
PDF · 1.0 MB · 1 pageText searchable
Download OCC-888 Attachment 1.pdfRead the text of OCC-888 Attachment 1.pdf
OCC-888 Attachment 2.pdf
PDF · 8.4 MB · 297 pagesText searchable
Download OCC-888 Attachment 2.pdfRead the text of OCC-888 Attachment 2.pdf
OCC-889_Final.pdf
PDF · 75 KB · 1 pageText searchable
Download OCC-889_Final.pdfRead the text of OCC-889_Final.pdf
OCC-890_Final.pdf
PDF · 74 KB · 1 pageText searchable
Download OCC-890_Final.pdfRead the text of OCC-890_Final.pdf
Page 26 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 26 of 297 Town WINDSOR WINDSOR LOCKS WOLCOTT WOODBURY WOODSTOCK Maintenance on Backbone Miles 12.90 11.93 22.26 22.53 0.00 Standard Maintenance on ETT on Grand Total Laterals Miles Laterals Miles Miles 12.54 0.15 25.59 13.95 1.24 27.13 57.35 0.00 79.61 75.47 8.78 106.79 0.07 0.00 0.07Page 27 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 27 of 297 SPECIFICATION for LOCAL DISTRIBUTION LINE CLEARANCE TREE WORK and BRUSH CONTROL Revision 2014-BPage 28 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 28 of 297 Table of Contents Section Page Number General Requirements .................................................................... 1 Scope of Work ................................................................................. 2 Scheduled Maintenance Trimming (SMT)...................................... 2 Enhanced Tree Work....................................................................... 4 Maintenance Enhanced Tree Trimming ......................................... 5 Mid-Cycle Trimming .........................................................................6 New Business and Capital Construction ....................................... 6 Tree Removal................................................................................... 6 Stumps ............................................................................................. 7 Brush and Vine Removal ................................................................ 7 Wood and Chip Disposal ................................................................ 7 Substation Perimeter Clearing ....................................................... 8 Definitions ..................................................................................... 10 2019 William Van Dam, Director - Vegetation Management Robert D. Allen, Manager – Massachusetts & New Hampshire Vegetation Management Sean D. Redding, Manager - Connecticut Vegetation Management - Transmission Allen Carey, Manager - Connecticut Vegetation Management Paul Sellers, Manager – Massachusetts Vegetation ManagementPage 29 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 29 of 297 Eversource Specification for Local Distribution Tree Work and Brush Control 1. General Requirements This document describes the scope of work and technical requirements for the Eversource Distribution Line Clearance Program. All work shall be performed by qualified line clearance contractors. Safety shall take precedence over all requirements described herein and at no time shall work be performed in an unsafe manner. • All contact with the public and government officials shall be done in a courteous manner. • Work shall be subject at all times to inspection by Eversource and government officials. The crew foreman, or the contractor's designee, shall notify Eversource of the crew's daily work location and of any change made during the day. • Work shall be performed in such a manner that it will not interfere with or affect in any way the operation of any existing energized lines or electrical equipment, except as specifically directed by Eversource. • All line clearance work shall be performed in strict accordance with all applicable federal, state and local governmental laws and regulations or approved standards and safety practices – ANSI A300 (Part 1)-2008, Best Management Practices – Utility Pruning of Trees, ANSI Z133.1-2012, OSHA 29 CFR 1910.269. The contractor shall be responsible for the knowledge, supervision and enforcement of them. • Each crew will have on the vehicle the Eversource Image Summit forms and door hanger. Administration of the process will be in accordance of all Eversource Image Summit procedures and guidelines. • When necessary, the contractor requests permission from tree owners and others to perform line clearance tree work around electrical conductors. Where the tree owner is not at home, use the appropriate permission card and customer brochure. For all refusals, light trims or no contacts the contractor shall fill out a copy of form DISTRIBUTION LINE CLEARANCE MODIFICATION FORM and submit the form weekly, or approved electronic form. • The crew foreman shall complete and submit weekly company approved reporting forms, adding information daily for all T&M work. Paper forms of this report shall be submitted to Eversource no later than Tuesday of thePage 30 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 30 of 297 week following the completed work week. Electronic forms shall be submitted at least weekly, depending on syncing and uploading system requirements. • The line clearance crew shall work progressively along the distribution system starting at the substation, or as directed by Eversource, and shall complete all work on a given portion of the line before starting work at another location, unless otherwise approved by Eversource. • Re-trimming will be required to correct all situations where trimming quality is determined by Eversource to be improper. • Climbing irons shall not be used in any tree unless the tree is to be removed. • Wherever Eversource is solely responsible for clean-up on scheduled work, clean-up shall be completed daily and the site shall be left in at least as neat and orderly condition as it was found. 2. Scope of Work This Specification covers the trimming and removal of trees and brush, including the use of herbicides (CT only) for brush control along rural and urban overhead electrical lines and around substations owned or used by Eversource. This includes clearing for existing lines as well as for new lines, and applies to local distribution only, along and off-roads, and not bulk supply distribution rights-of-way. Each tree must be evaluated on its own at the time it is trimmed. The tree crew must consider the variables including tree species, condition, growth rate and location. 2.1. Scheduled Maintenance Trimming (SMT) 2.1.1. Primary Conductors Conductor clearances relative to various primary wire positions are shown in Figure 1. Normally, remove all branches within the clearance zone bounded by the dashed line perimeter and all overhead hazards within reach of a 55’ aerial lift. Watersprouts and suckers shall not be trimmed; they shall be removed back to the originally established clearance level.Page 31 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 31 of 297 Figure 1 CLEARANCE ZONE DIMENSIONS For PRIMARY VOLTAGE CONDUCTORS (2.4 to 34.5 kV) 2.1.1.1. Overhead Clearances 15 feet overhead clearance shall be measured vertically upward from the highest primary. 2.1.1.2. Side Clearances 8 feet (10 feet MA-E) side clearance shall be measured horizontally outward from the outermost primary. 2.1.1.3. Under Clearances 10 feet under clearance shall be measured vertically downward from the lowest primary. 2.1.1.4. Brush and Vine Clearances Selectively remove only that tree brush which is presently at least 16 feet tall within the zone or growing into the zone. All vines which are growing up poles or guy wires shall be cut at the ground line and cleared 6 feet up the pole or guy.Page 32 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 32 of 297 2.1.2. Secondaries Without Primaries Above and Service Drops 2.1.2.1. Triplex Do not clear around them unless authorized by Eversource. When approved, trim only limbs in contact with the conductor. Trimmed branches shall provide 2 feet of clearance around all conductors. 2.1.2.2. Open Wire Secondary Do clear, trimmed branches shall provide 2 feet of clearance around all conductors. 2.1.3. Tree Removal Remove all hazard trees up to and including 16 inches DBH within 8 feet of the outermost conductor. The removal of any tree greater than 16 inches DBH must be approved by Eversource. Eversource will provide specific instructions in each case depending upon whether others are sharing the cost or disposing of the tree parts. 2.2. Enhanced Tree Work (ETT) 2.2.1. Primary Conductors Conductor clearances relative to various primary wire positions are shown in Figure 2. Normally, remove all branches and tall growing trees within the clearance zone bounded by the dashed line. Figure 2 Clearance Zone Dimensions for Enhanced Tree WorkPage 33 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 33 of 297 2.2.1.1. Overhead Clearances Prune and remove all limbs in the clearance zone over the outermost primary 2.2.1.2. Side Clearances 8 feet side clearance shall be measured horizontally outward from the outermost primary 2.2.1.3. Under Clearances Prune and remove all limbs in the clearance zone under the outermost primary 2.2.1.4. Brush and Vine Clearances Remove all brush that is capable of growing tall enough to touch the primary conductors that are in or growing into the clearance zone. All vines which are growing up poles or guy wires shall be cut at the ground line and cleared 6 feet up the pole or guy 2.2.2. Arboricultural Tree Management Remove trees if foliage removal from obtaining clearance exceeds ANSI A300 pruning standard 2.2.3. Fall Zone Hazard Tree Management Inspect, evaluate and eliminate all hazardous trees within the fall zone by pruning or removal. Utility compatible species may remain. 2.3. Maintenance Enhanced Tree Trimming (METT) 2.3.1. Primary Conductors 2.3.1.1. Overhead Clearances Re-clear to the previously established ETT clearances including new growth into the clearance zone. Remove all overhead hazards within reach of a 70 foot aerial lift. 2.3.1.2. Side Clearances 8 feet side clearance shall be measured horizontally outward from the outermost primaryPage 34 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 34 of 297 2.3.2. 2.3.1.3. Under Clearances Prune and remove all limbs in the clearance zone under the outermost primary 2.3.1.4. Brush and Vine Clearances Remove all brush that is capable of growing tall enough to touch the primary conductors that are in or growing into the clearance zone. All vines which are growing up poles or guy wires shall be cut at the ground line and cleared 6 feet up the pole or guy Hazard Tree Management Remove hazard trees up to 16 inches DBH within 8 feet of the outermost conductor. 2.4. Mid-Cycle Trimming Inspect and evaluate tree conditions along the entire back bone section of line scheduled. Prioritize pruning and removals based on tree conditions and likelihood of a tree causing an outage prior to the next scheduled routine trim. Where necessary: • Remove hazard trees within the fall zone. • Prune and remove all overhead hazards. • Cut vines on all poles and guy wires. 2.5. New Business and Capital Construction Prune all branches and remove all tall growing tree species in a strip centered on the pole line 8 feet to either side of the outermost conductors. Provide hazard tree removal as specified in article 2.2.2 and clearance as specified in article 2.1.1 for laterals and 2.2.1. for backbones. 3. Tree Removal • Contractor shall not "top" trees unless authorized by the Owner's Representative. Normally, these trees will be removed.Page 35 of 297
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 35 of 297 • Remove any tree which would after trimming to clearance exceed ANSI A300 foliage removal standard. Trees greater than 16 inches DBH shall be removed only after authorization from Eversource. • Specific instructions on billing of removals, depending upon whether others are sharing the cost will be provided by the Owner's Representative. 4. Stumps All stumps shall be cut as close to the ground as possible, and in no case shall they be cut higher than 3 inches unless used as supports for a fence or approved otherwise by Eversource. All stumps shall be cut off parallel to the ground to avoid leaving sharp points on the stumps. In Connecticut, sproutable cut-off stumps (all hardwoods, pitch pine and vines) shall be treated with an Eversource approved herbicide mixture in accordance with label directions and regulatory requirements. 5. Brush and Vine Removal 5.1. Brush Brush shall not be trimmed or topped. The width of the brush removal area shall be 8 feet on each side of the outermost conductor or growing into that zone. Flat cutting or selective brush removal shall be approved by Eversource. Cutting of tree brush and woody vines shall be done with care to minimize damage to non-interfering shrubs such as the following that are permitted to remain: Pinxterbloom Azalea Highbush Blueberry Redosier Dogwood Oldfield Common Juniper Sweetfern Bayberry Hazelnut Gray Dogwood Huckleberry Spicebush Mountainlaurel Rhododendron 5.2. Vines All woody vines which are growing up poles or guy wires shall be cut at the groundline and cleared for 6 feet up the pole or guy. 6. Wood and Chip Disposal
Text of OCC-890_Final.pdf
Extracted from the file · 1 page · 553 characters
As listed on the current system
Question(s) Answered 888, 889, 890 (The Connecticut Light and Power Company) Date Filed: 10/09/2026