    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 66 of 297 Major Inspection – De-Energized – Substation NOTE: Prior to beginning maintenance, ensure that all switching and notifications are performed in accordance with Company requirements. Metal-Enclosed Units Only Isolate and ground the capacitor bank using appropriate operating and safety procedures (allow 5 minutes before grounding bank after isolation). 1. Isolate and ground the capacitor bank from service in accordance with Company requirements. 2. Remove the capacitor bank from service in accordance with Company requirements. 3. Visually inspect the bank for the following: • Bulging cans • Oil leaks • Cracked housings 3. Check the ground switch and interlocking mechanism for damage or abnormalities. 5. I f a p p lic a b le , Open all compartment doors and check for water leaks, oil leaks, moisture, and contamination. 6. Check for foreign material or signs of animal entry. If an opening exists that may allow entry, repair or safely block the opening before returning the bank to service. 7. If applicable, Check the condition of ventilators and filters. 8. If applicable, Check the fans and thermostats, if applicable, for proper operation. 9. If applicable, Check all fuses. 10.If applicable, Check all capacitor tanks and connections for abnormalities. 11. If applicable, Clean the unit before re-energizing if it is dirty. 12. If applicable, Remove Worker’s grounds and short circuits from the bushings, if installed. 13. If applicable, Disconnect the phase jumpers between the capacitor cans, if installed. 14. Calibrate and functionally checked monitoring equipment (relays, etc) used to alarm or trip the bank under abnormal conditions. 15. Test any capacitors found to have blown fuses as follows: a). Review the capacitance meter manufacturer’s instructions. b). Calibrate the capacitance meter. c). Connect test leads to capacitor-can bushings. d). Ensure good test lead connection. e). Measure the capacitance of each capacitor can. See Appendix 1 for acceptable test values. Fail any can that tests outside of these values. NOTES:
  2. Page 67 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 67 of 297 • • Acceptable capacitance readings and a satisfactory visual inspection are indications of a good capacitor can. The capacitance meter test may not always be correct. A failed capacitor may read within the range which that indicates that the capacitor is good. Because this is not a conclusive test, every precaution shall be taken when energizing a capacitor. 16. Refer to Appendix 1, Capacitor Test Benchmarks and the following to determine if the capacitor can(s) are acceptable: 17. Compare test results to the indicated values for the size and voltage of the can. 18. Refer to Appendix 1 and verify the meter reading is within the acceptable range specified by upper and lower limits. 19. If the capacitance meter reading is outside of the acceptable range specified by the upper and lower limits, identify the cans as failed. 20. Replace failed capacitor can(s) if visual inspection and/or capacitance test results indicate capacitor can failure(s). Refer to TD 832, “Capacitor Bank Inspection”. 21. Restore the capacitor bank to service in accordance with Company requirements. 22. Check the operation of the oil switches when initiating a close (to re-energize the bank) Major Test – De-Energized – Substation Rack-Mounted and Metal-Enclosed Units 1. Test the voltage, current, time and/or radio operating controls for proper operation; check and verify their settings NOTE: Prior to performing the remainder of this maintenance, ensure that all switching and notifications are performed in accordance with Company requirements. 2. Isolate and ground the capacitor bank using appropriate operating and safety procedures. Allow 5 minutes before grounding the bank after isolating it. 3. Remove the capacitor from service in accordance with Company requirements. 4. Visually inspect the bank for the following: • Bulging cans • Oil leaks • Cracked housings 5. Open all compartment doors and check for water leaks, oil leaks, moisture, and contamination. 6. Check for foreign material or signs of animal entry. If an opening exists that may allow entry, repair or safely block the opening before returning the bank to service. 7. Check the condition of ventilators and filters. 8. Check the fans and thermostats, if applicable, for proper operation. 9. Operationally check all associated switches and interlocking
  3. Page 68 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 68 of 297 mechanisms (disconnect, ground, vacuum, etc). 10. Wipe clean all insulators, bus supports, fusses, and bushings. 11. Check all capacitor tanks and connections to ensure that connections are tight and that there are no abnormalities. 12. Visually check and verify proper fusing of capacitors. 13. Check for blown fuses. 14. Test any capacitors found to have blown fuses as follows: a) Review the capacitance meter manufacturer’s instructions. b) Calibrate the capacitance meter. c) Connect test leads to capacitor-can bushings. d) Ensure good test lead connections. e) Measure the capacitance of each capacitor can. See Appendix 1 for acceptable test values. Fail any can that tests outside of these values. NOTES: • Acceptable capacitance readings and a satisfactory visual inspection are indications of a good capacitor can. • The capacitance meter test may not always be correct. A failed capacitor may read within the range that would indicate that the capacitor is good. Because this is not a conclusive test, every precaution shall be taken when energizing a capacitor. 2. Refer to Appendix 1, Capacitor Test Benchmarks and the following to determine if the capacitor can(s) are acceptable: a) Compare test results to the indicated values for the size and voltage of the can. b) Refer to Appendix 1 and verify the meter reading is within the acceptable range specified by upper and lower limits. c) If the capacitance meter reading is outside of the acceptable range specified by the upper and lower limits, identify the cans as failed. 3. Replace failed capacitor can(s) if visual inspection and/or capacitance test results indicate capacitor can failure(s). Refer to TD 832, “Capacitor Bank Inspection”. NOTE: See Appendix 2 for a matrix to be used for determining when to replace capacitors based on inspection findings and maintenance history. Clean the unit before re-energization, if it is dirty. Restore the capacitor bank to service in accordance with Company requirements. Check the operation of the oil switches when initiating a close (to re energize the bank). Major Maintenance – De-Energized – Substation Rack-Mounted and Metal-Enclosed Units
  4. Page 69 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 69 of 297 1. Test the voltage, current, time and/or radio operating controls for proper operation; check and verify their settings. NOTE: Prior to performing the remainder of this maintenance, ensure that all switching and notifications are performed in accordance with Company requirements. 1. Isolate and ground the capacitor bank using appropriate operating and safety procedure (allow 5 minutes before grounding bank after isolating). Remove the capacitor from service in accordance with Company requirements. 2. Visually inspect the bank for the following: • Bulging cans • Oil leaks • Cracked housing 3. Open all compartment doors and check for water leaks, oil leaks, moisture, and contamination. 4. Check for foreign material or signs of animal entry. If an opening exists that may allow entry, repair or safely block the opening before returning the bank to service. 5. Check the condition of ventilators and filters. Check the fans and thermostats, if applicable, for proper operation. Test the voltage, current, time and/or radio operating controls for proper operation; check and verify settings. (If the bank is de- energized, it may not be possible to functionally check the controls. Functional check of a bank should be done prior to switching it out. This will allow for repairs to the controls while the bank is out). Operationally check all associated switches and interlocking mechanisms (disconnect, ground, vacuum, etc). Wipe clean all insulators, bus supports, fuses, and bushings. Check all capacitor tanks and connections to ensure that connections are tight and that there are no abnormalities. Visually check and verify proper fusing of capacitors. Check for blown fuses. Test any capacitors found to have blown fuses as follows: a) Review the capacitance meter manufacturer’s instructions. b) Calibrate the capacitance meter. c) Connect test leads to capacitor-can bushings. d) Ensure good test lead connection. e) Measure the capacitance of each capacitor can. See Appendix 1 for acceptable test values. Fail any can that tests outside of these values. NOTES:
  5. Page 70 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 70 of 297 • • Acceptable capacitance readings and a satisfactory visual inspection are indications of a good capacitor can. The capacitance meter test may not always be correct. A failed capacitor may read within the range which would indicate that the capacitor is good. Because this is not a conclusive test, every precaution shall be taken when energizing a capacitor. Refer to Appendix 1, Capacitor Test Benchmarks and the following to determine if the capacitor can(s) are acceptable: f) Compare test results to the indicated values for the size and voltage of the can. g) Refer to Appendix 1 and verify the meter reading is within the acceptable range specified by upper and lower limits. h) If the capacitance meter reading is outside of the acceptable range specified by the upper and lower limits, identify the cans as failed. Replace failed capacitor can(s) if visual inspection and/or capacitance test results indicate capacitor can failure(s). Refer to TD 832 “Capacitor Bank Inspection”. NOTE: See Appendix 2 for a matrix to be used for determining when to replace capacitors based on inspection findings and maintenance history. Clean the exterior of the capacitor can, if it is dirty. Test the breaker, interrupters, or switches as directed in their individual sections if on cycle with this work activity. Replace any faulty equipment prior to returning the capacitor bank to service. Restore the capacitor bank to service in accordance with company requirements. Check the operation of the oil switches when initiating a close (to re energize the bank). Pole-Top Capacitor Maintenance (Refer to TD 832) 1. Visually inspect the bank for the following: • Bulging cans • Oil leaks • Cracked or broken bushings, if possible • Loose connections, if possible • Blown fuses • Blown arresters • Grounds and grounding connections Visually inspect the Pole, related equipment, and surrounding area as
  6. Page 71 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 71 of 297 follows: • • Verify the Pole Number is present and correctly installed. Verify Tree/Vegetation growth is not encroaching on the equipment. • Verify a continuous ground wire is present from the pole base to the capacitor bank. • Verify a ground rod is present at the base of the pole • Verify a ground wire is present between the ground rod and system neutral. • Verify that oil switches and vacuum interrupters are in good condition. • Verify that radio-controlled switches are in good condition. Verify that all control switches are in their normal positions. Schedule a replacement of the capacitor can if any obvious problems are found, such as physical damage, etc. • If a fuse is blown, test the capacitor. From capacitor control, record the voltage, KVAR and Power Factor. (Note: this information may not be available on some controls). Initiate a close. The recorded values should have changed because of the added capacitance. NOTES: • Refer to PR-153 (Appendix 3 of this document for a description of SC 434202, Transformer and Capacitor tester. • A satisfactory visual inspection is an indication of a good capacitor can only. • If the capacitor is not functional and has oil switches, the bank should be replaced with new. Continuous Monitoring - Capacitor banks 69kV and above 1. Continuous monitoring of the input voltage and voltage or current imbalance within the capacitor banks is performed via SCADA alarm monitoring when the capacitor banks are in operation. Condition Based Maintenance Diagnostic Testing (performed with Bank de-energized) 1. Capacitor can values are recorded. 2. Neutral voltage imbalance protection relaying (if utilized) is tested for proper operation and settings are verified. 3. Over-voltage protection relaying (if utilized) is tested for proper operation and settings are verified. Failure Finding: (Refer to TD 832) See appendix 2 for a matrix to be used for determining when to
  7. Page 72 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 72 of 297 replace capacitors based on inspection findings and maintenance history. • Replace the entire capacitor bank (see Appendix 2): o If there have been three or more can failures on the capacitor bank. o If there have been more than two trips to the capacitor bank for repairs other than Cans and Switches. o If the capacitor is not functional and has oil switches. • Repair the capacitor bank if none of the above conditions for replacement exist. (See Appendix 2)
  8. Page 73 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 73 of 297 Appendix 1 – Capacitor Test Benchmarks System Line Voltage: kV Capacitor-Can Voltage Rating: kV 4.16Y/2.4 4.8Δ 8.32Y / 4.8 12.4Y / 7.20 13.2Y / 7.62 13.8Y / 7.96 34.5 / 19.92 23.0Y / 13.28 27.6Y / 15.93 2 * Capacitor microfarads = 2.65 x (kVAR ÷ kV ) (1) This is an ideal capacitor test reading. (2) Replace the capacitor can if the reading is below this value. (3) Replace the capacitor can if the reading is above this value. 2.40 4.80 7.20 7.62 7.96 19.92 13.28 15.93 Capacitor Rating: Mircrofarads * -5% 2 +15% 6.90 6.555 7.935 25 11.50 10.925 13.225 50 23.0 21.850 26.450 100 46.0 43.700 52.90 15 1.725 1.639 1.983 25 2.875 2.731 3.306 50 5.751 5.463 6.614 100 11.50 10.925 13.225 200 23.0 21.85 26.45 50 2.556 2.428 2.939 100 5.112 4.856 5.879 150 7.668 7.284 8.818 200 10.224 9.713 11.757 50 2.282 2.168 2.624 100 4.564 4.336 5.249 200 9.128 8.671 10.498 50 2.09 1.986 2.404 100 4.18 3.971 4.807 200 8.36 7.942 9.614 100 0.668 0.634 0.768 150 1.002 0.952 1.152 200 1.336 1.269 1.536 300 2.003 1.903 2.304 400 2.671 2.538 3.072 100 1.503 1.428 1.728 200 3.006 2.856 3.457 300 4.508 4.282 5.184 200 2.089 1.984 2.402 Kvar Ideal 15 1 3
  9. Page 74 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 74 of 297 Appendix 2 – Replacement Decision Matrix Eversource Capacitor Replacement Decision Matrix Total Number of Failures Quantity 2 3 1 Repair Equipment on Can Failures Pole during Inspection 4 Trips to bank for failures other than Cans and Switches Oil Switch Failures Replace the Entire Capacitor Bank
  10. Page 75 of 297

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 28, 2026 OCC- 888 Attachment 2 Page 75 of 297 Appendix – 3 PR-153 – Capacitor Tester
Words on different pages

Text of OCC-890_Final.pdf

Extracted from the file · 1 page · 553 characters

Words on different pagesRead the text of OCC-890_Final.pdf

As listed on the current system

Question(s) Answered 888, 889, 890 (The Connecticut Light and Power Company) Date Filed: 10/09/2026

This filing on the current system (opens in a new tab)