Every word of Eversource rate increase is in the text below, but not all on one page. Pages with any of them are listed and highlighted. Clear highlighting
Words on different pages

Scanned pages and machine-read text of RSR-038 Attachment 1 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 1 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 1 of 19 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] April 13, 1988 D01928 Mr. Ronald Corey, Fire Marshall City of Torrington 111 Water Street Torrington, Connecticut 06790 Reference: Letter and Notification, [redacted] o R. Corey, dated May 8, 1986. Dear Mr. Corey: Torrington Area Work Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for the Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Torrington Area Work Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the removal of all of the tanks (A1, B2, C3, D4) at the site. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted]. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] [redacted] Senior Vice President [redacted] By: C. F. Sears Vice President
  2. Scan of page 2 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 2 of 19 Mr. Ronald Corey, Fire Marshall DO1928/Page 2 April 13, 1988 Enclosure cc: w/enclosure (Copy 1) Mr. Scott Deshefy Hazardous Material's Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Mr. Richard Ciasullo Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106
  3. Scan of page 3 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 3 of 19 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION | PG. 2 of 1 | SITE ID | FOR STATE AGENCY USE ONLY | A. SITE I.D. | B. DATE RCVD BY D E P | C. DATE ENTERED | D. GRID COORDINATES X Y | E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM-6 NEW 10/85 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
    4. LOCATION OF FACILITYSITE NAME: Torrington Area Work CenterNO. AND STREET: 174 Franklin StreetNEAREST INTERSECTING STREET: Horwinton Ave.CITY OR TOWN: TorringtonSTATE: CT5. LATITUDE: 41° 48' 00"LONGITUDE: 73° 06' 55"
    5. BUSINESS NAME AND 6. MAILING ADDRESSNAME: The Connecticut Light + Power Co. (CL4P)NO. AND STREET: P O Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 06141-0270
    7. FACILITY OWNERNAME: CL&PNO. AND STREET: Same as AboveCITY OR TOWNSTATEZIP CODE
    8. TYPE OF OWNERPRIVATE (checked)STATEMUNICIPALFEDERAL (G.S.A. No.)
    9. OPERATOR/CONTACT PERSON[redacted]NO. AND STREET: 174 Franklin StreetCITY OR TOWN: TorringtonSTATE: CTZIP CODE: 06790TELEPHONE: 1203 482-4471
    10. TANK ID11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (in years)12a. TOTAL CAPACITY (Gals.)IN USEABANDONED IN PLACE12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCTCHEMICAL LIQUID14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)c. INTERNAL UNLINEDb. EXTERNAL UNLINEDCATHODIC PROTECTIONCOATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list B)16. PROTECTION17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (from list A/B)b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (if "YES", enter DATE and attach results; if "NO", enter "NO")
    Example5/75305000XXXH55/75UNO
    Example7/60-8000X8/78XXE77/60U-
    A112/781510,000X4/88XRegular GasolineXXE7E12/78O3-15-84
    B21/64154,000X3/88XDiesel FuelXXE7E1/64O3-15-84
    C31/64154,000X3/88XUnleaded GasolineXXE7E1/64O3-15-84
    D41/6015500X3/88XWaste OilXXE7E1/60UNO
    SECTION C 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [X] YES 21. COMMENTS: SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.
    22a. SIGNATUREX [redacted]
    22b. DATE SIGNED13 April 1988
    22c. NAME (type or print) [redacted] 22d. OFFICIAL TITLE | Vice President / Senior Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 06106
  4. Scan of page 4 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 4 of 19 CONN LIGHT & POWER CO. NORTHEAST UTILITIES WORK ORDER SKETCH SHEET
    DISTRICT / REGIONTOWNDATEMAP NO.WORK ORDER NO.ACTV.SHEETOF
    TORRINGTON / WESTERNTORRINGTON
    SKETCH INDICATE NORTH AND NAME STREETS Not To Scale B2 A1 21' 140' 159' 177' 44' 275' 255' D4 C3 GARAGE TRANSMISSION TORRINGTON SERVICE BUILDING HARWINTON SCHIBI ST. AVE. OP418? REV. 10-82 DEST. SAME AS ATT. REC. DRAWN BY | TELEPHONE EXT.
  5. Scan of page 5 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 5 of 19 REDACTED TO: File FROM: John Szymanski [signature] April 14, 1988 SUBJECT: Torrington AWC Tank removals were conducted at the Torrington AWC during the months of March and April 1988. o During March 1988: One (1) 4000 gallon unleaded gasoline tank and One (1) 500 gallon oil tank were removed; no problems o On March 30, 1988: Notified that (1) 4000 gallon diesel tank was removed with heavy rusting and several apparent holes the size of dimes. o On March 30, 1988: Examined site and took three (3) samples from excavation hole and one (1) sample from diesel tank to have material analyzed and identified by LAB per request by DEP Field Inspector, Richard Ciasullo. o On March 31, 1988: Samples dropped off for analyzing and identification at Souther-Newlands Laboratory. o On April 4, 1988: Souther Newland Laboratory called EPD office to report on lab findings. - Sample from diesel tank identified as diesel fuel - The three (3) samples from the excavation hole all had the same characteristic profiles, but it didn't match that of gasoline or diesel fuel and that it would take two to three weeks to identify samples from the excavation hole. o On Aril 4, 1988: Notified R. Robinson of the DEP Clean Water Group of the test results and asked for permission to continue tank installation construction after film cleaned off top of water and remainder of gray colored gravel removed from hole. Mr. Robinson gave approval to continue construction if I inspected site and assured this was done. o On April 6, 1988: NUSCO construction removed film from water and lowered water table by sucking out 3200 gallons of contaminated water which was hauled off site as contaminated waste water. Removed the remainder of gray contaminated gravel from excavation hole. o On April 6, 1988 after water table lowered gasoline film and strong fumes entered the excavation hole. The fire marshal was notified, who requested DEP to inspect the hole. Concern was generated regarding 10,000 gallon unleaded gasoline tank in the same vicinity where gas fumes and film were found. Construction stopped. o On April 7, 1988: DEP Field Inspector Richard Ciasullo and
  6. Scan of page 6 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 6 of 19 Torrington Fire Marshal Ron Corey arrived on site and gave us two alternatives: 1. Test tank full of product and be ready to remove it immediately if tank leaks; 2. Remove 10,000 gallon unleaded tank. o April 7, 1988: Discussions were held between Area Superintendent Walt Wadman, Ken Busick, Frank Melluzzo, Bud Meyer, John Betz, Jack Farrel and John Szymanski to discuss options and make decision as to disposition of 10,000 gallon gasoline tank. Final consensus was to remove tank based on presence of gasoline odor and fumes in area, water level in tank raised when emptied of product, bottom ash found in vicinity of tank, tank had been unprotected for 10 years, the older unprotected tank 4000 diesel came out of ground looking like swiss cheese. o April 7, 1988: Removed 10,000 gallon unleaded gasoline tank, some heavy rusting and pitting visible on tank but there was no apparent holes. Backfill around tank was improper per today's installation standards (very large boulders, large gravel and some sand) there were no hold down straps on tank, and bottom ash in close proximity to tank. Wet lines were heavily rusted in one large area.
  7. Scan of page 7 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 7 of 19 REDACTED Distribution: [redacted]Claims and Insurance [redacted]s. and Test Department [redacted]Regional Operations - WMECO [redacted]struction [redacted]HP [redacted]rans. SS and Mtce. [redacted] Trans. Bldg. Eng. Design [redacted]nsportation [redacted] EPD [redacted]ores [redacted] EPD [redacted]cilities Management [redacted] Legal [redacted] Nuclear Prod. [redacted]en. Fac. Lic. Dept. bsl cc: [redacted]
  8. Scan of page 8 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 8 of 19 TORRINGTON AUG / CT Bemis / Laura Lionts leak lokator hunter ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] TEST RESULTS DATE OF TEST | 07-6-85 CONTRACT NUMBER
    CUSTOMERNortheast Utilities
    LOCATION – IDENTIFICATION NUMBERNAME
    ADDRESS178 Franklin DriveCITYTorringtonSTATEConn
    LEAK LOKATOR USE ONLYCONCL. CODE
    TEST RESULTS SUMMARY
    NO.SYSTEM PRODUCTTANK SIZE GALLONSDIA/MATLWATER INCHESLEAK LOKATOR RESULTS LEVEL INCHESALR GPHCONCLUSIONRECOMMENDATIONSTESTTANKSYS
    IINo Lead Tank #I400064/371 1/2"106".039Tight
    IINo Lead Tank #II400064/371 1/2"95".038Tight
    VIIRegular Lead1000096/3T1 1/2"113".038Tight
    OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTS
    NO.SYSTEM PRODUCTTYPE OF PUMP REMOTETYPE OF PUMP SUCTION# APPLIEDMINUTES APPLIEDPRODUCT LOSS CC'SPRODUCT LOSS GPHCONCLUSION/RESULT
    IINo Lead Tank I>✓DLPressure testtestX
    IINo Lead Tank II>✓170Pressure testtestX
    IIIRegular Leaded> Pump✓ Side[illegible][illegible]XXTight
    NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTS
    NO.SYSTEM PRODUCTTEST NO.TEST LEVEL (INCHES)CLOCK STARTDURATION HRS.-MIN.LEAK RATE CC/DIVLEAK RATE CC/MINTEMP COMP Δ°FTEMP COMP CC/MINABSOLUTE LEAK RATE CC/MINABSOLUTE LEAK RATE GPHCHECK TEST Y or N
    INo Lead Tank I1106"9:4531 min.39+25.95+.161+33.80-1.85-.039N
    IINo Lead Tank II195"7:5231 min.47+2.82+.636+6.37-2.44-.038N
    IIIRegular Leaded1142"11:4620 min.35+21.47+.65523.88-2.41-.038N
  9. Scan of page 9 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 9 of 19 REDACTED ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] Bemis | TORRINGTON AWG / CT Laura [illegible] leak lokator TEST RESULTS DATE OF TEST | 03-6-8? CONTRACT NUMBER CUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER
    ADDRESS 178 Franklin DriveNAME
    CITY TorringtonSTATE Con
    TEST RESULTS SUMMARY
    NO.SYSTEM PRODUCTTANK SIZE GALLONSDIA/MATLWATER INCHESLEAK LOKATOR RESULTS LEVEL INCHESALR GPHCONCLUSIONRECOMMENDATIONSLEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS
    INO LEAD TANK I450064.371 1/2"166"-.029Tight
    IINO LEAD TANK II450064.371 1/2"95"-.038Tight
    IIIREGULAR LEADED1000096 x T1 1/2"115"-.026Tight
    OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTS
    NO.SYSTEM PRODUCTTYPE OF PUMP REMOTESUCTION# APPLIEDMINUTES APPLIEDPRODUCT LOSS CC'SPRODUCT LOSS GPHCONCLUSION/RESULT
    INO LEAD TANK I✓DODO[illegible]testX
    IINO LEAD TANK II✓testX
    IIIREGULAR LEADED✓✓110DueX
    IIIREGULAR LEADED✓ Pump✓[illegible][illegible][illegible][illegible]Tight
    NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTS
    NO.SYSTEM PRODUCTTEST NO.TEST LEVEL (INCHES)TIME CLOCK STARTTIME DURATION HRS.-MIN.LEAK RATE CC/DIVLEAK RATE CC/MINTEMPERATURE COMPENSATION Δ°FTEMPERATURE COMPENSATION CC/MINABSOLUTE LEAK RATE CC/MINABSOLUTE LEAK RATE GPHCHECK TEST Y or N
    INO LEAD TANK I1166"9:4531 min.39+25.95+.141+27.82-1.85-.029N
    IINO LEAD TANK II195"9:5235 min4.1712.08+.03616.37-2.44-.038N
    IIIREGULAR LEADED1114"9:4630 min-.37+21.17+.25523.66-2.41-.038N
    * LEVEL – INCHES FROM TANK BOTTOM TO TEST LEVEL ALR – ABSOLUTE LEAK RATE (MEASURED LEAK RATE – TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION – NFPA 329 CRITERION OF ± 0.05 GPH IS USED TO CERTIFY TIGHTNESS CERTIFICATION This is to certify that the above described tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated as tight meet the criterion established by the National Fire Protection Association Pamphlet 329 for Precision Testing.
    TESTS CONDUCTED BYCERTIFIED BY
    TEST VAN NO. [illegible]SIGNATURE [illegible]
    TANK TESTING SPECIALIST [illegible]NAME [illegible]DATE [illegible]
    TANK TESTING SPECIALIST [illegible]TITLE [illegible]
  10. Scan of page 10 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 10 of 19 TANK AND LOCATION DATA DATE: 03-6-85
    CUSTOMER: Northeast UtilitiesCITY: Torrington
    I.D. #STATE: Conn
    WEATHERTIMETEMPERATURECOMMENTS
    BEFORE TEST –
    AFTER TEST –
    SCHEMATIC: Building PUMP NO LEAD II 4000gal 64" NO LEAD II 4000gal 64" NO LEAD PUMP VENT Regular PUMPS VENT Regular LEADED 10000gal 96" Building
    PRODUCT/TANK NO.NO LEAD INO LEAD IIRegular
    BEFORE DELIVERY LEVELFillGaugeFillGaugeFillGaugeFillGaugeFillGauge
    LEVELFull
    GALLONS
    WATER1½"1½"1½"
    TOP OF RISER9796101132
    GRADE160163162137
    DROP TUBEALALAL
    CAPACITY, GALLONS4000400010000
    DIAMETER, INCHES646464
    MATERIALSTEELSTEELSTEEL
    PUMP TYPEGasboy[illegible]Bennett
    TYPE OF COVERTANTANTAN
    AGE OF TANKUKUKUK
    SIPHONNONONO
    TANK OPENINGS1-4" 1-2"1-4" 1-2"1-4"
    EXTRACTORSNONONO
    VAPOR RECOVERY TYPE VENT CONFIGURATION P-V VENT VALVE TYPE
    REPLACEMENT PARTS: PART #DESCRIPTIONQUANTITYPRICE
    #701[illegible]1[illegible]
    #124[illegible]1[illegible]
    #6" Quick Tite 2-gauge (wire)1[illegible]
    ADDITIONAL CHARGES: (pumpovers, overtime, etc.) [illegible] [illegible] *Data obtained from ☐ Station ☐ LL Charts ☐ Other ______

Scanned pages and machine-read text of RSR-038 Attachment 2 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 1 of 1 of RSR-038 Attachment 2 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 2 REDACTED Page 1 of 1 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION
    2. PG.of
    11
    STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D.
    3. FOR STATE AGENCY USE ONLYA. SITE I.D.
    B. DATE RCVD BY D.E.P.C. DATE ENTERED
    D. GRID COORDINATES X ___ Y ___E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
    SECTION A/B
    4. LOCATION OF FACILITYSITE NAME: East Hampton Service CenterNO. AND STREET: 22 East High StreetNEAREST INTERSECTING STREET: Route 2CITY OR TOWN: East HamptonSTATE: CT5. LATITUDE: 41° 34' 56"LONGITUDE: 72° 30' 14"
    6. BUSINESS NAME AND MAILING ADDRESSNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 061410270
    7. FACILITY OWNERNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 061410270
    8. TYPE OF OWNERX PRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. ___)
    9. OPERATOR/CONTACT PERSON[redacted]NO. AND STREET: 22 East High StreetCITY OR TOWN: East HamptonSTATE: CTZIP CODE: 06424
    [redacted] SECTION C
    10. TANK ID.11a. DATE OF INSTALLATION (Mo./Yr.)11b. TANK LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)12b. STATUS: IN USEABANDONED IN PLACEEST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCTCHEMICAL LIQUID14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No. if known)15. CONSTRUCTION MATERIALS: STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)16. PROTECTION a. INTERNAL: LINEDUNLINED; b. EXTERNAL: CATHODIC PROTECTIONCOATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list B)17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION PROTECTION (See list B)b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES," enter DATE and attach results. If "NO," enter "NO")
    Example5/75305000XXXXH55/75UNO
    Example7/60-8000X8/78XXXE77/60U—
    A1/7215275XXXXXH7/72H092584
    B2/721510000XXXX7/72O092684 (10-14-86 / 092684 struck through)
    C3'303010000X011/84XX8/80O092684
    D4'7215275XXXX7/72U092584
    E5,7215550XXXX7/72U092884
    P6,7215550XXXX7/72U092884
    20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? X YES 21. COMMENTS: 16b coal tar epoxy. Tanks B2, D4, E5 & F6 budgeted for cathodic protection in 1986. A1 is also for [illegible] [illegible] SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.
    22a. SIGNATUREX [redacted]22b. DATE SIGNED5/5/86
    22c. NAME (Type or Print)[redacted]
    22d. OFFICIAL TITLE (of owner or authorized representative)Senior Vice President
    COPY 4

Text of RSR-038 Attachment 3.pdf

Extracted from the file · 1 page · 146 characters

Scanned pages and machine-read text of RSR-038 Attachment 4 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 105 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 105 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [phone removed] February 3, 1992 D05244 UST Coordinator Department of Environmental Protection 165 Capitol Avenue Hartford, CT 06106 Reference: Letter and Notification (D05094), C. F. Sears to UST Coordinator, dated December 10, 1991. Dear Sir or Madam: Madison Service Center Amended UST Notification Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits an amended Underground Storage Facility Notification for CL&P's Madison Service Center. This notification supersedes the notification submitted on December 10, 1991 (referenced). The following changes have been made: o Removal of Tank C3, 10,000-gallon unleaded gasoline UST o Removal of Tank D4, 10,000-gallon unleaded gasoline UST If you have any questions, please call [redacted] NUSCO Generation and Environmental Licensing, at [redacted] Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] Vice President cc w/Copy No. 2: Mr. Arthur W. Cunningham Town Hall 8 Meeting House Lane Madison, CT 06443
  2. Scan of page 106 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 106 of 126 REDACTED PLEASE TYPE: COMPLETE ALL SECTIONS OF FORI! FACILITY NOTIFICATION UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D. POR STATE AGENCY USE ONLY B. DATE RCVD BY D.E.P | C. DATE ENTERED D. GRID COORDINATES X ___ Y ___ E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO SECTION A SECTION B
    4. LOCATION OF FACILITYSITE NAME: Madison Service CenterNO. AND STREET: 135 New RoadNEAREST INTERSECTING STREET: Duck Hole RoadCITY OR TOWN: MadisonSTATE: CTS. LATITUDELONGITUDE
    6. BUSINESS NAME AND MAILING ADDRESSNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    7. FACILITY OWNERNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 06141-0270[redacted]
    8. TYPE OF OWNERPRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. ___)
    9. OPERATOR/CONTACT PERSONNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    SECTION C
    10. TANK ID11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)IN USEABANDONED IN PLACE12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS OIL/PETRO-LEUM PRODUCTCHEMICAL LIQUID14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)16. PROTECTION a. INTERNAL LINEDUNLINEDCATHODIC PROTECTIONb. EXTERNAL COATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list A)17. INTEGRAL PIPING SYSTEM a.b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results) (If "NO", enter "NO")
    Example5/75305000XXHeating fuel #2XXH 3H5/75UNO
    Example7/60-8000X8/78X1,1,1 - Trichloroethane CAS #79016XXE 7W7/60U—
    A1/73-550X11/91XHydraulic Fluid
    B2/73-550X11/91XMotor Oil
    C3/73-5000X1/92XUnleaded Gasoline
    D4/73-5000X1/92XUnleaded Gasoline
    E5/73-10000X8/89XUnleaded Gasoline
    F6/73-550X11/91XWaste Oil
    G7/7330170XXHydraulic FluidXXXBP8WC/73RNO
    H8/73-1500X/89XDiesel
    SECTION D 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [ ] YES 21. COMMENTS: G7-16b-Tank is vaulted. 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted. [redacted] 22b. DATE SIGNED: February 3,1992 22c. OFFICIAL TITLE (of owner or authorized representative): Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 06106
  3. Scan of page 107 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 107 of 126 28 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
    FACILITY: Madison Service CenterCODE: BGNLETTER NO: D 05244
    TITLE/SUBJECT: Amended UST NotificationAGENCY: CDP
    SPECIAL INSTRUCTIONS:LETTER DATE: 2-3-92
    DISTRIBUTION/SIGNOFF Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.
    DSAPERSONSODISCIPLINELOC.EXTINIT.DATECOMMENTS
    XXR.P. KlattenbergXEnviro. Svcs.B3F34628Sav/Sup Copy✓
    R.C. NicholsEnviro. AuditB3F34645
    P.M. JacobsonEnviro. Prog.B3F34642
    T.J. ButwillCivil HydraulicsN2065403
    D.R. WadeFH Programs EngngN2265460
    W.J. KornackiFH Improv. EngngN2263792
    R.N. SmartFH Eng. & Const.N2075362
    RH PershanXLegalE2178175PWP1/27/92
    Land PlanningSBS
    N.J. LanzalottaProd. Opns. Svcs.W2395657
    Hydro ProductionW239
    Project Engineer
    Facility Mgr./Supt.
    C.A. EdgeFac. Opns. & EngngSBS6750
    P.C. RobothamTransportation33336677
    J. BarresiSupt. - CT&M33336662
    W.V. ReicheltSys. Supt. - FossilW2395467
    R.G. ChevalierSys. Supt. - HydroW2395064
    XKTHSzymanskiXOriginator/LeadB3F33540Sav/Supv CRS1-27-92
    XXC Kyurle SmithXGEL LeadW2183540CRS1-27-92NRC ☐ Yes ☐ No
    XSupvsr - NLW218
    R. OsellaXSupvsr - GELW2185448Ro1/31/92
    OTHER DISTRIBUTIONGEL CLERK INSTRUCTIONS
    XXFacilities FileGEL ClerkW218XORIGINAL AND ___ COPIES
    XXJ BetzTest BuildingXATTACHMENTS (X in "A" Column)
    XXJ SlaterMiddletown Reg. Ofc.FEE CHECK
    XXE KingstonMadisonFEDERAL EXPRESS
    XXS MartinMadisonREGISTERED MAIL
    TELECOPY
    COMMITMENT / ACTION TRACKING INFORMATION Response To: COTRAP # C_____ or FORCOM # F_____ DUE DATE:_____ Number of Calendar days in Advance (+) or Late (-) of Due Date_____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 6 1-92
  4. Scan of page 108 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 108 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] February 3, 1992 D05244 UST Coordinator Department of Environmental Protection 165 Capitol Avenue Hartford, CT 06106 Reference: Letter and Notification (D05094), C. F. Sears to UST Coordinator, dated December 10, 1991. Dear Sir or Madam: Madison Service Center Amended UST Notification Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits an amended Underground Storage Facility Notification for CL&P's Madison Service Center. This notification supersedes the notification submitted on December 10, 1991 (referenced). The following changes have been made: o Removal of Tank C3, 10,000-gallon unleaded gasoline UST o Removal of Tank D4, 10,000-gallon unleaded gasoline UST If you have any questions, please call [redacted] NUSCO Generation and Environmental Licensing, at [redacted] Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] Vice President cc w/Copy No. 2: Mr. Arthur W. Cunningham Town Hall 8 Meeting House Lane Madison, CT 06443
  5. Scan of page 109 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 109 of 126 REDACTED PLEASE TYPE: COMPLETE ALL SECTIONS OF FORI! UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. FACILITY NOTIFICATION 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D. 3. FOR STATE AGENCY USE ONLY
    B. DATE RCVD BY D.E.PC. DATE ENTERED
    D. GRID COORDINATES XY
    E. DOES FACILITY MEET NEW REQUIREMENTS? YESNO
    SECTION A SECTION B
    4. LOCATION OF FACILITYSITE NAME: Madison Service CenterNO. AND STREET: 135 New RoadNEAREST INTERSECTING STREET: Duck Hole RoadCITY OR TOWN: MadisonSTATE: CTS.LATITUDELONGITUDE
    6. BUSINESS NAME AND MAILING ADDRESSNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    7. FACILITY OWNERNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 06141-0270TELEPHONE: [redacted]
    8. TYPE OF OWNERPRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. )
    9. OPERATOR/CONTACT PERSONNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    SECTION C
    10. TANK ID11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)IN USEABANDONED IN PLACE12b. STATUS: EST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS: OIL/PETROLEUM PRODUCTCHEMICAL LIQUID14. CONTENTS - CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS: STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)16. PROTECTION a. INTERNAL: LINEDUNLINEDCATHODIC PROTECTIONb. EXTERNAL: COATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list B)17. INTEGRAL PIPING SYSTEM a.b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results) (If "NO", enter "NO")
    Example5/75305000X8/78?XHeating fuel #2XXH3H5/75UNO
    Example7/60-8000X8/78XI.I.I. - Trichloroethane CAS #79016XXE7W7/60U-
    A1/73-550X11/91XHydraulic Fluid
    B2/73-550X11/91XMotor Oil
    C3/73-5000X1/92XUnleaded Gasoline
    D4/73-5000X1/92XUnleaded Gasoline
    E580 /73-10000X8/89XUnleaded Gasoline
    F6/73-550X11/91XWaste Oil
    G7/7330170XXHydraulic FluidXXXBP8WC/73RNO
    H8/73-1500X/89XDiesel
    20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? ☐ YES 21. COMMENTS: G7-16b-Tank is vaulted. and is an in process tank which isn't required to be registered. SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted. 22a. [redacted] 22b. DATE SIGNED: February 3, 1992 22d. OFFICIAL TITLE (of owner or authorized representative): Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTF[redacted]
  6. Scan of page 110 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 110 of 126 29 STATE OF CONNECTICUT CONNECTICUT UNDERGROUND STORAGE TANK PETROLEUM CLEAN-UP FUND REVIEW BOARD April 18, 1994 The Honorable Timothy R. E. Keeney Commissioner Department of Environmental Protection 79 Elm St. P.O. Box 5066 Hartford, CT 06102-5066 Dear Commissioner Keeney, Pursuant to Section 22a-449 of the Connecticut General Statutes as amended by Public Act 91-254 the Underground Storage Tank Petroleum Clean-up Fund Review Board, "the Board" met on April 12, 1994 to consider applications for reimbursement from the Fund. The board at its meeting voted to approve the following twenty-two claims in the amounts noted:
    Site No.Site Name and AddressAmount
    5 6Tire Country of Enfield, 623 Hazard Ave., Enfield (Payment to: Frank J. Troiano, c/o Jim Ray, Robinson & Cole 1 Commercial Plz., Hartford, CT 06103-3597; SS# 012-30-1169)$52,799.57
    22.1 1.2Hartford Citgo, 888 New Britain Ave., Hartford (Payment to: Mercury Fuel Service, Inc., 43 Lafayette St., Waterbury, CT 06708; FEIN: 06-0769394)$15,705.04
    118 1.2Shell Service Station, 436 Slater Rd., New Britain (Payment to: Shell Oil Co., 175 Capitol Blvd., Suite 300, Rocky Hill, CT 06067; FEIN: 13-1299891)$50,649.70
    134 1.2Amoco Station #382, 927 East Main St., Meriden (Payment to: Amoco Oil Co., 41 Regan Rd., Ridgefield, CT 06877; FEIN: 36-2440313)$32,021.35
    168 1.1C,L & P, 135 New St., Madison (Payment to: The Connecticut Light & Power Co., P.O. Box 270, Hartford, CT 06141-0270 ATTN: John Szymanski; FEIN: 06-0303850)$9730.71
    149 1.1Johnson Glass & Auto Service, 276 Howe Ave., Shelton (Payment to: Krall Coal & Oil Co., 111 East St., New Haven, CT 06511; FEIN: 06-0417830)$17,896.03
    139 1.1Classic Carriage, 351 Boston Post Rd., Old Saybrook (Payment to: Hendel's, Inc., 35 Great Neck Rd., Waterford, CT 06385-0201; FEIN: 06-0641670)$33,291.27
    141 1Precision Auto Center, 1335 Hope St., Stamford (Payment to: Carole DeFrancesco, 40 Theresa Ct., Stamford, CT 06907; SS# 042-32-4888)$3653.70
  7. Scan of page 111 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 111 of 126 Mobil Oil claims:
    153 1Mobil Service Station #06-HAO, I95 Westbound, Darien$126,731.06
    108 1Mobil Station #06-E22, 205 Sound Beach Ave., Greenwich$17,534.29
    163 1Mobil Station #06-122, 995 South Main St., Cheshire$121,588.18
    166 1Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford$96,233.70
    171 1Mobil Station #06-HMO, 818 Federal Rd., Brookfield$193,288.79
    152 1.1Mobil Station #06-037, 519 Farmington Ave., Hartford$6823.32
    155 1.2Mobil Service Station #06-GPO, Newtown Rd., Danbury$3511.22
    161 1.1Mobil Station #06-ELA, 142 Willard Ave., Newington$3362.68
    170 1.1Mobil Station #06-HGO, 1705 Park St., Bridgeport$35,333.47
    (Payment to: Mobil Oil Corp., 134 Forbes Ave., New Haven, CT 06512; FEIN: 13-5401570) United Realty of Connecticut claims:
    63 5.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$3394.98
    63 6.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$1997.02
    63 7.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$2087.10
    (Payment to: United Realty of Connecticut, 11 Crystal St., Stamford, CT 06902; FEIN: 06-0643088) The Board affirmed the settlement agreements recommended by the hearing officer for the following sites which were under appeal in the amounts noted:
    SiteSite Name and AddressAmount
    28Wethersfield Sunoco, 1780 Berlin Tpk., Wethersfield$570.90
    32Oxford Petrol Plus, 357 Oxford Rd., Oxford$2482.72
    35Sorel's Gulf, Rt. 6, Brooklyn0
    39Orange Amoco, 404 Boston Post Rd., Orange$91.60
    40Cheshire Sunoco, 200 Meriden-Waterbury Rd., Cheshire$3613.40
    89Prospect Amoco, 21 Waterbury Rd., Prospect$464.79
    90Cheshire Texaco, 986 South Main St., Cheshire$2135.05
    92Groton Sunoco, 1023 Poquonnock Rd., Groton$17.30
    112Branford Sunoco 202 East Main St., Branford$8715.42
    127S & S Transmission, 208 Rt. 12, Groton$662.69
    132Rondeau's Gulf, 42 Woodstock Ave., Putnam$1500.00
    (Payment to: Petrol Plus, Inc., 38 Commerce St., Derby, CT 06418; FEIN: 06-0465420) In voting to authorize the Commissioner of Environmental Protection to make payments from the Fund as provided by Section 22a-449c(b) of the Connecticut General Statutes the Board determined that for each application a release occurred, damages resulted, and the costs of the claims are acceptable for the services/goods rendered. The amount of each authorized claim represented the amount of costs incurred by the applicant less $10,000 as required by Section 22a-449c of the Connecticut General Statutes as amended by PA No. 91-254. The Board, at its meeting, also voted to reject the following amounts due to the existence of grounds for recovery specified in Section 22a-449f of the general statutes:
    SiteSite Name and AddressAmountReduction
    63 5.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$507.3013%
    63 6.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$298.4113%
  8. Scan of page 112 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 112 of 126
    637.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$311.8613%
    1081Mobil #06-E22, 205 Sound Beach Ave., Greenwich$1757.516%
    1521.1Mobil #06-037, 519 Farmington Ave., Hartford$4131.7020%
    1631Mobil #06-122, 995 South Main St., Cheshire$4094.185%
    The Board, at its meeting, also voted to reject the following amounts due to incompleteness:
    Site No.Site Name and AddressAmount
    635.1High Ridge Citgo, 1070 High Ridge Rd., Stamford$282.71
    1531Mobil Service Station #06-HAO, I95 Westbound, Darien$2264.47
    22.11.1Hartford Citgo, 888 New Britain Ave., Hartford$8983.77
    1181.1Shell Service Station, 436 Slater Rd., New Britain$4532.00
    1341.1Amoco Station #382, 927 East Main St., Meriden$76,576.21
    1551.2Mobil Service Station #06-GPO, Newtown Rd., Danbury$3619.40
    1681.1C,L & P, 135 New St., Madison$34,250.20
    The Board, at its meeting, also voted to reject the following amounts due to ineligibility.
    Site No.Site Name and AddressAmount
    1391.1Classic Carriage, 351 Boston Post Rd., Old Saybrook$10,575.44
    1491.1Johnson Glass & Auto Service, 176 Howe Ave., Shelton$8322.48
    1341.1Amoco Station #382, 927 East Main St., Meriden$19,636.34
    1521.1Mobil Station #06-037, 519 Farmington Ave., Hartford$579.92
    1611.1Mobil Station #06-ELA, 142 Willard Ave., Newington$9473.94
    1701.1Mobil Station #06-HGO, 1705 Park St., Bridgeport$9469.81
    The following amounts were withdrawn by the applicants:
    Site No.Site Name and AddressAmount
    56Tire Country of Enfield, 623 Hazard Ave., Enfield$13,539.84
    3411Monroe Petrol Plus, 40-44 Main St., Monroe$131,870.41
    1081Mobil #06-E22, 205 Sound Beach Ave., Old Greenwich$12,276.68
    1631Mobil Station #06-122, 995 South Main St., Cheshire$31,645.10
    1661Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford$218,487.37
    1691Rite-Way #2, 2 Scott Rd., Waterbury$67,196.21
    1711Mobil Station #06-HMO, 818 Federal Rd., Brookfield$102,209.48
    1701.1Mobil Station #06-HGO, 1705 Park St., Bridgeport$7540.69
    Sincerely, [signature] John Mitchell Chairman Underground Storage Tank Petroleum Clean-up Fund Board
  9. Scan of page 113 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 113 of 126 30 GEL CORRESPONDENCE RECEIPT AND DISTRIBUTION FORM TO: GENERATION ENVIRONMENTAL LICENSING FROM: Sears C.F. Sears Please distribute the attached document to involved or affected disciplines in the NU system and insure proper and timely action based on their input, as appropriate. LETTER NO: c 05673 AGENCY: CDP FACILITY: MADISON CODE(unit): BGN LETTER DATE: April 1?, 1994 TITLE/SUBJECT: UST Petroleum Cleanup Fund -Award RECEIPT DATE: 5-9-94 DISTRIBUTION/ACTION
    DSAPERSONC/ADISCIPLINELOC.EXTREMARKS
    P.M. JacobsonEnv. Prog.Br. Mgr.NU East4642
    XXR. KlattenbergERMNU East4628
    T.J. ButwillF/H Eng. (Civil)N2065403
    FH Eng. & Const.N207
    XXD. GilbaneLegalE2173731
    Land PlanningNU East
    POS Env. Comp.W239
    Hydro ProductionW239
    J.W. McLaughlinHydro Prod., NHManch.
    J.B. LanderEnv. & Results, NHManch.
    XXM. HornyakERMNU East4613
    XXT. ElyeFacilities Mgr.NU East6750
    Facility Mgr./Supt.
    Fac. Opns. & EngngNU East
    Trans. CT&M3333
    W.H. SmagulaDir. - Fossil Prod.W2395467
    W.J. NadeauDir. - Hydro Prod.W2395064
    D.R. BrownPSNH ProductionManch.
    Lead Discipline
    Project Engineer
    XXJ. SzymanskiXGEL LeadW2183743
    Supvsr - NLW218
    L.E. BireleyXManager-GELW2185448
    NRC ☐ Yes ☐ No
    OTHER DISTRIBUTIONGEL CLERK INSTRUCTIONS
    XXFacilities FileTELECOPY TO:
    ATTACHMENTS (X in "A" Column)
    COMMITMENT / ACTION TRACKING INFORMATION Response To: COTRAP # D____ or FORCOM # F____ DUE DATE:____ Commitment Number | GEL Lead | Lead Discipline | Response Date | DESCRIPTION REV. 9 11-93
  10. Scan of page 114 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 114 of 126 STATE OF CONNECTICUT CONNECTICUT UNDERGROUND STORAGE TANK PETROLEUM CLEAN-UP FUND REVIEW BOARD April 18, 1994 [redacted] MAY 9 1994 ENVIRONMENTAL The Honorable Timothy R. E. Keeney Commissioner Department of Environmental Protection 79 Elm St. P.O. Box 5066 Hartford, CT 06102-5066 Dear Commissioner Keeney, Pursuant to Section 22a-449 of the Connecticut General Statutes as amended by Public Act 91-254 the Underground Storage Tank Petroleum Clean-up Fund Review Board, "the Board" met on April 12, 1994 to consider applications for reimbursement from the Fund. The board at its meeting voted to approve the following twenty-two claims in the amounts noted:
    Site No.Site Name and AddressAmount
    56Tire Country of Enfield, 623 Hazard Ave., Enfield (Payment to: Frank J. Troiano, c/o Jim Ray, Robinson & Cole 1 Commercial Plz., Hartford, CT 06103-3597; SS# 012-30-1169)~$52,799.57
    22.11.2Hartford Citgo, 888 New Britain Ave., Hartford (Payment to: Mercury Fuel Service, Inc., 43 Lafayette St., Waterbury, CT 06708; FEIN: 06-0769394)$15,705.04
    1181.2Shell Service Station, 436 Slater Rd., New Britain (Payment to: Shell Oil Co., 175 Capitol Blvd., Suite 300, Rocky Hill, CT 06067; FEIN: 13-1299891)$50,649.70
    1341.2Amoco Station #382, 927 East Main St., Meriden (Payment to: Amoco Oil Co., 41 Regan Rd., Ridgefield, CT 06877; FEIN: 36-2440313)$32,021.35
    1681.1C,L & P, 135 New St., Madison (Payment to: The Connecticut Light & Power Co., P.O. Box 270, Hartford, CT 06141-0270 ATTN: John Szymanski; FEIN: 06-0303850)$9730.71
    1491.1Johnson Glass & Auto Service, 276 Howe Ave., Shelton (Payment to: Krall Coal & Oil Co., 111 East St., New Haven, CT 06511; FEIN: 06-0417830)$17,896.03
    1391.1Classic Carriage, 351 Boston Post Rd., Old Saybrook (Payment to: Hendel's, Inc., 35 Great Neck Rd., Waterford, CT 06385-0201; FEIN: 06-0641670)$33,291.27
    1411Precision Auto Center, 1335 Hope St., Stamford (Payment to: Carole DeFrancesco, 40 Theresa Ct., Stamford, CT 06907; SS# 042-32-4888)$3653.70
    165 Capitol Avenue • Hartford, Connecticut 06106 Phone:

As listed on the current system

Question(s) Answered 38 (The Connecticut Light and Power Company) Date Filed: 10/20/2026

This filing on the current system (opens in a new tab)