Interrogatory responses
Answers to questions 38
Files5
RSR-038_Final.pdf
PDF · 146 KB · 7 pagesText searchable
Download RSR-038_Final.pdfRead the text of RSR-038_Final.pdf
RSR-038 Attachment 1 REDACTED.pdf
PDF · 4.6 MB · 19 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 1 REDACTED.pdfScanned pages and text of RSR-038 Attachment 1 REDACTED.pdf
RSR-038 Attachment 2 REDACTED.pdf
PDF · 798 KB · 1 pageText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 2 REDACTED.pdfScanned pages and text of RSR-038 Attachment 2 REDACTED.pdf
RSR-038 Attachment 3.pdf
PDF · 502 KB · 1 pageText searchable
Download RSR-038 Attachment 3.pdfRead the text of RSR-038 Attachment 3.pdf
RSR-038 Attachment 4 REDACTED.pdf
PDF · 51 MB · 126 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 4 REDACTED.pdfScanned pages and text of RSR-038 Attachment 4 REDACTED.pdf
Scanned pages and machine-read text of RSR-038 Attachment 1 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 1 of 19 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] April 13, 1988 D01928 Mr. Ronald Corey, Fire Marshall City of Torrington 111 Water Street Torrington, Connecticut 06790 Reference: Letter and Notification, [redacted] o R. Corey, dated May 8, 1986. Dear Mr. Corey: Torrington Area Work Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for the Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Torrington Area Work Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the removal of all of the tanks (A1, B2, C3, D4) at the site. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted]. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] [redacted] Senior Vice President [redacted] By: C. F. Sears Vice President
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 2 of 19 Mr. Ronald Corey, Fire Marshall DO1928/Page 2 April 13, 1988 Enclosure cc: w/enclosure (Copy 1) Mr. Scott Deshefy Hazardous Material's Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Mr. Richard Ciasullo Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 3 of 19 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION | PG. 2 of 1 | SITE ID | FOR STATE AGENCY USE ONLY | A. SITE I.D. | B. DATE RCVD BY D E P | C. DATE ENTERED | D. GRID COORDINATES X Y | E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM-6 NEW 10/85 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
SECTION C 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [X] YES 21. COMMENTS: SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.4. LOCATION OF FACILITY SITE NAME: Torrington Area Work Center NO. AND STREET: 174 Franklin Street NEAREST INTERSECTING STREET: Horwinton Ave. CITY OR TOWN: Torrington STATE: CT 5. LATITUDE: 41° 48' 00" LONGITUDE: 73° 06' 55" 5. BUSINESS NAME AND 6. MAILING ADDRESS NAME: The Connecticut Light + Power Co. (CL4P) NO. AND STREET: P O Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 06141-0270 7. FACILITY OWNER NAME: CL&P NO. AND STREET: Same as Above CITY OR TOWN STATE ZIP CODE 8. TYPE OF OWNER PRIVATE (checked) STATE MUNICIPAL FEDERAL (G.S.A. No.) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 174 Franklin Street CITY OR TOWN: Torrington STATE: CT ZIP CODE: 06790 TELEPHONE: 1203 482-4471 10. TANK ID 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. LIFE EXPECTANCY (in years) 12a. TOTAL CAPACITY (Gals.) IN USE ABANDONED IN PLACE 12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known) 15. CONSTRUCTION MATERIALS STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) c. INTERNAL UNLINED b. EXTERNAL UNLINED CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 16. PROTECTION 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (from list A/B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (if "YES", enter DATE and attach results; if "NO", enter "NO") Example 5/75 30 5000 X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X E 7 7/60 U - A1 12/78 15 10,000 X 4/88 X Regular Gasoline X X E 7E 12/78 O 3-15-84 B2 1/64 15 4,000 X 3/88 X Diesel Fuel X X E 7E 1/64 O 3-15-84 C3 1/64 15 4,000 X 3/88 X Unleaded Gasoline X X E 7E 1/64 O 3-15-84 D4 1/60 15 500 X 3/88 X Waste Oil X X E 7E 1/60 U NO
22c. NAME (type or print) [redacted] 22d. OFFICIAL TITLE | Vice President / Senior Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 0610622a. SIGNATURE X [redacted] 22b. DATE SIGNED 13 April 1988 
The scanned page Machine-read text
REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 4 of 19 CONN LIGHT & POWER CO. NORTHEAST UTILITIES WORK ORDER SKETCH SHEET
SKETCH INDICATE NORTH AND NAME STREETS Not To Scale B2 A1 21' 140' 159' 177' 44' 275' 255' D4 C3 GARAGE TRANSMISSION TORRINGTON SERVICE BUILDING HARWINTON SCHIBI ST. AVE. OP418? REV. 10-82 DEST. SAME AS ATT. REC. DRAWN BY | TELEPHONE EXT.DISTRICT / REGION TOWN DATE MAP NO. WORK ORDER NO. ACTV. SHEET OF TORRINGTON / WESTERN TORRINGTON 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 5 of 19 REDACTED TO: File FROM: John Szymanski [signature] April 14, 1988 SUBJECT: Torrington AWC Tank removals were conducted at the Torrington AWC during the months of March and April 1988. o During March 1988: One (1) 4000 gallon unleaded gasoline tank and One (1) 500 gallon oil tank were removed; no problems o On March 30, 1988: Notified that (1) 4000 gallon diesel tank was removed with heavy rusting and several apparent holes the size of dimes. o On March 30, 1988: Examined site and took three (3) samples from excavation hole and one (1) sample from diesel tank to have material analyzed and identified by LAB per request by DEP Field Inspector, Richard Ciasullo. o On March 31, 1988: Samples dropped off for analyzing and identification at Souther-Newlands Laboratory. o On April 4, 1988: Souther Newland Laboratory called EPD office to report on lab findings. - Sample from diesel tank identified as diesel fuel - The three (3) samples from the excavation hole all had the same characteristic profiles, but it didn't match that of gasoline or diesel fuel and that it would take two to three weeks to identify samples from the excavation hole. o On Aril 4, 1988: Notified R. Robinson of the DEP Clean Water Group of the test results and asked for permission to continue tank installation construction after film cleaned off top of water and remainder of gray colored gravel removed from hole. Mr. Robinson gave approval to continue construction if I inspected site and assured this was done. o On April 6, 1988: NUSCO construction removed film from water and lowered water table by sucking out 3200 gallons of contaminated water which was hauled off site as contaminated waste water. Removed the remainder of gray contaminated gravel from excavation hole. o On April 6, 1988 after water table lowered gasoline film and strong fumes entered the excavation hole. The fire marshal was notified, who requested DEP to inspect the hole. Concern was generated regarding 10,000 gallon unleaded gasoline tank in the same vicinity where gas fumes and film were found. Construction stopped. o On April 7, 1988: DEP Field Inspector Richard Ciasullo and
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 6 of 19 Torrington Fire Marshal Ron Corey arrived on site and gave us two alternatives: 1. Test tank full of product and be ready to remove it immediately if tank leaks; 2. Remove 10,000 gallon unleaded tank. o April 7, 1988: Discussions were held between Area Superintendent Walt Wadman, Ken Busick, Frank Melluzzo, Bud Meyer, John Betz, Jack Farrel and John Szymanski to discuss options and make decision as to disposition of 10,000 gallon gasoline tank. Final consensus was to remove tank based on presence of gasoline odor and fumes in area, water level in tank raised when emptied of product, bottom ash found in vicinity of tank, tank had been unprotected for 10 years, the older unprotected tank 4000 diesel came out of ground looking like swiss cheese. o April 7, 1988: Removed 10,000 gallon unleaded gasoline tank, some heavy rusting and pitting visible on tank but there was no apparent holes. Backfill around tank was improper per today's installation standards (very large boulders, large gravel and some sand) there were no hold down straps on tank, and bottom ash in close proximity to tank. Wet lines were heavily rusted in one large area.
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 7 of 19 REDACTED Distribution: [redacted]Claims and Insurance [redacted]s. and Test Department [redacted]Regional Operations - WMECO [redacted]struction [redacted]HP [redacted]rans. SS and Mtce. [redacted] Trans. Bldg. Eng. Design [redacted]nsportation [redacted] EPD [redacted]ores [redacted] EPD [redacted]cilities Management [redacted] Legal [redacted] Nuclear Prod. [redacted]en. Fac. Lic. Dept. bsl cc: [redacted]
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 8 of 19 TORRINGTON AUG / CT Bemis / Laura Lionts leak lokator hunter ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] TEST RESULTS DATE OF TEST | 07-6-85 CONTRACT NUMBER
TEST RESULTS SUMMARYCUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER NAME ADDRESS 178 Franklin Drive CITY Torrington STATE Conn LEAK LOKATOR USE ONLY CONCL. CODE
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS TEST TANK SYS II No Lead Tank #I 4000 64/37 1 1/2" 106" .039 Tight II No Lead Tank #II 4000 64/37 1 1/2" 95" .038 Tight VII Regular Lead 10000 96/3T 1 1/2" 113" .038 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE TYPE OF PUMP SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT II No Lead Tank I > ✓ DL Pressure test test X II No Lead Tank II > ✓ 170 Pressure test test X III Regular Leaded > Pump ✓ Side [illegible] [illegible] X X Tight NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) CLOCK START DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMP COMP Δ°F TEMP COMP CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I No Lead Tank I 1 106" 9:45 31 min .39 +25.95 +.161 +33.80 -1.85 -.039 N II No Lead Tank II 1 95" 7:52 31 min .47 +2.82 +.636 +6.37 -2.44 -.038 N III Regular Leaded 1 142" 11:46 20 min .35 +21.47 +.655 23.88 -2.41 -.038 N 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 9 of 19 REDACTED ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] Bemis | TORRINGTON AWG / CT Laura [illegible] leak lokator TEST RESULTS DATE OF TEST | 03-6-8? CONTRACT NUMBER CUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER
TEST RESULTS SUMMARYADDRESS 178 Franklin Drive NAME CITY Torrington STATE Con
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS LEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS I NO LEAD TANK I 4500 64.37 1 1/2" 166" -.029 Tight II NO LEAD TANK II 4500 64.37 1 1/2" 95" -.038 Tight III REGULAR LEADED 10000 96 x T 1 1/2" 115" -.026 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT I NO LEAD TANK I ✓ DO DO [illegible] test X II NO LEAD TANK II ✓ test X III REGULAR LEADED ✓ ✓ 110 Due X III REGULAR LEADED ✓ Pump ✓ [illegible] [illegible] [illegible] [illegible] Tight
* LEVEL – INCHES FROM TANK BOTTOM TO TEST LEVEL ALR – ABSOLUTE LEAK RATE (MEASURED LEAK RATE – TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION – NFPA 329 CRITERION OF ± 0.05 GPH IS USED TO CERTIFY TIGHTNESS CERTIFICATION This is to certify that the above described tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated as tight meet the criterion established by the National Fire Protection Association Pamphlet 329 for Precision Testing.NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) TIME CLOCK START TIME DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMPERATURE COMPENSATION Δ°F TEMPERATURE COMPENSATION CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I NO LEAD TANK I 1 166" 9:45 31 min .39 +25.95 +.141 +27.82 -1.85 -.029 N II NO LEAD TANK II 1 95" 9:52 35 min 4.17 12.08 +.036 16.37 -2.44 -.038 N III REGULAR LEADED 1 114" 9:46 30 min -.37 +21.17 +.255 23.66 -2.41 -.038 N TESTS CONDUCTED BY CERTIFIED BY TEST VAN NO. [illegible] SIGNATURE [illegible] TANK TESTING SPECIALIST [illegible] NAME [illegible] DATE [illegible] TANK TESTING SPECIALIST [illegible] TITLE [illegible] 
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 10 of 19 TANK AND LOCATION DATA DATE: 03-6-85
SCHEMATIC: Building PUMP NO LEAD II 4000gal 64" NO LEAD II 4000gal 64" NO LEAD PUMP VENT Regular PUMPS VENT Regular LEADED 10000gal 96" BuildingCUSTOMER: Northeast Utilities CITY: Torrington I.D. # STATE: Conn WEATHER TIME TEMPERATURE COMMENTS BEFORE TEST – AFTER TEST –
VAPOR RECOVERY TYPE VENT CONFIGURATION P-V VENT VALVE TYPEPRODUCT/TANK NO. NO LEAD I NO LEAD II Regular BEFORE DELIVERY LEVEL Fill Gauge Fill Gauge Fill Gauge Fill Gauge Fill Gauge LEVEL Full GALLONS WATER 1½" 1½" 1½" TOP OF RISER 97 96 101 132 GRADE 160 163 162 137 DROP TUBE AL AL AL CAPACITY, GALLONS 4000 4000 10000 DIAMETER, INCHES 64 64 64 MATERIAL STEEL STEEL STEEL PUMP TYPE Gasboy [illegible] Bennett TYPE OF COVER TAN TAN TAN AGE OF TANK UK UK UK SIPHON NO NO NO TANK OPENINGS 1-4" 1-2" 1-4" 1-2" 1-4" EXTRACTORS NO NO NO
ADDITIONAL CHARGES: (pumpovers, overtime, etc.) [illegible] [illegible] *Data obtained from ☐ Station ☐ LL Charts ☐ Other ______REPLACEMENT PARTS: PART # DESCRIPTION QUANTITY PRICE #701 [illegible] 1 [illegible] #124 [illegible] 1 [illegible] # 6" Quick Tite 2-gauge (wire) 1 [illegible]
Scanned pages and machine-read text of RSR-038 Attachment 2 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 2 REDACTED Page 1 of 1 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION
STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D.2. PG. of 1 1
SECTION A/B3. FOR STATE AGENCY USE ONLY A. SITE I.D. B. DATE RCVD BY D.E.P. C. DATE ENTERED D. GRID COORDINATES X ___ Y ___ E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
[redacted] SECTION C4. LOCATION OF FACILITY SITE NAME: East Hampton Service Center NO. AND STREET: 22 East High Street NEAREST INTERSECTING STREET: Route 2 CITY OR TOWN: East Hampton STATE: CT 5. LATITUDE: 41° 34' 56" LONGITUDE: 72° 30' 14" 6. BUSINESS NAME AND MAILING ADDRESS NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 7. FACILITY OWNER NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 8. TYPE OF OWNER X PRIVATE STATE MUNICIPAL FEDERAL (G.S.A. No. ___) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 22 East High Street CITY OR TOWN: East Hampton STATE: CT ZIP CODE: 06424
20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? X YES 21. COMMENTS: 16b coal tar epoxy. Tanks B2, D4, E5 & F6 budgeted for cathodic protection in 1986. A1 is also for [illegible] [illegible] SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.10. TANK ID. 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. TANK LIFE EXPECTANCY (# of years) 12a. TOTAL CAPACITY (Gals.) 12b. STATUS: IN USE ABANDONED IN PLACE EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No. if known) 15. CONSTRUCTION MATERIALS: STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) 16. PROTECTION a. INTERNAL: LINED UNLINED; b. EXTERNAL: CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION PROTECTION (See list B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (If "YES," enter DATE and attach results. If "NO," enter "NO") Example 5/75 30 5000 X X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X X E 7 7/60 U — A1 /72 15 275 X X X X X H 7 /72 H 092584 B2 /72 15 10000 X X X X 7 /72 O 092684 (10-14-86 / 092684 struck through) C3 '30 30 10000 X 0 11/84 X X 8 /80 O 092684 D4 '72 15 275 X X X X 7 /72 U 092584 E5 ,72 15 550 X X X X 7 /72 U 092884 P6 ,72 15 550 X X X X 7 /72 U 092884
COPY 422a. SIGNATURE X [redacted] 22b. DATE SIGNED 5/5/86 22c. NAME (Type or Print) [redacted] 22d. OFFICIAL TITLE (of owner or authorized representative) Senior Vice President
Text of RSR-038 Attachment 3.pdf
Extracted from the file · 1 page · 146 characters
Scanned pages and machine-read text of RSR-038 Attachment 4 REDACTED.pdf
Page 109 of 126
Full-size scan of page 109 (opens in a new tab)In the PDF: page 109 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 109 of 126 REDACTED PLEASE TYPE: COMPLETE ALL SECTIONS OF FORI! UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. FACILITY NOTIFICATION 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D. 3. FOR STATE AGENCY USE ONLY
SECTION A SECTION BB. DATE RCVD BY D.E.P C. DATE ENTERED D. GRID COORDINATES X Y E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
SECTION C4. LOCATION OF FACILITY SITE NAME: Madison Service Center NO. AND STREET: 135 New Road NEAREST INTERSECTING STREET: Duck Hole Road CITY OR TOWN: Madison STATE: CT S.LATITUDE LONGITUDE 6. BUSINESS NAME AND MAILING ADDRESS NAME NO. AND STREET CITY OR TOWN STATE ZIP CODE TELEPHONE 7. FACILITY OWNER NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 06141-0270 TELEPHONE: [redacted] 8. TYPE OF OWNER PRIVATE STATE MUNICIPAL FEDERAL (G.S.A. No. ) 9. OPERATOR/CONTACT PERSON NAME NO. AND STREET CITY OR TOWN STATE ZIP CODE TELEPHONE
20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? ☐ YES 21. COMMENTS: G7-16b-Tank is vaulted. and is an in process tank which isn't required to be registered. SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted. 22a. [redacted] 22b. DATE SIGNED: February 3, 1992 22d. OFFICIAL TITLE (of owner or authorized representative): Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTF[redacted]10. TANK ID 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. LIFE EXPECTANCY (# of years) 12a. TOTAL CAPACITY (Gals.) IN USE ABANDONED IN PLACE 12b. STATUS: EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS: OIL/PETROLEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS - CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known) 15. CONSTRUCTION MATERIALS: STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) 16. PROTECTION a. INTERNAL: LINED UNLINED CATHODIC PROTECTION b. EXTERNAL: COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 17. INTEGRAL PIPING SYSTEM a. b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results) (If "NO", enter "NO") Example 5/75 30 5000 X 8/78? X Heating fuel #2 X X H 3 H 5/75 U NO Example 7/60 - 8000 X 8/78 X I.I.I. - Trichloroethane CAS #79016 X X E 7 W 7/60 U - A1 /73 - 550 X 11/91 X Hydraulic Fluid B2 /73 - 550 X 11/91 X Motor Oil C3 /73 - 5000 X 1/92 X Unleaded Gasoline D4 /73 - 5000 X 1/92 X Unleaded Gasoline E5 80 /73 - 10000 X 8/89 X Unleaded Gasoline F6 /73 - 550 X 11/91 X Waste Oil G7 /73 30 170 X X Hydraulic Fluid X X X BP 8 WC /73 R NO H8 /73 - 1500 X /89 X Diesel Page 110 of 126
Full-size scan of page 110 (opens in a new tab)In the PDF: page 110 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 110 of 126 29 STATE OF CONNECTICUT CONNECTICUT UNDERGROUND STORAGE TANK PETROLEUM CLEAN-UP FUND REVIEW BOARD April 18, 1994 The Honorable Timothy R. E. Keeney Commissioner Department of Environmental Protection 79 Elm St. P.O. Box 5066 Hartford, CT 06102-5066 Dear Commissioner Keeney, Pursuant to Section 22a-449 of the Connecticut General Statutes as amended by Public Act 91-254 the Underground Storage Tank Petroleum Clean-up Fund Review Board, "the Board" met on April 12, 1994 to consider applications for reimbursement from the Fund. The board at its meeting voted to approve the following twenty-two claims in the amounts noted:Site No. Site Name and Address Amount 5 6 Tire Country of Enfield, 623 Hazard Ave., Enfield (Payment to: Frank J. Troiano, c/o Jim Ray, Robinson & Cole 1 Commercial Plz., Hartford, CT 06103-3597; SS# 012-30-1169) $52,799.57 22.1 1.2 Hartford Citgo, 888 New Britain Ave., Hartford (Payment to: Mercury Fuel Service, Inc., 43 Lafayette St., Waterbury, CT 06708; FEIN: 06-0769394) $15,705.04 118 1.2 Shell Service Station, 436 Slater Rd., New Britain (Payment to: Shell Oil Co., 175 Capitol Blvd., Suite 300, Rocky Hill, CT 06067; FEIN: 13-1299891) $50,649.70 134 1.2 Amoco Station #382, 927 East Main St., Meriden (Payment to: Amoco Oil Co., 41 Regan Rd., Ridgefield, CT 06877; FEIN: 36-2440313) $32,021.35 168 1.1 C,L & P, 135 New St., Madison (Payment to: The Connecticut Light & Power Co., P.O. Box 270, Hartford, CT 06141-0270 ATTN: John Szymanski; FEIN: 06-0303850) $9730.71 149 1.1 Johnson Glass & Auto Service, 276 Howe Ave., Shelton (Payment to: Krall Coal & Oil Co., 111 East St., New Haven, CT 06511; FEIN: 06-0417830) $17,896.03 139 1.1 Classic Carriage, 351 Boston Post Rd., Old Saybrook (Payment to: Hendel's, Inc., 35 Great Neck Rd., Waterford, CT 06385-0201; FEIN: 06-0641670) $33,291.27 141 1 Precision Auto Center, 1335 Hope St., Stamford (Payment to: Carole DeFrancesco, 40 Theresa Ct., Stamford, CT 06907; SS# 042-32-4888) $3653.70 Page 111 of 126
Full-size scan of page 111 (opens in a new tab)In the PDF: page 111 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 111 of 126 Mobil Oil claims:
(Payment to: Mobil Oil Corp., 134 Forbes Ave., New Haven, CT 06512; FEIN: 13-5401570) United Realty of Connecticut claims:153 1 Mobil Service Station #06-HAO, I95 Westbound, Darien $126,731.06 108 1 Mobil Station #06-E22, 205 Sound Beach Ave., Greenwich $17,534.29 163 1 Mobil Station #06-122, 995 South Main St., Cheshire $121,588.18 166 1 Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford $96,233.70 171 1 Mobil Station #06-HMO, 818 Federal Rd., Brookfield $193,288.79 152 1.1 Mobil Station #06-037, 519 Farmington Ave., Hartford $6823.32 155 1.2 Mobil Service Station #06-GPO, Newtown Rd., Danbury $3511.22 161 1.1 Mobil Station #06-ELA, 142 Willard Ave., Newington $3362.68 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $35,333.47
(Payment to: United Realty of Connecticut, 11 Crystal St., Stamford, CT 06902; FEIN: 06-0643088) The Board affirmed the settlement agreements recommended by the hearing officer for the following sites which were under appeal in the amounts noted:63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $3394.98 63 6.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $1997.02 63 7.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $2087.10
(Payment to: Petrol Plus, Inc., 38 Commerce St., Derby, CT 06418; FEIN: 06-0465420) In voting to authorize the Commissioner of Environmental Protection to make payments from the Fund as provided by Section 22a-449c(b) of the Connecticut General Statutes the Board determined that for each application a release occurred, damages resulted, and the costs of the claims are acceptable for the services/goods rendered. The amount of each authorized claim represented the amount of costs incurred by the applicant less $10,000 as required by Section 22a-449c of the Connecticut General Statutes as amended by PA No. 91-254. The Board, at its meeting, also voted to reject the following amounts due to the existence of grounds for recovery specified in Section 22a-449f of the general statutes:Site Site Name and Address Amount 28 Wethersfield Sunoco, 1780 Berlin Tpk., Wethersfield $570.90 32 Oxford Petrol Plus, 357 Oxford Rd., Oxford $2482.72 35 Sorel's Gulf, Rt. 6, Brooklyn 0 39 Orange Amoco, 404 Boston Post Rd., Orange $91.60 40 Cheshire Sunoco, 200 Meriden-Waterbury Rd., Cheshire $3613.40 89 Prospect Amoco, 21 Waterbury Rd., Prospect $464.79 90 Cheshire Texaco, 986 South Main St., Cheshire $2135.05 92 Groton Sunoco, 1023 Poquonnock Rd., Groton $17.30 112 Branford Sunoco 202 East Main St., Branford $8715.42 127 S & S Transmission, 208 Rt. 12, Groton $662.69 132 Rondeau's Gulf, 42 Woodstock Ave., Putnam $1500.00 Site Site Name and Address Amount Reduction 63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $507.30 13% 63 6.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $298.41 13% Page 112 of 126
Full-size scan of page 112 (opens in a new tab)In the PDF: page 112 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 112 of 126
The Board, at its meeting, also voted to reject the following amounts due to incompleteness:63 7.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $311.86 13% 108 1 Mobil #06-E22, 205 Sound Beach Ave., Greenwich $1757.51 6% 152 1.1 Mobil #06-037, 519 Farmington Ave., Hartford $4131.70 20% 163 1 Mobil #06-122, 995 South Main St., Cheshire $4094.18 5%
The Board, at its meeting, also voted to reject the following amounts due to ineligibility.Site No. Site Name and Address Amount 63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $282.71 153 1 Mobil Service Station #06-HAO, I95 Westbound, Darien $2264.47 22.1 1.1 Hartford Citgo, 888 New Britain Ave., Hartford $8983.77 118 1.1 Shell Service Station, 436 Slater Rd., New Britain $4532.00 134 1.1 Amoco Station #382, 927 East Main St., Meriden $76,576.21 155 1.2 Mobil Service Station #06-GPO, Newtown Rd., Danbury $3619.40 168 1.1 C,L & P, 135 New St., Madison $34,250.20
The following amounts were withdrawn by the applicants:Site No. Site Name and Address Amount 139 1.1 Classic Carriage, 351 Boston Post Rd., Old Saybrook $10,575.44 149 1.1 Johnson Glass & Auto Service, 176 Howe Ave., Shelton $8322.48 134 1.1 Amoco Station #382, 927 East Main St., Meriden $19,636.34 152 1.1 Mobil Station #06-037, 519 Farmington Ave., Hartford $579.92 161 1.1 Mobil Station #06-ELA, 142 Willard Ave., Newington $9473.94 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $9469.81
Sincerely, [signature] John Mitchell Chairman Underground Storage Tank Petroleum Clean-up Fund BoardSite No. Site Name and Address Amount 5 6 Tire Country of Enfield, 623 Hazard Ave., Enfield $13,539.84 34 11 Monroe Petrol Plus, 40-44 Main St., Monroe $131,870.41 108 1 Mobil #06-E22, 205 Sound Beach Ave., Old Greenwich $12,276.68 163 1 Mobil Station #06-122, 995 South Main St., Cheshire $31,645.10 166 1 Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford $218,487.37 169 1 Rite-Way #2, 2 Scott Rd., Waterbury $67,196.21 171 1 Mobil Station #06-HMO, 818 Federal Rd., Brookfield $102,209.48 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $7540.69 Page 113 of 126
Full-size scan of page 113 (opens in a new tab)In the PDF: page 113 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 113 of 126 30 GEL CORRESPONDENCE RECEIPT AND DISTRIBUTION FORM TO: GENERATION ENVIRONMENTAL LICENSING FROM: Sears C.F. Sears Please distribute the attached document to involved or affected disciplines in the NU system and insure proper and timely action based on their input, as appropriate. LETTER NO: c 05673 AGENCY: CDP FACILITY: MADISON CODE(unit): BGN LETTER DATE: April 1?, 1994 TITLE/SUBJECT: UST Petroleum Cleanup Fund -Award RECEIPT DATE: 5-9-94 DISTRIBUTION/ACTION
NRC ☐ Yes ☐ NoDS A PERSON C/A DISCIPLINE LOC. EXT REMARKS P.M. Jacobson Env. Prog.Br. Mgr. NU East 4642 X X R. Klattenberg ERM NU East 4628 T.J. Butwill F/H Eng. (Civil) N206 5403 FH Eng. & Const. N207 X X D. Gilbane Legal E217 3731 Land Planning NU East POS Env. Comp. W239 Hydro Production W239 J.W. McLaughlin Hydro Prod., NH Manch. J.B. Lander Env. & Results, NH Manch. X X M. Hornyak ERM NU East 4613 X X T. Elye Facilities Mgr. NU East 6750 Facility Mgr./Supt. Fac. Opns. & Engng NU East Trans. CT&M 3333 W.H. Smagula Dir. - Fossil Prod. W239 5467 W.J. Nadeau Dir. - Hydro Prod. W239 5064 D.R. Brown PSNH Production Manch. Lead Discipline Project Engineer X X J. Szymanski X GEL Lead W218 3743 Supvsr - NL W218 L.E. Bireley X Manager-GEL W218 5448
COMMITMENT / ACTION TRACKING INFORMATION Response To: COTRAP # D____ or FORCOM # F____ DUE DATE:____ Commitment Number | GEL Lead | Lead Discipline | Response Date | DESCRIPTION REV. 9 11-93OTHER DISTRIBUTION GEL CLERK INSTRUCTIONS X X Facilities File TELECOPY TO: ATTACHMENTS (X in "A" Column) Page 114 of 126
Full-size scan of page 114 (opens in a new tab)In the PDF: page 114 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 114 of 126 STATE OF CONNECTICUT CONNECTICUT UNDERGROUND STORAGE TANK PETROLEUM CLEAN-UP FUND REVIEW BOARD April 18, 1994 [redacted] MAY 9 1994 ENVIRONMENTAL The Honorable Timothy R. E. Keeney Commissioner Department of Environmental Protection 79 Elm St. P.O. Box 5066 Hartford, CT 06102-5066 Dear Commissioner Keeney, Pursuant to Section 22a-449 of the Connecticut General Statutes as amended by Public Act 91-254 the Underground Storage Tank Petroleum Clean-up Fund Review Board, "the Board" met on April 12, 1994 to consider applications for reimbursement from the Fund. The board at its meeting voted to approve the following twenty-two claims in the amounts noted:
165 Capitol Avenue • Hartford, Connecticut 06106 Phone:Site No. Site Name and Address Amount 5 6 Tire Country of Enfield, 623 Hazard Ave., Enfield (Payment to: Frank J. Troiano, c/o Jim Ray, Robinson & Cole 1 Commercial Plz., Hartford, CT 06103-3597; SS# 012-30-1169) ~$52,799.57 22.1 1.2 Hartford Citgo, 888 New Britain Ave., Hartford (Payment to: Mercury Fuel Service, Inc., 43 Lafayette St., Waterbury, CT 06708; FEIN: 06-0769394) $15,705.04 118 1.2 Shell Service Station, 436 Slater Rd., New Britain (Payment to: Shell Oil Co., 175 Capitol Blvd., Suite 300, Rocky Hill, CT 06067; FEIN: 13-1299891) $50,649.70 134 1.2 Amoco Station #382, 927 East Main St., Meriden (Payment to: Amoco Oil Co., 41 Regan Rd., Ridgefield, CT 06877; FEIN: 36-2440313) $32,021.35 168 1.1 C,L & P, 135 New St., Madison (Payment to: The Connecticut Light & Power Co., P.O. Box 270, Hartford, CT 06141-0270 ATTN: John Szymanski; FEIN: 06-0303850) $9730.71 149 1.1 Johnson Glass & Auto Service, 276 Howe Ave., Shelton (Payment to: Krall Coal & Oil Co., 111 East St., New Haven, CT 06511; FEIN: 06-0417830) $17,896.03 139 1.1 Classic Carriage, 351 Boston Post Rd., Old Saybrook (Payment to: Hendel's, Inc., 35 Great Neck Rd., Waterford, CT 06385-0201; FEIN: 06-0641670) $33,291.27 141 1 Precision Auto Center, 1335 Hope St., Stamford (Payment to: Carole DeFrancesco, 40 Theresa Ct., Stamford, CT 06907; SS# 042-32-4888) $3653.70 Page 115 of 126
Full-size scan of page 115 (opens in a new tab)In the PDF: page 115 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 115 of 126 Mobil Oil claims:
(Payment to: Mobil Oil Corp., 134 Forbes Ave., New Haven, CT 06512; FEIN: 13-5401570) United Realty of Connecticut claims:153 1 Mobil Service Station #06-HAO, I95 Westbound, Darien $126,731.06 108 1 Mobil Station #06-E22, 205 Sound Beach Ave., Greenwich $17,534.29 163 1 Mobil Station #06-122, 995 South Main St., Cheshire $121,588.18 166 1 Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford $96,233.70 171 1 Mobil Station #06-HMO, 818 Federal Rd., Brookfield $193,288.79 152 1.1 Mobil Station #06-037, 519 Farmington Ave., Hartford $6823.32 155 1.2 Mobil Service Station #06-GPO, Newtown Rd., Danbury $3511.22 161 1.1 Mobil Station #06-ELA, 142 Willard Ave., Newington $3362.68 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $35,333.47
(Payment to: United Realty of Connecticut, 11 Crystal St., Stamford, CT 06902; FEIN: 06-0643088) The Board affirmed the settlement agreements recommended by the hearing officer for the following sites which were under appeal in the amounts noted:63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $3394.98 63 6.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $1997.02 63 7.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $2087.10
(Payment to: Petrol Plus, Inc., 38 Commerce St., Derby, CT 06418; FEIN: 06-0465420) In voting to authorize the Commissioner of Environmental Protection to make payments from the Fund as provided by Section 22a-449c(b) of the Connecticut General Statutes the Board determined that for each application a release occurred, damages resulted, and the costs of the claims are acceptable for the services/goods rendered. The amount of each authorized claim represented the amount of costs incurred by the applicant less $10,000 as required by Section 22a-449c of the Connecticut General Statutes as amended by PA No. 91-254. The Board, at its meeting, also voted to reject the following amounts due to the existence of grounds for recovery specified in Section 22a-449f of the general statutes:Site Site Name and Address Amount 28 Wethersfield Sunoco, 1780 Berlin Tpk., Wethersfield $570.90 32 Oxford Petrol Plus, 357 Oxford Rd., Oxford $2482.72 35 Sorel's Gulf, Rt. 6, Brooklyn 0 39 Orange Amoco, 404 Boston Post Rd., Orange $91.60 40 Cheshire Sunoco, 200 Meriden-Waterbury Rd., Cheshire $3613.40 89 Prospect Amoco, 21 Waterbury Rd., Prospect $464.79 90 Cheshire Texaco, 986 South Main St., Cheshire $2135.05 92 Groton Sunoco, 1023 Poquonnock Rd., Groton $17.30 112 Branford Sunoco 202 East Main St., Branford $8715.42 127 S & S Transmission, 208 Rt. 12, Groton $662.69 132 Rondeau's Gulf, 42 Woodstock Ave., Putnam $1500.00 Site Site Name and Address Amount Reduction 63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $507.30 13% 63 6.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $298.41 13% Page 116 of 126
Full-size scan of page 116 (opens in a new tab)In the PDF: page 116 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 116 of 126
The Board, at its meeting, also voted to reject the following amounts due to incompleteness:63 7.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $311.86 13% 108 1 Mobil #06-E22, 205 Sound Beach Ave., Greenwich $1757.51 6% 152 1.1 Mobil #06-037, 519 Farmington Ave., Hartford $4131.70 20% 163 1 Mobil #06-122, 995 South Main St., Cheshire $4094.18 5%
The Board, at its meeting, also voted to reject the following amounts due to ineligibility.Site No. Site Name and Address Amount 63 5.1 High Ridge Citgo, 1070 High Ridge Rd., Stamford $282.71 153 1 Mobil Service Station #06-HAO, I95 Westbound, Darien $2264.47 22.1 1.1 Hartford Citgo, 888 New Britain Ave., Hartford $8983.77 118 1.1 Shell Service Station, 436 Slater Rd., New Britain $4532.00 134 1.1 Amoco Station #382, 927 East Main St., Meriden $76,576.21 155 1.2 Mobil Service Station #06-GPO, Newtown Rd., Danbury $3619.40 168 1.1 C,L & P, 135 New St., Madison $34,250.20
The following amounts were withdrawn by the applicants:Site No. Site Name and Address Amount 139 1.1 Classic Carriage, 351 Boston Post Rd., Old Saybrook $10,575.44 149 1.1 Johnson Glass & Auto Service, 176 Howe Ave., Shelton $8322.48 134 1.1 Amoco Station #382, 927 East Main St., Meriden $19,636.34 152 1.1 Mobil Station #06-037, 519 Farmington Ave., Hartford $579.92 161 1.1 Mobil Station #06-ELA, 142 Willard Ave., Newington $9473.94 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $9469.81
Sincerely, [signature] John Mitchell Chairman Underground Storage Tank Petroleum Clean-up Fund BoardSite No. Site Name and Address Amount 5 6 Tire Country of Enfield, 623 Hazard Ave., Enfield $13,539.84 34 11 Monroe Petrol Plus, 40-44 Main St., Monroe $131,870.41 108 1 Mobil #06-E22, 205 Sound Beach Ave., Old Greenwich $12,276.68 163 1 Mobil Station #06-122, 995 South Main St., Cheshire $31,645.10 166 1 Mobil Station #06-QBA, 1164 Boston Post Rd., Guilford $218,487.37 169 1 Rite-Way #2, 2 Scott Rd., Waterbury $67,196.21 171 1 Mobil Station #06-HMO, 818 Federal Rd., Brookfield $102,209.48 170 1.1 Mobil Station #06-HGO, 1705 Park St., Bridgeport $7540.69 Page 117 of 126
Full-size scan of page 117 (opens in a new tab)In the PDF: page 117 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 117 of 126 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSION 5487/FAX 5896
DISTRIBUTION/SIGNOFF Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.FACILITY: Madison Service Center CODE(unit): BGN LETTER NO: D 08179 TITLE/SUBJECT: Supplemental Application for Reimbursement from the Fund - Site No. 168 AGENCY: CDP SPECIAL INSTRUCTIONS: LETTER DATE: 11/28/94
COMMITMENT / ACTION TRACKING INFORMATION Response To: COTRAP # C____________ or FORCOM # F____________ DUE DATE: __________ Number of Calendar days in Advance (+) or Late (-) of Due Date____________DS A PERSON SO DISCIPLINE LOC. EXT INIT. DATE COMMENTS P.M. Jacobson Env. Programs Mgr. NU East 4642 M. Keser Aqua.Ser.Br. Mgr. NUEL 4238 P. Brindamour Aqua. Services NU East T.J. Butwill F/H Eng. (Civil) N206 5403 X R.P. Klahenberg X ERM NU East 4628 RPK 11/21/94 Nice job X D. Gilbane X Legal E217 3431 [illegible] 11/22/94 [illegible] Land Planning NU East J.P. Donohue POS Env. Comp. Mgr. W239 Hydro Production W239 J.W. McLaughlin Hydro Prod., NH Manch. R. Pickering Env. & Results, NH Manch. X W. Haynack X ERM NU East 4613 [illegible] 11/21/94 As noted X D. Fleming Tolland Facility Mgr./Supt. Fac. Opns. & Engng NU East Trans. CT&M 3333 W.H. Smagula Dir. - Fossil Prod. W239 5467 W.J. Nadeau Dir. - Hydro Prod. W239 5064 D.R. Brown PSNH Production Manch. Lead Discipline Project Engineer X L. Sheridan X GEL Lead W218 N22 3743 LMS 11/23/94 Supvsr - NL W218 NRC ☐ Yes ☐ No L.E. Bireley X GEL Manager W218 N22 5448 [illegible] 11/28/94 OTHER DISTRIBUTION GEL CLERK INSTRUCTIONS X X Facilities File X ORIGINAL AND ____ COPIES X C.A. Edge NU East FEE CHECK FEDERAL EXPRESS REGISTERED MAIL TELECOPY
REV. 9 11-93Commitment Number GEL Lead Lead Discipline Response Date DESCRIPTION Page 118 of 126
Full-size scan of page 118 (opens in a new tab)In the PDF: page 118 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 118 of 126 Northeast Utilities System 107 Selden Street, Berlin, CT 06037 Northeast Utilities Service Company P.O. Box 270 Hartford, CT 06141-0270 [redacted] November 28, 1994 D08179 UST Petroleum Clean-Up Fund Review Board Bureau of Waste Management Department of Environmental Protection 79 Elm Street Hartford, CT 06102 Dear Sir or Madam: Madison Service Center Supplemental Application for Reimbursement from the Fund - Site No. 168 Northeast Utilities Service Company (NUSCO), on behalf of The Connecticut Light and Power Company (CL&P), hereby submits a supplemental application for reimbursement from the UST Petroleum Clean-Up Fund for the referenced site. This supplemental application covers the period beginning May, 1993 and ending June 30, 1994. The total amount requested for the referenced period is $49,283.32. Fuss & O'Neill, Inc. prepared this application in cooperation with our operations, environmental and laboratory personnel. Attached documentation includes the following: • Application Forms (sheets 1 and 2 only of full application) • Summary of Total Costs and Supporting Data for Contracted Services • Supporting Data for Costs Incurred by NUSCO Environmental Programs Personnel • Supporting Data for Costs Incurred by Production Operations Services Laboratory • Environmental Assessment and Progress Reports (April, May, June, 1994) We trust that the application forms, supporting cost and environmental data provides sufficient detail for review by DEP staff. Both NUSCO and Fuss & O'Neill, Inc. are prepared to answer any questions that may arise during your review. Please call Mr. [redacted] NUSCO Environmental Programs, at [redacted] initiate disc[redacted] Very truly yours, THE CONNECTICUT LIGHT AND POWER COMPANY [redacted] Attachment OS3422 REV. 1-94
As listed on the current system
Question(s) Answered 38 (The Connecticut Light and Power Company) Date Filed: 10/20/2026