Interrogatory responses
Answers to questions 38
Files5
RSR-038_Final.pdf
PDF · 146 KB · 7 pagesText searchable
Download RSR-038_Final.pdfRead the text of RSR-038_Final.pdf
RSR-038 Attachment 1 REDACTED.pdf
PDF · 4.6 MB · 19 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 1 REDACTED.pdfScanned pages and text of RSR-038 Attachment 1 REDACTED.pdf
RSR-038 Attachment 2 REDACTED.pdf
PDF · 798 KB · 1 pageText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 2 REDACTED.pdfScanned pages and text of RSR-038 Attachment 2 REDACTED.pdf
RSR-038 Attachment 3.pdf
PDF · 502 KB · 1 pageText searchable
Download RSR-038 Attachment 3.pdfRead the text of RSR-038 Attachment 3.pdf
RSR-038 Attachment 4 REDACTED.pdf
PDF · 51 MB · 126 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 4 REDACTED.pdfScanned pages and text of RSR-038 Attachment 4 REDACTED.pdf
Scanned pages and machine-read text of RSR-038 Attachment 1 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 1 of 19 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] April 13, 1988 D01928 Mr. Ronald Corey, Fire Marshall City of Torrington 111 Water Street Torrington, Connecticut 06790 Reference: Letter and Notification, [redacted] o R. Corey, dated May 8, 1986. Dear Mr. Corey: Torrington Area Work Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for the Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Torrington Area Work Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the removal of all of the tanks (A1, B2, C3, D4) at the site. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted]. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] [redacted] Senior Vice President [redacted] By: C. F. Sears Vice President
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 2 of 19 Mr. Ronald Corey, Fire Marshall DO1928/Page 2 April 13, 1988 Enclosure cc: w/enclosure (Copy 1) Mr. Scott Deshefy Hazardous Material's Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Mr. Richard Ciasullo Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 3 of 19 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION | PG. 2 of 1 | SITE ID | FOR STATE AGENCY USE ONLY | A. SITE I.D. | B. DATE RCVD BY D E P | C. DATE ENTERED | D. GRID COORDINATES X Y | E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM-6 NEW 10/85 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
SECTION C 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [X] YES 21. COMMENTS: SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.4. LOCATION OF FACILITY SITE NAME: Torrington Area Work Center NO. AND STREET: 174 Franklin Street NEAREST INTERSECTING STREET: Horwinton Ave. CITY OR TOWN: Torrington STATE: CT 5. LATITUDE: 41° 48' 00" LONGITUDE: 73° 06' 55" 5. BUSINESS NAME AND 6. MAILING ADDRESS NAME: The Connecticut Light + Power Co. (CL4P) NO. AND STREET: P O Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 06141-0270 7. FACILITY OWNER NAME: CL&P NO. AND STREET: Same as Above CITY OR TOWN STATE ZIP CODE 8. TYPE OF OWNER PRIVATE (checked) STATE MUNICIPAL FEDERAL (G.S.A. No.) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 174 Franklin Street CITY OR TOWN: Torrington STATE: CT ZIP CODE: 06790 TELEPHONE: 1203 482-4471 10. TANK ID 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. LIFE EXPECTANCY (in years) 12a. TOTAL CAPACITY (Gals.) IN USE ABANDONED IN PLACE 12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known) 15. CONSTRUCTION MATERIALS STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) c. INTERNAL UNLINED b. EXTERNAL UNLINED CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 16. PROTECTION 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (from list A/B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (if "YES", enter DATE and attach results; if "NO", enter "NO") Example 5/75 30 5000 X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X E 7 7/60 U - A1 12/78 15 10,000 X 4/88 X Regular Gasoline X X E 7E 12/78 O 3-15-84 B2 1/64 15 4,000 X 3/88 X Diesel Fuel X X E 7E 1/64 O 3-15-84 C3 1/64 15 4,000 X 3/88 X Unleaded Gasoline X X E 7E 1/64 O 3-15-84 D4 1/60 15 500 X 3/88 X Waste Oil X X E 7E 1/60 U NO
22c. NAME (type or print) [redacted] 22d. OFFICIAL TITLE | Vice President / Senior Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 0610622a. SIGNATURE X [redacted] 22b. DATE SIGNED 13 April 1988 
The scanned page Machine-read text
REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 4 of 19 CONN LIGHT & POWER CO. NORTHEAST UTILITIES WORK ORDER SKETCH SHEET
SKETCH INDICATE NORTH AND NAME STREETS Not To Scale B2 A1 21' 140' 159' 177' 44' 275' 255' D4 C3 GARAGE TRANSMISSION TORRINGTON SERVICE BUILDING HARWINTON SCHIBI ST. AVE. OP418? REV. 10-82 DEST. SAME AS ATT. REC. DRAWN BY | TELEPHONE EXT.DISTRICT / REGION TOWN DATE MAP NO. WORK ORDER NO. ACTV. SHEET OF TORRINGTON / WESTERN TORRINGTON 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 5 of 19 REDACTED TO: File FROM: John Szymanski [signature] April 14, 1988 SUBJECT: Torrington AWC Tank removals were conducted at the Torrington AWC during the months of March and April 1988. o During March 1988: One (1) 4000 gallon unleaded gasoline tank and One (1) 500 gallon oil tank were removed; no problems o On March 30, 1988: Notified that (1) 4000 gallon diesel tank was removed with heavy rusting and several apparent holes the size of dimes. o On March 30, 1988: Examined site and took three (3) samples from excavation hole and one (1) sample from diesel tank to have material analyzed and identified by LAB per request by DEP Field Inspector, Richard Ciasullo. o On March 31, 1988: Samples dropped off for analyzing and identification at Souther-Newlands Laboratory. o On April 4, 1988: Souther Newland Laboratory called EPD office to report on lab findings. - Sample from diesel tank identified as diesel fuel - The three (3) samples from the excavation hole all had the same characteristic profiles, but it didn't match that of gasoline or diesel fuel and that it would take two to three weeks to identify samples from the excavation hole. o On Aril 4, 1988: Notified R. Robinson of the DEP Clean Water Group of the test results and asked for permission to continue tank installation construction after film cleaned off top of water and remainder of gray colored gravel removed from hole. Mr. Robinson gave approval to continue construction if I inspected site and assured this was done. o On April 6, 1988: NUSCO construction removed film from water and lowered water table by sucking out 3200 gallons of contaminated water which was hauled off site as contaminated waste water. Removed the remainder of gray contaminated gravel from excavation hole. o On April 6, 1988 after water table lowered gasoline film and strong fumes entered the excavation hole. The fire marshal was notified, who requested DEP to inspect the hole. Concern was generated regarding 10,000 gallon unleaded gasoline tank in the same vicinity where gas fumes and film were found. Construction stopped. o On April 7, 1988: DEP Field Inspector Richard Ciasullo and
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 6 of 19 Torrington Fire Marshal Ron Corey arrived on site and gave us two alternatives: 1. Test tank full of product and be ready to remove it immediately if tank leaks; 2. Remove 10,000 gallon unleaded tank. o April 7, 1988: Discussions were held between Area Superintendent Walt Wadman, Ken Busick, Frank Melluzzo, Bud Meyer, John Betz, Jack Farrel and John Szymanski to discuss options and make decision as to disposition of 10,000 gallon gasoline tank. Final consensus was to remove tank based on presence of gasoline odor and fumes in area, water level in tank raised when emptied of product, bottom ash found in vicinity of tank, tank had been unprotected for 10 years, the older unprotected tank 4000 diesel came out of ground looking like swiss cheese. o April 7, 1988: Removed 10,000 gallon unleaded gasoline tank, some heavy rusting and pitting visible on tank but there was no apparent holes. Backfill around tank was improper per today's installation standards (very large boulders, large gravel and some sand) there were no hold down straps on tank, and bottom ash in close proximity to tank. Wet lines were heavily rusted in one large area.
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 7 of 19 REDACTED Distribution: [redacted]Claims and Insurance [redacted]s. and Test Department [redacted]Regional Operations - WMECO [redacted]struction [redacted]HP [redacted]rans. SS and Mtce. [redacted] Trans. Bldg. Eng. Design [redacted]nsportation [redacted] EPD [redacted]ores [redacted] EPD [redacted]cilities Management [redacted] Legal [redacted] Nuclear Prod. [redacted]en. Fac. Lic. Dept. bsl cc: [redacted]
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 8 of 19 TORRINGTON AUG / CT Bemis / Laura Lionts leak lokator hunter ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] TEST RESULTS DATE OF TEST | 07-6-85 CONTRACT NUMBER
TEST RESULTS SUMMARYCUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER NAME ADDRESS 178 Franklin Drive CITY Torrington STATE Conn LEAK LOKATOR USE ONLY CONCL. CODE
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS TEST TANK SYS II No Lead Tank #I 4000 64/37 1 1/2" 106" .039 Tight II No Lead Tank #II 4000 64/37 1 1/2" 95" .038 Tight VII Regular Lead 10000 96/3T 1 1/2" 113" .038 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE TYPE OF PUMP SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT II No Lead Tank I > ✓ DL Pressure test test X II No Lead Tank II > ✓ 170 Pressure test test X III Regular Leaded > Pump ✓ Side [illegible] [illegible] X X Tight NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) CLOCK START DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMP COMP Δ°F TEMP COMP CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I No Lead Tank I 1 106" 9:45 31 min .39 +25.95 +.161 +33.80 -1.85 -.039 N II No Lead Tank II 1 95" 7:52 31 min .47 +2.82 +.636 +6.37 -2.44 -.038 N III Regular Leaded 1 142" 11:46 20 min .35 +21.47 +.655 23.88 -2.41 -.038 N 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 9 of 19 REDACTED ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] Bemis | TORRINGTON AWG / CT Laura [illegible] leak lokator TEST RESULTS DATE OF TEST | 03-6-8? CONTRACT NUMBER CUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER
TEST RESULTS SUMMARYADDRESS 178 Franklin Drive NAME CITY Torrington STATE Con
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS LEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS I NO LEAD TANK I 4500 64.37 1 1/2" 166" -.029 Tight II NO LEAD TANK II 4500 64.37 1 1/2" 95" -.038 Tight III REGULAR LEADED 10000 96 x T 1 1/2" 115" -.026 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT I NO LEAD TANK I ✓ DO DO [illegible] test X II NO LEAD TANK II ✓ test X III REGULAR LEADED ✓ ✓ 110 Due X III REGULAR LEADED ✓ Pump ✓ [illegible] [illegible] [illegible] [illegible] Tight
* LEVEL – INCHES FROM TANK BOTTOM TO TEST LEVEL ALR – ABSOLUTE LEAK RATE (MEASURED LEAK RATE – TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION – NFPA 329 CRITERION OF ± 0.05 GPH IS USED TO CERTIFY TIGHTNESS CERTIFICATION This is to certify that the above described tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated as tight meet the criterion established by the National Fire Protection Association Pamphlet 329 for Precision Testing.NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) TIME CLOCK START TIME DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMPERATURE COMPENSATION Δ°F TEMPERATURE COMPENSATION CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I NO LEAD TANK I 1 166" 9:45 31 min .39 +25.95 +.141 +27.82 -1.85 -.029 N II NO LEAD TANK II 1 95" 9:52 35 min 4.17 12.08 +.036 16.37 -2.44 -.038 N III REGULAR LEADED 1 114" 9:46 30 min -.37 +21.17 +.255 23.66 -2.41 -.038 N TESTS CONDUCTED BY CERTIFIED BY TEST VAN NO. [illegible] SIGNATURE [illegible] TANK TESTING SPECIALIST [illegible] NAME [illegible] DATE [illegible] TANK TESTING SPECIALIST [illegible] TITLE [illegible] 
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 10 of 19 TANK AND LOCATION DATA DATE: 03-6-85
SCHEMATIC: Building PUMP NO LEAD II 4000gal 64" NO LEAD II 4000gal 64" NO LEAD PUMP VENT Regular PUMPS VENT Regular LEADED 10000gal 96" BuildingCUSTOMER: Northeast Utilities CITY: Torrington I.D. # STATE: Conn WEATHER TIME TEMPERATURE COMMENTS BEFORE TEST – AFTER TEST –
VAPOR RECOVERY TYPE VENT CONFIGURATION P-V VENT VALVE TYPEPRODUCT/TANK NO. NO LEAD I NO LEAD II Regular BEFORE DELIVERY LEVEL Fill Gauge Fill Gauge Fill Gauge Fill Gauge Fill Gauge LEVEL Full GALLONS WATER 1½" 1½" 1½" TOP OF RISER 97 96 101 132 GRADE 160 163 162 137 DROP TUBE AL AL AL CAPACITY, GALLONS 4000 4000 10000 DIAMETER, INCHES 64 64 64 MATERIAL STEEL STEEL STEEL PUMP TYPE Gasboy [illegible] Bennett TYPE OF COVER TAN TAN TAN AGE OF TANK UK UK UK SIPHON NO NO NO TANK OPENINGS 1-4" 1-2" 1-4" 1-2" 1-4" EXTRACTORS NO NO NO
ADDITIONAL CHARGES: (pumpovers, overtime, etc.) [illegible] [illegible] *Data obtained from ☐ Station ☐ LL Charts ☐ Other ______REPLACEMENT PARTS: PART # DESCRIPTION QUANTITY PRICE #701 [illegible] 1 [illegible] #124 [illegible] 1 [illegible] # 6" Quick Tite 2-gauge (wire) 1 [illegible]
Scanned pages and machine-read text of RSR-038 Attachment 2 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 2 REDACTED Page 1 of 1 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION
STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D.2. PG. of 1 1
SECTION A/B3. FOR STATE AGENCY USE ONLY A. SITE I.D. B. DATE RCVD BY D.E.P. C. DATE ENTERED D. GRID COORDINATES X ___ Y ___ E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
[redacted] SECTION C4. LOCATION OF FACILITY SITE NAME: East Hampton Service Center NO. AND STREET: 22 East High Street NEAREST INTERSECTING STREET: Route 2 CITY OR TOWN: East Hampton STATE: CT 5. LATITUDE: 41° 34' 56" LONGITUDE: 72° 30' 14" 6. BUSINESS NAME AND MAILING ADDRESS NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 7. FACILITY OWNER NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 8. TYPE OF OWNER X PRIVATE STATE MUNICIPAL FEDERAL (G.S.A. No. ___) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 22 East High Street CITY OR TOWN: East Hampton STATE: CT ZIP CODE: 06424
20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? X YES 21. COMMENTS: 16b coal tar epoxy. Tanks B2, D4, E5 & F6 budgeted for cathodic protection in 1986. A1 is also for [illegible] [illegible] SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.10. TANK ID. 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. TANK LIFE EXPECTANCY (# of years) 12a. TOTAL CAPACITY (Gals.) 12b. STATUS: IN USE ABANDONED IN PLACE EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No. if known) 15. CONSTRUCTION MATERIALS: STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) 16. PROTECTION a. INTERNAL: LINED UNLINED; b. EXTERNAL: CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION PROTECTION (See list B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (If "YES," enter DATE and attach results. If "NO," enter "NO") Example 5/75 30 5000 X X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X X E 7 7/60 U — A1 /72 15 275 X X X X X H 7 /72 H 092584 B2 /72 15 10000 X X X X 7 /72 O 092684 (10-14-86 / 092684 struck through) C3 '30 30 10000 X 0 11/84 X X 8 /80 O 092684 D4 '72 15 275 X X X X 7 /72 U 092584 E5 ,72 15 550 X X X X 7 /72 U 092884 P6 ,72 15 550 X X X X 7 /72 U 092884
COPY 422a. SIGNATURE X [redacted] 22b. DATE SIGNED 5/5/86 22c. NAME (Type or Print) [redacted] 22d. OFFICIAL TITLE (of owner or authorized representative) Senior Vice President
Text of RSR-038 Attachment 3.pdf
Extracted from the file · 1 page · 146 characters
Scanned pages and machine-read text of RSR-038 Attachment 4 REDACTED.pdf
Page 69 of 126
Full-size scan of page 69 (opens in a new tab)In the PDF: page 69 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 69 of 126 HUNTER ENVIRONMENTAL SERVICES, INC. FINAL TEST REPORT San Francisco, CA | Philadelphia, PA | Tampa, FL DATE March 19, 1991 CONTACT: [redacted]
ADDITIONAL COMMENTS *GRADE - INCHES FROM BOTTOM OF TANK TEST LEVEL - INCHES FROM BOTTOM OF TANK GPH - ABSOLUTE LEAK RATE (MEASURED LEAK RATE - TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION IS BASED ON NFPA 329 STANDARD OF ±0.05 GPH ADDITIONAL SERVICES PRODUCT LINES — HYDROSTATIC PRESSURE TEST RESULTSLOCATION: Connecticut Light & Power CUSTOMER: Northeast Utilities LL: 47 135 New Road OO/ER Madison CT SYSTEM# PRODUCT TANK SIZE GALLON TANK SIZE DIAM. (IN.) WATER LEVEL (IN.) LEAK LOKATOR RESULTS GRADE (IN.) LEAK LOKATOR RESULTS TEST LEVEL (IN.) LEAK LOKATOR RESULTS GPH LEAK LOKATOR RESULTS CONCLUSION PASS/FAIL COMMENTS Regular Unleaded 5,000 96 0 134 140 -.032 X
5 & ½SYSTEM TYPE OF PUMP # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION COMMENTS Reg. U/L Gilbarco Remote ☐ Submersible ☐ Suction ☒ PASS ☐ FAIL ☐ Remote ☐ Submersible ☐ Suction ☐ PASS ☐ FAIL ☐ Remote ☐ Submersible ☐ Suction ☐ PASS ☐ FAIL ☐ Remote ☐ Submersible ☐ Suction ☐ PASS ☐ FAIL ☐ QTY PART # DESCRIPTION PRICE EA. QTY PART # DESCRIPTION PRICE EA Page 70 of 126
Full-size scan of page 70 (opens in a new tab)In the PDF: page 70 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 70 of 126 HUNTER ENVIRONMENTAL SERVICES, INC. 512 TOWNSHIP LINE ROAD, SUITE 230 BLUE BELL, PA 19422 215 540-5400 or 800 248-6837
CONTACT: [redacted]FINAL TEST REPORT PG. 1/ 2 DATE OF TEST: 3/19/91 LL473191.91 3837 CUSTOMER: NORTHEAST UTILITIES LOCATION: NORTHEAST UTILITIES
LOCATION ID: 0 SITE INFORMATIONSITE CONTACT: ED VALENE ADDRESS: 135 NEW RD. ASSIGNED TESTING TEAM: LL47 PHONE: [redacted] MADISON CT. 0
††† GROUND WATER LEVEL IS THE DEPTH TO GROUND WATER FROM GRADE, IN INCHES ††† HYDROSTATIC PRODUCT LINE PRESSURE TESTS AND/OR LEAK DETECTOR TESTSSYS NO. PRODUCT NAME TANK NO. CAPACITY GALLONS DIAMETER INCHES WATER LEVEL INCHES GRADE INCHES GROUND WATER LEVEL TEST NO. TEST LEVEL INCHES LEAK RATE GPH CONFIDENCE INTERVAL GPH CONCLUSION PASS/FAIL 1 REGULAR UNLEADED GASOLINE 1 5000 96 0.00 134 1 140.00 -0.0328 0.0016 PASS
REPLACEMENT PARTS QTY | PART NO. | DESCRIPTION PUMP OVER: gal. FROM: TO: COMMENTS: CERTIFICATION: The tank systems described above were tested using HUNTER PRECISION TESTING, INC. LEAK LOKATOR LD3000 according to all standard operating procedures. The LEAK LOKATOR LD3000 complies with the technical standards for tank tightness tests of U.S.E.P.A. Regulation 40 CFR 280. The LD3000 is capable of detecting a 0.1 GPH leak with a Pd > 99% and a Pfa = 5%. Tests indicated as PASS meet NFPA 329 criterion.TEST TYPE SYS NO. DISP NO. PUMP BRAND PUMP TYPE PRESSURE PSI TIME MIN VOLUME ML LEAK RATE GPH CONCLUSION PASS/FAIL PR 1 0 GILBARCO SUCTION 0.000 PASS [redacted] [redacted] Technical Review: SITE: 5 TRVL: Page 71 of 126
Full-size scan of page 71 (opens in a new tab)In the PDF: page 71 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 71 of 126 HUNTER ENVIRONMENTAL SERVICES, INC. 512 TOWNSHIP LINE ROAD, SUITE 230
CONTACT: [redacted] SITE CONTACT: [redacted] ADDRESS: 135 NEW RD.FINAL TEST REPORT PG. 2/2 DATE OF TEST: 3/19/91 LL473191.91 3837 BLUE BELL, PA 19422 215 540-5400 or 800 248-6837 CUSTOMER: NORTHEAST UTILITIES LOCATION: NORTHEAST UTILITIES
SYSTEM AND TANK INFORMATIONASSIGNED TESTING TEAM: LL47 PHONE: [redacted] LOCATION ID: 0 MADISON CT. 0
The coefficient of expansion of hydrocarbon based fuels (gasoline, diesel fuel, etc...) is determined by ASTM D-1250 data. The coefficient of expansion of other chemicals is obtained from published data or is provided by the customer.SYSTEM NUMBER PRODUCT NAME TANK NUMBER TOP OF STATION RISER " TOP OF HUNTER RISER " DROP TUBE TANK MATERIAL PUMP TYPE TYPE OF COVER AGE OF TANK YEARS NUMBER OF TANK RISERS NUMBER OF EXTRACTORS 1 REGULAR UNLEADED GASOLINE 1 123 152 NONE STEEL SUCTION CONCRETE 0 2 0 SYSTEM NUMBER PRODUCT NAME VAPOR RECOVERY SYSTEM STAGE I VAPOR RECOVERY SYSTEM STAGE II COEFFICIENT OF EXPANSION (1/F) DENSITY API TEMPERATURE DEGREES F 1 REGULAR UNLEADED GASOLINE NONE NONE 0.0006905 60.0 50.0
SYSTEM PREPARATION INFORMATIONWEATHER: OVERCAST TEMPERATURE (DEGREES F): 39 OTHER CONTRACTORS, OFFICIALS, AND CUSTOMER REPRESENTATIVES PRESENT NAME ORGANIZATION TITLE PHONE [redacted] NE.UTILITIES ENGINEER [redacted] TEST NO. SYS NO. START TIME STOP TIME RISERS DROP TUBE OVER FILL DRY BREAK BALL FLOAT DISPENSERS VENT PUMP CHECK VALVE LOC. OF LEVEL MEASUREMENTS 1 1 8:40 11:40 INSTALLED REMOVED NO PREP NONE IN OTHER Page 72 of 126
Full-size scan of page 72 (opens in a new tab)In the PDF: page 72 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 72 of 126 11-9 removal 18 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.FACILITY: Madison CODE: BGN LETTER NO: D 04955 TITLE/SUBJECT: UST Removal AGENCY: CDP SPECIAL INSTRUCTIONS: LETTER DATE:
COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C_____ or FORCOM # F_____ DUE DATE: ____ Number of Calendar days in Advance (+) or Late (-) of Due Date_____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91DS A PERSON SO DISCIPLINE LOC. EXT INIT. DATE COMMENTS X R.P. Klattenberg X Enviro. Svcs. B3F3 4628 Telecopy ✓ Cnt 102 R.C. Nichols Enviro. Audit B3F3 4645 W.C. Renfro Enviro. Prog. B3F3 4620 T.J. Butwill Civil Hydraulics N206 5403 D.R. Wade FH Programs Engng N226 5460 W.J. Kornacki FH Improv. Engng N226 3792 R.N. Smart FH Eng. & Const. N207 5362 X RHPershan X Legal E217 3175 Rlbp 10/2/91 Land Planning SBS N.J. Lanzalotta Prod. Opns. Svcs. W239 5657 Project Engineer Facility Mgr./Supt. X C.A. Edge X Fac. Opns. & Engng SBS 6750 Telecopy Cnt 103 P.C. Robotham Transportation 3333 6677 J. Barresi Supt. - CT&M 3333 6662 W.V. Reichelt Sys. Supt. - Fossil W239 5467 R.G. Chevalier Sys. Supt. - Hydro W239 5064 X JHSzymanski X Originator/Lead B3F3 3548 Telecopy 10-2-91 ✓ X CLKerlic X GEL Lead W218 3548 NRC ☐ Yes ☐ No X Supvsr - NL W218 R. Osella X Supvsr - GEL W218 5448 ev 10/7/91 OTHER DISTRIBUTION GEL CLERK INSTRUCTIONS X X Facilities File GEL Clerk W218 X ORIGINAL AND ___ COPIES X KBusick 3333 NOTARY REQUIRED ATTACHMENTS (X in "A" Column) FEE CHECK FEDERAL EXPRESS REGISTERED MAIL TELECOPY Page 73 of 126
Full-size scan of page 73 (opens in a new tab)In the PDF: page 73 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 73 of 126 OOT 2-91 WED 13:37 | GEN. FACIL. LICENSING | FAX NO. 2036556896 | P.02 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.FACILITY: Madison CODE: BGN LETTER NO: D 04955 TITLE/SUBJECT: UST Removal AGENCY: CDP SPECIAL INSTRUCTIONS: LETTER DATE:
COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C_____ or FORCOM # F_____ DUE DATE: ____ Number of Calendar days in Advance (+) or Late (-) of Due Date ____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91DS A PERSON SO DISCIPLINE LOC. EXT INIT. DATE COMMENTS R.P. Klattenberg X Enviro. Svcs. B3F3 4628 Telecopy ROK 12/3/91 R.C. Nichols Enviro. Audit B3F3 4645 W.C. Renfro Enviro. Prog. B3F3 4620 T.J. Butwill Civil Hydraulics N206 5403 D.R. Wade FH Programs Engng N226 5460 W.J. Kornacki FH Improv. Engng N226 3792 R.N. Smart FH Eng. & Const. N207 5362 RHPershon X Legal E217 3725 Land Planning SBS N.J. Lanzalotta Prod. Opns. Svcs. W239 5657 Project Engineer Facility Mgr./Supt. C.A. Edge X Fac. Opns. & Engng SBS 6750 Telecopy P.C. Robotham Transportation 3333 6677 J. Barresi Supt. - CT&M 3333 6662 W.V. Reichelt Sys. Supt. - Fossil W239 5467 R.G. Chevalier Sys. Supt. - Hydro W239 5064 X JHSzymanski X Originator/Lead B3F3 Telecopy HS ok 10-4-91 X CLKyler X GEL Lead W218 3540 Telecopy 10-2-91 X Supvsr - NL W218 NRC ☐ Yes ☐ No R. Osella X Supvsr - GEL W218 5448 OTHER DISTRIBUTION GEL CLERK INSTRUCTIONS X X Facilities File GEL Clerk W218 X ORIGINAL AND ___ COPIES X R Busick 3333 NOTARY REQUIRED ATTACHMENTS (X in "A" Column) FEE CHECK FEDERAL EXPRESS REGISTERED MAIL TELECOPY Page 74 of 126
Full-size scan of page 74 (opens in a new tab)In the PDF: page 74 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 74 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] October 8, 1991 D04955 UST Coordinator Department of Environmental Protection 165 Capitol Avenue Hartford, CT 06106 Reference: Letter and Notification (D03879), C. F. Sears to F. Wackt, dated October 16, 1990. Dear Sir or Madam: Madison Regional Service Center UST Removal Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P) and pursuant to 40 CFR 270.71(a), notifies you of CL&P's plan to remove three 550-gallon underground storage tanks (USTs) at its Madison Regional Service Center. The USTs are identified as Tanks A1, B2, and F6 in the referenced notification. Removal of the USTs will not be done for at least 30 days from the date of this letter. We will notify the town fire marshal once a removal date is set. If you have any questions, please call [redacted] NUSCO Generation and Environmental Licensing, at [redacted] Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] Vice PresidentPage 75 of 126
Full-size scan of page 75 (opens in a new tab)In the PDF: page 75 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 75 of 126 19 FHEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296, 3715 OR 5974.
SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.FACILITY: Madison Area Work Center CODE: BGN LETTER NO: D 03028 TITLE/SUBJECT: UST Release 20-Day Letter AGENCY: CDP SPECIAL INSTRUCTIONS: Must 90 Sept. 18, 1989 LETTER DATE: Sept. 18, 1989
COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C____ or FORCOM # F____ | DUE DATE: N/A Number of Calendar days in Advance (+) or Late (-) of Due Date____DS A PERSON SO DISCIPLINE LOC. EXT INIT. DATE COMMENTS X X CLKarlic X Originator/Lead W218 3740 CdlC 9-13-89 J.H. Gastler Gen. Env. Svcs. B3F3 4638 X X R.P. Klattenberg X Fac. Env. Svcs. B3F3 4628 Telecopy Letter Only Sent 9-13 R.C. Nichols Enviro. Audit B3F3 4645 T.J. Butwill Civil Hydraulics N206 5403 D.R. Wade FH Programs Engng N226 5460 W.J. Kornacki FH Improv. Engng N226 3792 X X JCStatstrom X Legal E217 5087 JCS 9/15/89 OK per Kanka comments R. de Brigard Land Planning SBS 6714 N.J. Lanzalotta Prod. Opns. Svcs. W239 5657 X X W. Haynack X EPD B3F3 4613 Telecopy Letter Only Sent 9-13 vacation X X J. Slatter X Fac Mgmt SBS Sent Sep. Copy vacation Project Engineer Facility Mgr./Supt. C.A. Edge Fac. Opns. & Engng SBS 6750 P.C. Robotham Transportation 3333 6677 J. Barresi Supt. - CT&M 3333 6662 W.V. Reichelt Sys. Supt. - Fossil W239 5467 R.G. Chevalier Sys. Supt. - Hydro W239 5064 CL Karlic X FHEL Lead W218 3740 CLK 9-18-89 as amended R. Osella X Supvsr - FHEL W218 5448 RO 9/18/89 OTHER DISTRIBUTION GFL CLERK INSTRUCTIONS X X Facilities File GFL Clerk W218 X ORIGINAL AND ___ COPIES X X P. Wilson NOTARY REQUIRED X ATTACHMENTS (X in "A" Column) FEE CHECK FEDERAL EXPRESS REGISTERED MAIL TELECOPY Commitment Number GFL Lead Discipline Lead Response Date DESCRIPTION ALL CORRESPONDENCE TO COPY TO NUCLEAR LICENSING NPDES PERMITTING AGENCIES: SUPERVISOR FOR FORWARDING TO USNRC REV. 2 1-03-89 Page 76 of 126
Full-size scan of page 76 (opens in a new tab)In the PDF: page 76 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company [REDACTED] d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 76 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 [redacted]CTICUT 06141-0270 Honorable Leslie Carothers, Commissioner Department of Environmental Protection 165 Capitol Avenue Hartford , Connecticut 06106 CERTIFICATION STATEMENT CATHODIC PROTECTION SYSTEMS AND MONITORING DEVICES I [redacted] certify that I am employed by the Northeast Utilities Service Company as Supervisor-Corrosion Control. I further certify that I supervised the installation of cathodic protection (C.P.) and C.P. monitoring devices completed on 26-Jan-87 , for the underground tank(s) registered on Connecticut State Form , EPHM-6 , as H8 , owned by the Connecticut Light and Power Company and located at 135 New Rd., Madison. To the best of my knowledge, such installation was carried out in accordance with the requirements of Section 22a-449(d)-1(e)(1)(D), Regulations of Connecticut State Agencies. [redacted] NACE Corrosion Specialist #1518Page 77 of 126
Full-size scan of page 77 (opens in a new tab)In the PDF: page 77 (opens in a new tab)
The scanned page Machine-read text
**The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 77 of 126 ** The following formulas may be used to determine the life expectancy of a given weight anode or to determine the anode weight necessary for desired life at known current outputs. L_m = 57.08 × w. / i ; L_z = 3824 × w / i L_m = life of magnesium anode, years L_z = life of zinc anode, years w = weight of anode, pounds i = milliampere output of anode In the above formulas the current efficiency of zinc is assumed to be 90% and for magnesium 50% of their theoretical output per pound based on Faraday's Law. Madison Regional Service Center CALCULATION OF ANODE LIFE EXPECTANCY TANK I.D. H8 8 MAGNESIUM ANODES AT 17 LBS. EACH = 136 LBS. ANODE CURRENT = 50 MILLIAMPERES L = 57.08 x 136 LBS = 155 YEARS 50 MILLIAMPERES **PROCEEDINGS of the Ninth Annual Ap[redacted]nd Corrosion Short Course. Edited by [redacted]**Page 78 of 126
Full-size scan of page 78 (opens in a new tab)In the PDF: page 78 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 78 of 126 HUNTER ENVIRONMENTAL SERVICES, INC. 1665 Lilburn Park Road St. Louis, MO 63146 4-567-4600 TEST RESULTS leak lokator LD 2000 DATE OF TEST 8/18/89 CONTRACT NUMBER CUSTOMER Conn Light & Power
TEST RESULTS SUMMARYLOCATION — IDENTIFICATION NUMBER NAME ADDRESS 135 new rd CITY Madison STATE ct.
OTHER INFORMATION PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSSYSTEM PRODUCT TANK SIZE GALLONS TANK SIZE DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION [redacted] LEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS #1 Unleaded 10,000 96"/ST 0" 140" -.016 Tight Full System Diesel 5,000 96"/ST 0" 142" -.020 Tight Full System #2 Unleaded 5,000 96"/ST 0" 142" +.003 Tight Full System
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSSYSTEM PRODUCT TYPE OF PUMP REMOTE TYPE OF PUMP SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT #1 Unleaded Tuthem 10-lbs 10-MIN 17CC's -.009 Tight Diesel Gilbarco no check valve in line n/A #2 Unleaded Wayne no check valve in line n/A SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) TIME CLOCK START TIME DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMPERATURE COMPENSATION Δ °F TEMPERATURE COMPENSATION CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N #1 Unleaded 1 140" 10:50 26 Min 1.20 -3.67 -.006 -2.60 -1.07 -.016 N Diesel 1 142 12:00 22 Min 1.40 -2.30 -.007 -1.02 -1.28 -.020 N #2 Unleaded 1 142 13:10 26 min 1.3 +1.07 -.004 -.868 +.202 +.003 N
As listed on the current system
Question(s) Answered 38 (The Connecticut Light and Power Company) Date Filed: 10/20/2026