Interrogatory responses
Answers to questions 38
Files5
RSR-038_Final.pdf
PDF · 146 KB · 7 pagesText searchable
Download RSR-038_Final.pdfRead the text of RSR-038_Final.pdf
RSR-038 Attachment 1 REDACTED.pdf
PDF · 4.6 MB · 19 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 1 REDACTED.pdfScanned pages and text of RSR-038 Attachment 1 REDACTED.pdf
RSR-038 Attachment 2 REDACTED.pdf
PDF · 798 KB · 1 pageText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 2 REDACTED.pdfScanned pages and text of RSR-038 Attachment 2 REDACTED.pdf
RSR-038 Attachment 3.pdf
PDF · 502 KB · 1 pageText searchable
Download RSR-038 Attachment 3.pdfRead the text of RSR-038 Attachment 3.pdf
RSR-038 Attachment 4 REDACTED.pdf
PDF · 51 MB · 126 pagesText read by machine from a scan; may contain errors, especially in numbers
Download RSR-038 Attachment 4 REDACTED.pdfScanned pages and text of RSR-038 Attachment 4 REDACTED.pdf
Scanned pages and machine-read text of RSR-038 Attachment 1 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 1 of 19 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] April 13, 1988 D01928 Mr. Ronald Corey, Fire Marshall City of Torrington 111 Water Street Torrington, Connecticut 06790 Reference: Letter and Notification, [redacted] o R. Corey, dated May 8, 1986. Dear Mr. Corey: Torrington Area Work Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for the Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Torrington Area Work Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the removal of all of the tanks (A1, B2, C3, D4) at the site. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted]. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] [redacted] Senior Vice President [redacted] By: C. F. Sears Vice President
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 2 of 19 Mr. Ronald Corey, Fire Marshall DO1928/Page 2 April 13, 1988 Enclosure cc: w/enclosure (Copy 1) Mr. Scott Deshefy Hazardous Material's Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Mr. Richard Ciasullo Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 3 of 19 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION | PG. 2 of 1 | SITE ID | FOR STATE AGENCY USE ONLY | A. SITE I.D. | B. DATE RCVD BY D E P | C. DATE ENTERED | D. GRID COORDINATES X Y | E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM-6 NEW 10/85 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
SECTION C 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [X] YES 21. COMMENTS: SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.4. LOCATION OF FACILITY SITE NAME: Torrington Area Work Center NO. AND STREET: 174 Franklin Street NEAREST INTERSECTING STREET: Horwinton Ave. CITY OR TOWN: Torrington STATE: CT 5. LATITUDE: 41° 48' 00" LONGITUDE: 73° 06' 55" 5. BUSINESS NAME AND 6. MAILING ADDRESS NAME: The Connecticut Light + Power Co. (CL4P) NO. AND STREET: P O Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 06141-0270 7. FACILITY OWNER NAME: CL&P NO. AND STREET: Same as Above CITY OR TOWN STATE ZIP CODE 8. TYPE OF OWNER PRIVATE (checked) STATE MUNICIPAL FEDERAL (G.S.A. No.) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 174 Franklin Street CITY OR TOWN: Torrington STATE: CT ZIP CODE: 06790 TELEPHONE: 1203 482-4471 10. TANK ID 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. LIFE EXPECTANCY (in years) 12a. TOTAL CAPACITY (Gals.) IN USE ABANDONED IN PLACE 12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known) 15. CONSTRUCTION MATERIALS STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) c. INTERNAL UNLINED b. EXTERNAL UNLINED CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 16. PROTECTION 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (from list A/B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (if "YES", enter DATE and attach results; if "NO", enter "NO") Example 5/75 30 5000 X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X E 7 7/60 U - A1 12/78 15 10,000 X 4/88 X Regular Gasoline X X E 7E 12/78 O 3-15-84 B2 1/64 15 4,000 X 3/88 X Diesel Fuel X X E 7E 1/64 O 3-15-84 C3 1/64 15 4,000 X 3/88 X Unleaded Gasoline X X E 7E 1/64 O 3-15-84 D4 1/60 15 500 X 3/88 X Waste Oil X X E 7E 1/60 U NO
22c. NAME (type or print) [redacted] 22d. OFFICIAL TITLE | Vice President / Senior Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 0610622a. SIGNATURE X [redacted] 22b. DATE SIGNED 13 April 1988 
The scanned page Machine-read text
REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 4 of 19 CONN LIGHT & POWER CO. NORTHEAST UTILITIES WORK ORDER SKETCH SHEET
SKETCH INDICATE NORTH AND NAME STREETS Not To Scale B2 A1 21' 140' 159' 177' 44' 275' 255' D4 C3 GARAGE TRANSMISSION TORRINGTON SERVICE BUILDING HARWINTON SCHIBI ST. AVE. OP418? REV. 10-82 DEST. SAME AS ATT. REC. DRAWN BY | TELEPHONE EXT.DISTRICT / REGION TOWN DATE MAP NO. WORK ORDER NO. ACTV. SHEET OF TORRINGTON / WESTERN TORRINGTON 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 5 of 19 REDACTED TO: File FROM: John Szymanski [signature] April 14, 1988 SUBJECT: Torrington AWC Tank removals were conducted at the Torrington AWC during the months of March and April 1988. o During March 1988: One (1) 4000 gallon unleaded gasoline tank and One (1) 500 gallon oil tank were removed; no problems o On March 30, 1988: Notified that (1) 4000 gallon diesel tank was removed with heavy rusting and several apparent holes the size of dimes. o On March 30, 1988: Examined site and took three (3) samples from excavation hole and one (1) sample from diesel tank to have material analyzed and identified by LAB per request by DEP Field Inspector, Richard Ciasullo. o On March 31, 1988: Samples dropped off for analyzing and identification at Souther-Newlands Laboratory. o On April 4, 1988: Souther Newland Laboratory called EPD office to report on lab findings. - Sample from diesel tank identified as diesel fuel - The three (3) samples from the excavation hole all had the same characteristic profiles, but it didn't match that of gasoline or diesel fuel and that it would take two to three weeks to identify samples from the excavation hole. o On Aril 4, 1988: Notified R. Robinson of the DEP Clean Water Group of the test results and asked for permission to continue tank installation construction after film cleaned off top of water and remainder of gray colored gravel removed from hole. Mr. Robinson gave approval to continue construction if I inspected site and assured this was done. o On April 6, 1988: NUSCO construction removed film from water and lowered water table by sucking out 3200 gallons of contaminated water which was hauled off site as contaminated waste water. Removed the remainder of gray contaminated gravel from excavation hole. o On April 6, 1988 after water table lowered gasoline film and strong fumes entered the excavation hole. The fire marshal was notified, who requested DEP to inspect the hole. Concern was generated regarding 10,000 gallon unleaded gasoline tank in the same vicinity where gas fumes and film were found. Construction stopped. o On April 7, 1988: DEP Field Inspector Richard Ciasullo and
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 6 of 19 Torrington Fire Marshal Ron Corey arrived on site and gave us two alternatives: 1. Test tank full of product and be ready to remove it immediately if tank leaks; 2. Remove 10,000 gallon unleaded tank. o April 7, 1988: Discussions were held between Area Superintendent Walt Wadman, Ken Busick, Frank Melluzzo, Bud Meyer, John Betz, Jack Farrel and John Szymanski to discuss options and make decision as to disposition of 10,000 gallon gasoline tank. Final consensus was to remove tank based on presence of gasoline odor and fumes in area, water level in tank raised when emptied of product, bottom ash found in vicinity of tank, tank had been unprotected for 10 years, the older unprotected tank 4000 diesel came out of ground looking like swiss cheese. o April 7, 1988: Removed 10,000 gallon unleaded gasoline tank, some heavy rusting and pitting visible on tank but there was no apparent holes. Backfill around tank was improper per today's installation standards (very large boulders, large gravel and some sand) there were no hold down straps on tank, and bottom ash in close proximity to tank. Wet lines were heavily rusted in one large area.
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 7 of 19 REDACTED Distribution: [redacted]Claims and Insurance [redacted]s. and Test Department [redacted]Regional Operations - WMECO [redacted]struction [redacted]HP [redacted]rans. SS and Mtce. [redacted] Trans. Bldg. Eng. Design [redacted]nsportation [redacted] EPD [redacted]ores [redacted] EPD [redacted]cilities Management [redacted] Legal [redacted] Nuclear Prod. [redacted]en. Fac. Lic. Dept. bsl cc: [redacted]
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 8 of 19 TORRINGTON AUG / CT Bemis / Laura Lionts leak lokator hunter ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] TEST RESULTS DATE OF TEST | 07-6-85 CONTRACT NUMBER
TEST RESULTS SUMMARYCUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER NAME ADDRESS 178 Franklin Drive CITY Torrington STATE Conn LEAK LOKATOR USE ONLY CONCL. CODE
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS TEST TANK SYS II No Lead Tank #I 4000 64/37 1 1/2" 106" .039 Tight II No Lead Tank #II 4000 64/37 1 1/2" 95" .038 Tight VII Regular Lead 10000 96/3T 1 1/2" 113" .038 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE TYPE OF PUMP SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT II No Lead Tank I > ✓ DL Pressure test test X II No Lead Tank II > ✓ 170 Pressure test test X III Regular Leaded > Pump ✓ Side [illegible] [illegible] X X Tight NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) CLOCK START DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMP COMP Δ°F TEMP COMP CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I No Lead Tank I 1 106" 9:45 31 min .39 +25.95 +.161 +33.80 -1.85 -.039 N II No Lead Tank II 1 95" 7:52 31 min .47 +2.82 +.636 +6.37 -2.44 -.038 N III Regular Leaded 1 142" 11:46 20 min .35 +21.47 +.655 23.88 -2.41 -.038 N 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 9 of 19 REDACTED ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] Bemis | TORRINGTON AWG / CT Laura [illegible] leak lokator TEST RESULTS DATE OF TEST | 03-6-8? CONTRACT NUMBER CUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER
TEST RESULTS SUMMARYADDRESS 178 Franklin Drive NAME CITY Torrington STATE Con
OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES ALR GPH CONCLUSION RECOMMENDATIONS LEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS I NO LEAD TANK I 4500 64.37 1 1/2" 166" -.029 Tight II NO LEAD TANK II 4500 64.37 1 1/2" 95" -.038 Tight III REGULAR LEADED 10000 96 x T 1 1/2" 115" -.026 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT I NO LEAD TANK I ✓ DO DO [illegible] test X II NO LEAD TANK II ✓ test X III REGULAR LEADED ✓ ✓ 110 Due X III REGULAR LEADED ✓ Pump ✓ [illegible] [illegible] [illegible] [illegible] Tight
* LEVEL – INCHES FROM TANK BOTTOM TO TEST LEVEL ALR – ABSOLUTE LEAK RATE (MEASURED LEAK RATE – TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION – NFPA 329 CRITERION OF ± 0.05 GPH IS USED TO CERTIFY TIGHTNESS CERTIFICATION This is to certify that the above described tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated as tight meet the criterion established by the National Fire Protection Association Pamphlet 329 for Precision Testing.NO. SYSTEM PRODUCT TEST NO. TEST LEVEL (INCHES) TIME CLOCK START TIME DURATION HRS.-MIN. LEAK RATE CC/DIV LEAK RATE CC/MIN TEMPERATURE COMPENSATION Δ°F TEMPERATURE COMPENSATION CC/MIN ABSOLUTE LEAK RATE CC/MIN ABSOLUTE LEAK RATE GPH CHECK TEST Y or N I NO LEAD TANK I 1 166" 9:45 31 min .39 +25.95 +.141 +27.82 -1.85 -.029 N II NO LEAD TANK II 1 95" 9:52 35 min 4.17 12.08 +.036 16.37 -2.44 -.038 N III REGULAR LEADED 1 114" 9:46 30 min -.37 +21.17 +.255 23.66 -2.41 -.038 N TESTS CONDUCTED BY CERTIFIED BY TEST VAN NO. [illegible] SIGNATURE [illegible] TANK TESTING SPECIALIST [illegible] NAME [illegible] DATE [illegible] TANK TESTING SPECIALIST [illegible] TITLE [illegible] 
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 10 of 19 TANK AND LOCATION DATA DATE: 03-6-85
SCHEMATIC: Building PUMP NO LEAD II 4000gal 64" NO LEAD II 4000gal 64" NO LEAD PUMP VENT Regular PUMPS VENT Regular LEADED 10000gal 96" BuildingCUSTOMER: Northeast Utilities CITY: Torrington I.D. # STATE: Conn WEATHER TIME TEMPERATURE COMMENTS BEFORE TEST – AFTER TEST –
VAPOR RECOVERY TYPE VENT CONFIGURATION P-V VENT VALVE TYPEPRODUCT/TANK NO. NO LEAD I NO LEAD II Regular BEFORE DELIVERY LEVEL Fill Gauge Fill Gauge Fill Gauge Fill Gauge Fill Gauge LEVEL Full GALLONS WATER 1½" 1½" 1½" TOP OF RISER 97 96 101 132 GRADE 160 163 162 137 DROP TUBE AL AL AL CAPACITY, GALLONS 4000 4000 10000 DIAMETER, INCHES 64 64 64 MATERIAL STEEL STEEL STEEL PUMP TYPE Gasboy [illegible] Bennett TYPE OF COVER TAN TAN TAN AGE OF TANK UK UK UK SIPHON NO NO NO TANK OPENINGS 1-4" 1-2" 1-4" 1-2" 1-4" EXTRACTORS NO NO NO
ADDITIONAL CHARGES: (pumpovers, overtime, etc.) [illegible] [illegible] *Data obtained from ☐ Station ☐ LL Charts ☐ Other ______REPLACEMENT PARTS: PART # DESCRIPTION QUANTITY PRICE #701 [illegible] 1 [illegible] #124 [illegible] 1 [illegible] # 6" Quick Tite 2-gauge (wire) 1 [illegible]
Scanned pages and machine-read text of RSR-038 Attachment 2 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 2 REDACTED Page 1 of 1 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION
STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D.2. PG. of 1 1
SECTION A/B3. FOR STATE AGENCY USE ONLY A. SITE I.D. B. DATE RCVD BY D.E.P. C. DATE ENTERED D. GRID COORDINATES X ___ Y ___ E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
[redacted] SECTION C4. LOCATION OF FACILITY SITE NAME: East Hampton Service Center NO. AND STREET: 22 East High Street NEAREST INTERSECTING STREET: Route 2 CITY OR TOWN: East Hampton STATE: CT 5. LATITUDE: 41° 34' 56" LONGITUDE: 72° 30' 14" 6. BUSINESS NAME AND MAILING ADDRESS NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 7. FACILITY OWNER NAME: The Connecticut Light & Power Company NO. AND STREET: P.O. Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE: 061410270 8. TYPE OF OWNER X PRIVATE STATE MUNICIPAL FEDERAL (G.S.A. No. ___) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET: 22 East High Street CITY OR TOWN: East Hampton STATE: CT ZIP CODE: 06424
20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? X YES 21. COMMENTS: 16b coal tar epoxy. Tanks B2, D4, E5 & F6 budgeted for cathodic protection in 1986. A1 is also for [illegible] [illegible] SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.10. TANK ID. 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. TANK LIFE EXPECTANCY (# of years) 12a. TOTAL CAPACITY (Gals.) 12b. STATUS: IN USE ABANDONED IN PLACE EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No. if known) 15. CONSTRUCTION MATERIALS: STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) 16. PROTECTION a. INTERNAL: LINED UNLINED; b. EXTERNAL: CATHODIC PROTECTION COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION PROTECTION (See list B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (If "YES," enter DATE and attach results. If "NO," enter "NO") Example 5/75 30 5000 X X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X X E 7 7/60 U — A1 /72 15 275 X X X X X H 7 /72 H 092584 B2 /72 15 10000 X X X X 7 /72 O 092684 (10-14-86 / 092684 struck through) C3 '30 30 10000 X 0 11/84 X X 8 /80 O 092684 D4 '72 15 275 X X X X 7 /72 U 092584 E5 ,72 15 550 X X X X 7 /72 U 092884 P6 ,72 15 550 X X X X 7 /72 U 092884
COPY 422a. SIGNATURE X [redacted] 22b. DATE SIGNED 5/5/86 22c. NAME (Type or Print) [redacted] 22d. OFFICIAL TITLE (of owner or authorized representative) Senior Vice President
Text of RSR-038 Attachment 3.pdf
Extracted from the file · 1 page · 146 characters
Scanned pages and machine-read text of RSR-038 Attachment 4 REDACTED.pdf

The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 8 of 126 REDACTED MADISON A.W.C/C 3/18 Bernie Laura Zionts HUNTER ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] leak lokator LD 2000 TEST RESULTS
TEST RESULTS SUMMARYDATE OF TEST [illegible] CONTRACT NUMBER CUSTOMER [illegible] LOCATION — IDENTIFICATION NUMBER [illegible] NAME ADDRESS [illegible] CITY Madison STATE CT
OTHER INFORMATION FINAL REPORT PRODUCT LINES — HYDROSTATIC PRESSURE TEST RESULTSNO. SYSTEM PRODUCT TANK SIZE GALLONS TANK SIZE DIA/MATL WATER INCHES LEAK LOKATOR RESULTS LEVEL INCHES LEAK LOKATOR RESULTS AIR GPH LEAK LOKATOR RESULTS CONCLUSION RECOMMENDATIONS LEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS I [illegible] 5,000 [illegible] 0" 140" .032 Tight I [illegible] 5,000 [illegible] 0" 1.5" .040 Tight I [illegible] 10,000 [illegible] 0" 120" .037 Tight
NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTSNO. SYSTEM PRODUCT TYPE OF PUMP REMOTE TYPE OF PUMP SUCTION # APPLIED MINUTES APPLIED PRODUCT LOSS CC'S PRODUCT LOSS GPH CONCLUSION/RESULT I [illegible] ✓ [illegible] [illegible] x x Tight I [illegible] ✓ [illegible] [illegible] x x Tight I [illegible] ✓ [illegible] [illegible] x x Tight 
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 9 of 126 REDACTED [illegible] (handwritten, top center) [illegible] (handwritten, top center) 3/1? (handwritten, top right) Page 2 TANK AND LOCATION DATA DATE: 3-14-85
SCHEMATIC: TANK #2 UNLEADED 10000 gal 96" | ③ ④Fill Pump #4 Pump #3 TANK #1 UNLEADED 3000 gal 96" | Fill ④ | Pump #1 | Booth | Pump #2 | ④Fill | TANK #3 UNLEADED 3000 gal 96" VENTS BuildingCUSTOMER: Northeast Utilities CITY: Madison I.D. # STATE: Conn WEATHER TIME TEMPERATURE COMMENTS BEFORE TEST – TER TEST – PRODUCT/TANK NO. UNLEADED TANK #1 UNLEADED TANK #2 UNLEADED TANK #3 BEFORE DELIVERY LEVEL Fill Gauge Fill Gauge Fill Gauge Fill Gauge Fill Gauge GALLONS X X WATER 0" X 0" X 0" 0" TOP OF RISER 140 141 117 118 GRADE 142 1/2 147 134 136 DROP TUBE AL AL AL Page 10 of 126
Full-size scan of page 10 (opens in a new tab)In the PDF: page 10 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 10 of 126 PUMP METER CALIBRATION
RJT - 2/85 [no text]DATE: 3-14-85 CUSTOMER: northEAST utilities LOCATION: madison service center (New Rd) madison ct PRODUCT ID unleaded (TANK #1) PUMP INFO/SERIAL NO. 0324325 A3 Serial # INITIAL TEST READING + -1 cubic inches CORRECT TO + cubic inches PRODUCT ID unleaded (TANK #2) PUMP INFO/SERIAL NO. 0324327 A3 INITIAL TEST READING + +2 cubic inches CORRECT TO + cubic inches PRODUCT ID unleaded (TANK #3) PUMP INFO/SERIAL NO. (Left side) side 1 Serial # KH23228 INITIAL TEST READING + +0 1/2 cubic inches CORRECT TO + cubic inches PRODUCT ID unleaded (TANK #3) PUMP INFO/SERIAL NO. (Right side) side 2 Serial # KH23228 INITIAL TEST READING + -1 cubic inches CORRECT TO + cubic inches LL VAN # 6 TEAM MANAGER [redacted] Page 11 of 126
Full-size scan of page 11 (opens in a new tab)In the PDF: page 11 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 11 of 126 STATE OF CONNECTICUT Department of Environmental Protection RGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 EPHM- 6 NEW 10/85 3.
: TYPE. ALL THREE COPIES MUST BE LEGIBLE! ONS FOR FILING NOTIFICATION before completing form. X ____ Y ____FOR STATE AGENCY USE ONLY A. SITE I.D. B. DATE RCVD BY D.E.P C. DATE ENTERED D. GRID COORDINATES E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
FEDERAL (G.S.A. No. ____)STREET: New Road NEAREST INTERSECTING STREET: Duck Hole Road CITY OR TOWN: Madison STATE: CT 5.LATITUDE 41° 17' 31" LONGITUDE 72° 34' 36" STREET: Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE 061410270 TELEPHONE 203 665-5000 STREET: Box 270 CITY OR TOWN: Hartford STATE: CT ZIP CODE 061410270 TELEPHONE 203 665-5000
22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.STREET: New Road CITY OR TOWN: Madison STATE: CT ZIP CODE 06443 TELEPHONE 203 245-7313 14. CONTENTS- CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., If known) 15. CONSTRUCTION MATERIALS 16.PROTECTION 17. INTEGRAL PIPING SYSTEM 18. MONITORING SYSTEM 19. FAILURE DETERMINATION CONDUCTED? Heating fuel #2 X X H 5 5/75 U NO 1,1,1,- Trichloroethane CAS #79016 X X E 7 7/60 U — Hydraulic Fluid X X X H 7 /73 R NO Motor Oil X X X H 7 /73 R NO Unleaded Gasoline X X X A 8 /73 O 031485 Diesel Fuel X X X A 8 /73 O 031485 Unleaded Gasoline X X X A 8 /80 O 031485 Waste Oil - Empty X X X H 7 /73 R NO HYDRAULIC OIL X X X F /73 R NO
1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 0610622a. SIGNATURE X 22b. DATE SIGNED 22c. NAME (Type or Print) 22d. OFFICIAL TITLE (of owner or authorized representative). Page 12 of 126
Full-size scan of page 12 (opens in a new tab)In the PDF: page 12 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 12 of 126 REDACTED
LV-6 / E.O.UE. Utilities SUMMARY OF TEST RESULTS LOCATION: Madison Svc. Ctr DATE: 3/14/85 CUSTOMER: Bernie Madison, Ct. COPIES TO: Laura Zents
ADDITIONAL COMMENTS: OTHER CHARGES: (i.e., pumpovers, overtime, parts, etc.) EL - INCHES FROM TANK BOTTOM TO TEST LEVEL I - ABSOLUTE LEAK RATE (MEASURED LEAK RATE - TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CLUSION - NFPA 329 STANDARD OF +0.05 GPH IS USED TO CERTIFY TIGHTNESS. PRELIMINARY REPORT 8+1[illegible] TANK SIZE GALLONS DIAMETER INCHES WATER INCHES PUMP DISCHARGE PRESSURE TEST LEAK LOKATOR RESULTS LEVEL INCHES GPH CONCLUSION COMMENTS - RECOMMENDATIONS [illegible] 5,000 96 none 9/10 140" .033 tight Pump = -1 cubic inches upon arrival [illegible] 5,000 96 none 8/10 150" .040 tight pump = +2 cubic inches upon arrival [illegible] 10,000 96 none 8/10 130" .027 tight Lt. pump = +2½ cubic inches upon arrival / Rt. pump = -1 cubic inches upon arrival Page 13 of 126
Full-size scan of page 13 (opens in a new tab)In the PDF: page 13 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 13 of 126 3 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [phone removed] April 14, 1988 D01900 Mr. Arthur W. Cunningham, Fire Marshall Town Hall 8 Meeting House Lane Madison, CT 06443 Reference: Letter, J. F. Opeka to A. Cunningham, dated May 8, 1986. Dear Mr. Cunningham: Madison Regional Service Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Madison Regional Service Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the cathodic protection of the tanks and discovery of another tank on site not previously notified for. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted] Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] Senior Vice President Enclosure cc: w/Enclosure (Copy 1) Mr. Scott Deshefy Hazardous Materials Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106Page 14 of 126
Full-size scan of page 14 (opens in a new tab)In the PDF: page 14 (opens in a new tab)
The scanned page Machine-read text
**Header (top right):** The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 14 of 126 REDACTED
SITE I.D. STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM- 6 NEW 10/85UNDERGROUND STORAGE FACILITY NOTIFICATION PG. of 2. 1 1
1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.)3. FOR STATE AGENCY USE ONLY A. SITE I.D. B. DATE RCVD BY D.E.P C. DATE ENTERED D. GRID COORDINATES E. DOES FACILITY MEET NEW REQUIREMENTS? X Y YES NO
[redacted]4. LOCATION OF FACILITY SITE NAME NO. AND STREET NEAREST INTERSECTING STREET CITY OR TOWN STATE 5. LATITUDE LONGITUDE Madison Regional Service Center 135 New Road Dock Hole Road Madison CT 41° 17' 31" 72° 34' 36" 6. BUSINESS NAME AND MAILING ADDRESS NAME NO. AND STREET CITY OR TOWN STATE ZIP CODE The Connecticut Light + Power Co (CL&P) P.O. Box 270 Hartford CT 06141-0270
20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? ☐ YES 21. COMMENTS: N.B. Coat for epoxy G7 is knitted 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted. [redacted]7. FACILITY OWNER NAME NO. AND STREET CITY OR TOWN STATE ZIP CODE CL&P Same as Above 8. TYPE OF OWNER PRIVATE STATE MUNICIPAL FEDERAL (G.S.A. No. ____) 9. OPERATOR/CONTACT PERSON [redacted] NO. AND STREET CITY OR TOWN STATE ZIP CODE TELEPHONE 135 New Road Madison CT 06443 [phone removed] 10. TANK ID 11a. DATE OF INSTALLATION (Mo./Yr.) 11b. LIFE EXPECTANCY (# of years) 12a. TOTAL CAPACITY (Gals.) IN USE ABANDONED IN PLACE 12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.) REMOVED DATE TANK LAST USED (Mo./Yr.) 13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCT CHEMICAL LIQUID 14. CONTENTS- CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known) 15. CONSTRUCTION MATERIALS STEEL FIBERGLASS REINFORCED PLASTIC OTHER (Specify from list A) UNLINED UNLINED 16. PROTECTION a. INTERNAL CATHODIC PROTECTION b. EXTERNAL COATED/WRAPPED CATHODIC PROTECTION OTHER (Specify from list B) 17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (See list A&B) b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.) 18. MONITORING SYSTEM (Specify type from list B) 19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results). (If "NO", enter "NO") Example 5/75 30 5000 X X X X H 5 5/75 U NO Example 7/60 - 8000 X 8/78 X X X E 7 7/60 U - A1 /73 30 550 X X X X X H 7 /73 R NO B2 /73 50 550 X X X X X H 7 /73 R NO C3 /73 30 3000 X X X X X A 8 /73 0 3-14-85 D4 /73 30 3000 X X X X X A 8 /73 O 3-14-85 E5 /80 30 10000 X X X X X A 8 /80 O 3-14-85 F6 /73 30 550 X X X X X H 7 /73 R NO G7 /73 30 170 X X X X X F 7 /73 R NO
COPY 3: RETAIN FOR YOUR RECORDS22b. DATE SIGNED 4-14-88 22d. OFFICIAL TITLE (of owner or authorized representative) Senior Vice President Page 15 of 126
Full-size scan of page 15 (opens in a new tab)In the PDF: page 15 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 15 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [phone removed] Honorable Leslie Carothers, Commissioner Department of Environmental Protection 165 Capitol Avenue Hartford , Connecticut 06106 CERTIFICATION STATEMENT CATHODIC PROTECTION SYSTEMS AND MONITORING DEVICES I, [redacted] certify that I am employed by the Northeast Utilities Service Company as Supervisor-Corrosion Control. I further certify that I supervised the installation of cathodic protection and monitoring devices completed on 26-Oct-87 , for the underground tank(s) registered on Connecticut State Form , EPHM-6 , as A1,B2,C3,D4 , owned by the Connecticut Light and Power Company and located at 135 New Rd., Madison. To the best of my knowledge, such installation was carried out in accordance with the requirements of Section 22a-449(d)-1(e)(1)(D), Regulations of Connecticut State Agencies. [redacted] NACE Corrosion Specialist #1518Page 16 of 126
Full-size scan of page 16 (opens in a new tab)In the PDF: page 16 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 16 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [phone removed] Honorable Leslie Carothers, Commissioner Department of Environmental Protection 165 Capitol Avenue Hartford , Connecticut 06106 CERTIFICATION STATEMENT CATHODIC PROTECTION SYSTEMS AND MONITORING DEVICES I, [redacted], certify that I am employed by the Northeast Utilities Service Company as Supervisor-Corrosion Control. I further certify that I supervised the installation of cathodic protection and monitoring devices completed on 26-Oct-87 , for the underground tank(s) registered on Connecticut State Form , EPHM-6 , as E5,F6,G7 , owned by the Connecticut Light and Power Company and located at 135 New Rd., Madison. To the best of my knowledge, such installation was carried out in accordance with the requirements of Section 22a-449(d)-1(e)(1)(D), Regulations of Connecticut State Agencies. [redacted] NACE Corrosion Specialist #1518Page 17 of 126
Full-size scan of page 17 (opens in a new tab)In the PDF: page 17 (opens in a new tab)
The scanned page Machine-read text
The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 17 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [phone removed] August 3, 1988 D02069 Mr. G. Scott Deshefy PCB - Toxics/UST Programs Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Dear Mr. Deshefy: Underground Storage Tanks - Certification Statements Cathodic Protection and Monitoring Devices Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits Certification Statements for the installation of cathodic protection systems and monitoring devices for underground tank systems at 27 CL&P facilities. These facilities are listed in Enclosure 1. An in-house review of NUSCO files showed that while the majority of the protective devices had been installed in 1987 and 1988 and that these installations are noted on the tank registrations, certifications had not been sent to you. NUSCO is rectifying this oversight with this submittal. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted] Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] E. J. Mroczka Senior Vice President Enclosures
As listed on the current system
Question(s) Answered 38 (The Connecticut Light and Power Company) Date Filed: 10/20/2026