Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Interrogatory responses

Answers to questions 38

Files5

Words on different pages
Every word of Eversource rate increase is in the text below, but not all on one page. Pages with any of them are listed and highlighted. Clear highlighting
Words on different pages

Scanned pages and machine-read text of RSR-038 Attachment 1 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 1 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 1 of 19 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] April 13, 1988 D01928 Mr. Ronald Corey, Fire Marshall City of Torrington 111 Water Street Torrington, Connecticut 06790 Reference: Letter and Notification, [redacted] o R. Corey, dated May 8, 1986. Dear Mr. Corey: Torrington Area Work Center Notification of Underground Storage Tanks Northeast Utilities Service Company (NUSCO), as agent for the Connecticut Light and Power Company (CL&P), submits an amended Copy No. 2 of Notification Form EPHM-6 for underground storage tanks at CL&P's Torrington Area Work Center. The form submitted to you on May 8, 1986 (Referenced) has been amended to reflect the removal of all of the tanks (A1, B2, C3, D4) at the site. If you have any questions, please call [redacted] NUSCO Generation Facilities Licensing, at [redacted]. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company [redacted] [redacted] Senior Vice President [redacted] By: C. F. Sears Vice President
  2. Scan of page 2 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 2 of 19 Mr. Ronald Corey, Fire Marshall DO1928/Page 2 April 13, 1988 Enclosure cc: w/enclosure (Copy 1) Mr. Scott Deshefy Hazardous Material's Management Unit Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106 Mr. Richard Ciasullo Department of Environmental Protection 165 Capitol Avenue Hartford, Connecticut 06106
  3. Scan of page 3 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 3 of 19 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION | PG. 2 of 1 | SITE ID | FOR STATE AGENCY USE ONLY | A. SITE I.D. | B. DATE RCVD BY D E P | C. DATE ENTERED | D. GRID COORDINATES X Y | E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. EPHM-6 NEW 10/85 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
    4. LOCATION OF FACILITYSITE NAME: Torrington Area Work CenterNO. AND STREET: 174 Franklin StreetNEAREST INTERSECTING STREET: Horwinton Ave.CITY OR TOWN: TorringtonSTATE: CT5. LATITUDE: 41° 48' 00"LONGITUDE: 73° 06' 55"
    5. BUSINESS NAME AND 6. MAILING ADDRESSNAME: The Connecticut Light + Power Co. (CL4P)NO. AND STREET: P O Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 06141-0270
    7. FACILITY OWNERNAME: CL&PNO. AND STREET: Same as AboveCITY OR TOWNSTATEZIP CODE
    8. TYPE OF OWNERPRIVATE (checked)STATEMUNICIPALFEDERAL (G.S.A. No.)
    9. OPERATOR/CONTACT PERSON[redacted]NO. AND STREET: 174 Franklin StreetCITY OR TOWN: TorringtonSTATE: CTZIP CODE: 06790TELEPHONE: 1203 482-4471
    10. TANK ID11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (in years)12a. TOTAL CAPACITY (Gals.)IN USEABANDONED IN PLACE12b. STATUS EST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS OIL/PETROLEUM PRODUCTCHEMICAL LIQUID14. CONTENTS CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)c. INTERNAL UNLINEDb. EXTERNAL UNLINEDCATHODIC PROTECTIONCOATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list B)16. PROTECTION17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION AND PROTECTION (from list A/B)b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (if "YES", enter DATE and attach results; if "NO", enter "NO")
    Example5/75305000XXXH55/75UNO
    Example7/60-8000X8/78XXE77/60U-
    A112/781510,000X4/88XRegular GasolineXXE7E12/78O3-15-84
    B21/64154,000X3/88XDiesel FuelXXE7E1/64O3-15-84
    C31/64154,000X3/88XUnleaded GasolineXXE7E1/64O3-15-84
    D41/6015500X3/88XWaste OilXXE7E1/60UNO
    SECTION C 20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? [X] YES 21. COMMENTS: SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.
    22a. SIGNATUREX [redacted]
    22b. DATE SIGNED13 April 1988
    22c. NAME (type or print) [redacted] 22d. OFFICIAL TITLE | Vice President / Senior Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 06106
  4. Scan of page 4 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 4 of 19 CONN LIGHT & POWER CO. NORTHEAST UTILITIES WORK ORDER SKETCH SHEET
    DISTRICT / REGIONTOWNDATEMAP NO.WORK ORDER NO.ACTV.SHEETOF
    TORRINGTON / WESTERNTORRINGTON
    SKETCH INDICATE NORTH AND NAME STREETS Not To Scale B2 A1 21' 140' 159' 177' 44' 275' 255' D4 C3 GARAGE TRANSMISSION TORRINGTON SERVICE BUILDING HARWINTON SCHIBI ST. AVE. OP418? REV. 10-82 DEST. SAME AS ATT. REC. DRAWN BY | TELEPHONE EXT.
  5. Scan of page 5 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 5 of 19 REDACTED TO: File FROM: John Szymanski [signature] April 14, 1988 SUBJECT: Torrington AWC Tank removals were conducted at the Torrington AWC during the months of March and April 1988. o During March 1988: One (1) 4000 gallon unleaded gasoline tank and One (1) 500 gallon oil tank were removed; no problems o On March 30, 1988: Notified that (1) 4000 gallon diesel tank was removed with heavy rusting and several apparent holes the size of dimes. o On March 30, 1988: Examined site and took three (3) samples from excavation hole and one (1) sample from diesel tank to have material analyzed and identified by LAB per request by DEP Field Inspector, Richard Ciasullo. o On March 31, 1988: Samples dropped off for analyzing and identification at Souther-Newlands Laboratory. o On April 4, 1988: Souther Newland Laboratory called EPD office to report on lab findings. - Sample from diesel tank identified as diesel fuel - The three (3) samples from the excavation hole all had the same characteristic profiles, but it didn't match that of gasoline or diesel fuel and that it would take two to three weeks to identify samples from the excavation hole. o On Aril 4, 1988: Notified R. Robinson of the DEP Clean Water Group of the test results and asked for permission to continue tank installation construction after film cleaned off top of water and remainder of gray colored gravel removed from hole. Mr. Robinson gave approval to continue construction if I inspected site and assured this was done. o On April 6, 1988: NUSCO construction removed film from water and lowered water table by sucking out 3200 gallons of contaminated water which was hauled off site as contaminated waste water. Removed the remainder of gray contaminated gravel from excavation hole. o On April 6, 1988 after water table lowered gasoline film and strong fumes entered the excavation hole. The fire marshal was notified, who requested DEP to inspect the hole. Concern was generated regarding 10,000 gallon unleaded gasoline tank in the same vicinity where gas fumes and film were found. Construction stopped. o On April 7, 1988: DEP Field Inspector Richard Ciasullo and
  6. Scan of page 6 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 6 of 19 Torrington Fire Marshal Ron Corey arrived on site and gave us two alternatives: 1. Test tank full of product and be ready to remove it immediately if tank leaks; 2. Remove 10,000 gallon unleaded tank. o April 7, 1988: Discussions were held between Area Superintendent Walt Wadman, Ken Busick, Frank Melluzzo, Bud Meyer, John Betz, Jack Farrel and John Szymanski to discuss options and make decision as to disposition of 10,000 gallon gasoline tank. Final consensus was to remove tank based on presence of gasoline odor and fumes in area, water level in tank raised when emptied of product, bottom ash found in vicinity of tank, tank had been unprotected for 10 years, the older unprotected tank 4000 diesel came out of ground looking like swiss cheese. o April 7, 1988: Removed 10,000 gallon unleaded gasoline tank, some heavy rusting and pitting visible on tank but there was no apparent holes. Backfill around tank was improper per today's installation standards (very large boulders, large gravel and some sand) there were no hold down straps on tank, and bottom ash in close proximity to tank. Wet lines were heavily rusted in one large area.
  7. Scan of page 7 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 7 of 19 REDACTED Distribution: [redacted]Claims and Insurance [redacted]s. and Test Department [redacted]Regional Operations - WMECO [redacted]struction [redacted]HP [redacted]rans. SS and Mtce. [redacted] Trans. Bldg. Eng. Design [redacted]nsportation [redacted] EPD [redacted]ores [redacted] EPD [redacted]cilities Management [redacted] Legal [redacted] Nuclear Prod. [redacted]en. Fac. Lic. Dept. bsl cc: [redacted]
  8. Scan of page 8 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 8 of 19 TORRINGTON AUG / CT Bemis / Laura Lionts leak lokator hunter ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] TEST RESULTS DATE OF TEST | 07-6-85 CONTRACT NUMBER
    CUSTOMERNortheast Utilities
    LOCATION – IDENTIFICATION NUMBERNAME
    ADDRESS178 Franklin DriveCITYTorringtonSTATEConn
    LEAK LOKATOR USE ONLYCONCL. CODE
    TEST RESULTS SUMMARY
    NO.SYSTEM PRODUCTTANK SIZE GALLONSDIA/MATLWATER INCHESLEAK LOKATOR RESULTS LEVEL INCHESALR GPHCONCLUSIONRECOMMENDATIONSTESTTANKSYS
    IINo Lead Tank #I400064/371 1/2"106".039Tight
    IINo Lead Tank #II400064/371 1/2"95".038Tight
    VIIRegular Lead1000096/3T1 1/2"113".038Tight
    OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTS
    NO.SYSTEM PRODUCTTYPE OF PUMP REMOTETYPE OF PUMP SUCTION# APPLIEDMINUTES APPLIEDPRODUCT LOSS CC'SPRODUCT LOSS GPHCONCLUSION/RESULT
    IINo Lead Tank I>✓DLPressure testtestX
    IINo Lead Tank II>✓170Pressure testtestX
    IIIRegular Leaded> Pump✓ Side[illegible][illegible]XXTight
    NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTS
    NO.SYSTEM PRODUCTTEST NO.TEST LEVEL (INCHES)CLOCK STARTDURATION HRS.-MIN.LEAK RATE CC/DIVLEAK RATE CC/MINTEMP COMP Δ°FTEMP COMP CC/MINABSOLUTE LEAK RATE CC/MINABSOLUTE LEAK RATE GPHCHECK TEST Y or N
    INo Lead Tank I1106"9:4531 min.39+25.95+.161+33.80-1.85-.039N
    IINo Lead Tank II195"7:5231 min.47+2.82+.636+6.37-2.44-.038N
    IIIRegular Leaded1142"11:4620 min.35+21.47+.65523.88-2.41-.038N
  9. Scan of page 9 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 9 of 19 REDACTED ENVIRONMENTAL SERVICES, INC. 18 GREAT VALLEY PARKWAY, SUITE 6 MALVERN, PA 19355 [phone removed] [phone removed] Bemis | TORRINGTON AWG / CT Laura [illegible] leak lokator TEST RESULTS DATE OF TEST | 03-6-8? CONTRACT NUMBER CUSTOMER Northeast Utilities LOCATION – IDENTIFICATION NUMBER
    ADDRESS 178 Franklin DriveNAME
    CITY TorringtonSTATE Con
    TEST RESULTS SUMMARY
    NO.SYSTEM PRODUCTTANK SIZE GALLONSDIA/MATLWATER INCHESLEAK LOKATOR RESULTS LEVEL INCHESALR GPHCONCLUSIONRECOMMENDATIONSLEAK LOKATOR USE ONLY CONCL. CODE TEST TANK SYS
    INO LEAD TANK I450064.371 1/2"166"-.029Tight
    IINO LEAD TANK II450064.371 1/2"95"-.038Tight
    IIIREGULAR LEADED1000096 x T1 1/2"115"-.026Tight
    OTHER INFORMATION FINAL REPORT PRODUCT LINES – HYDROSTATIC PRESSURE TEST RESULTS
    NO.SYSTEM PRODUCTTYPE OF PUMP REMOTESUCTION# APPLIEDMINUTES APPLIEDPRODUCT LOSS CC'SPRODUCT LOSS GPHCONCLUSION/RESULT
    INO LEAD TANK I✓DODO[illegible]testX
    IINO LEAD TANK II✓testX
    IIIREGULAR LEADED✓✓110DueX
    IIIREGULAR LEADED✓ Pump✓[illegible][illegible][illegible][illegible]Tight
    NOTE: On suction systems, NEVER put more than 15 psi on any pump system. OTHER CONTRACTORS, OFFICIALS, CUSTOMER REPRESENTATIVES PRESENT DETAIL OF TEST RESULTS
    NO.SYSTEM PRODUCTTEST NO.TEST LEVEL (INCHES)TIME CLOCK STARTTIME DURATION HRS.-MIN.LEAK RATE CC/DIVLEAK RATE CC/MINTEMPERATURE COMPENSATION Δ°FTEMPERATURE COMPENSATION CC/MINABSOLUTE LEAK RATE CC/MINABSOLUTE LEAK RATE GPHCHECK TEST Y or N
    INO LEAD TANK I1166"9:4531 min.39+25.95+.141+27.82-1.85-.029N
    IINO LEAD TANK II195"9:5235 min4.1712.08+.03616.37-2.44-.038N
    IIIREGULAR LEADED1114"9:4630 min-.37+21.17+.25523.66-2.41-.038N
    * LEVEL – INCHES FROM TANK BOTTOM TO TEST LEVEL ALR – ABSOLUTE LEAK RATE (MEASURED LEAK RATE – TEMPERATURE COMPENSATION) IN GALLONS PER HOUR CONCLUSION – NFPA 329 CRITERION OF ± 0.05 GPH IS USED TO CERTIFY TIGHTNESS CERTIFICATION This is to certify that the above described tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated as tight meet the criterion established by the National Fire Protection Association Pamphlet 329 for Precision Testing.
    TESTS CONDUCTED BYCERTIFIED BY
    TEST VAN NO. [illegible]SIGNATURE [illegible]
    TANK TESTING SPECIALIST [illegible]NAME [illegible]DATE [illegible]
    TANK TESTING SPECIALIST [illegible]TITLE [illegible]
  10. Scan of page 10 of 19 of RSR-038 Attachment 1 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 1 REDACTED Page 10 of 19 TANK AND LOCATION DATA DATE: 03-6-85
    CUSTOMER: Northeast UtilitiesCITY: Torrington
    I.D. #STATE: Conn
    WEATHERTIMETEMPERATURECOMMENTS
    BEFORE TEST –
    AFTER TEST –
    SCHEMATIC: Building PUMP NO LEAD II 4000gal 64" NO LEAD II 4000gal 64" NO LEAD PUMP VENT Regular PUMPS VENT Regular LEADED 10000gal 96" Building
    PRODUCT/TANK NO.NO LEAD INO LEAD IIRegular
    BEFORE DELIVERY LEVELFillGaugeFillGaugeFillGaugeFillGaugeFillGauge
    LEVELFull
    GALLONS
    WATER1½"1½"1½"
    TOP OF RISER9796101132
    GRADE160163162137
    DROP TUBEALALAL
    CAPACITY, GALLONS4000400010000
    DIAMETER, INCHES646464
    MATERIALSTEELSTEELSTEEL
    PUMP TYPEGasboy[illegible]Bennett
    TYPE OF COVERTANTANTAN
    AGE OF TANKUKUKUK
    SIPHONNONONO
    TANK OPENINGS1-4" 1-2"1-4" 1-2"1-4"
    EXTRACTORSNONONO
    VAPOR RECOVERY TYPE VENT CONFIGURATION P-V VENT VALVE TYPE
    REPLACEMENT PARTS: PART #DESCRIPTIONQUANTITYPRICE
    #701[illegible]1[illegible]
    #124[illegible]1[illegible]
    #6" Quick Tite 2-gauge (wire)1[illegible]
    ADDITIONAL CHARGES: (pumpovers, overtime, etc.) [illegible] [illegible] *Data obtained from ☐ Station ☐ LL Charts ☐ Other ______

Scanned pages and machine-read text of RSR-038 Attachment 2 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 1 of 1 of RSR-038 Attachment 2 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 2 REDACTED Page 1 of 1 REDACTED UNDERGROUND STORAGE FACILITY NOTIFICATION
    2. PG.of
    11
    STATE OF CONNECTICUT Department of Environmental Protection UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 556-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. 1a. FIRST NOTIFICATION OR b. SUBSEQUENT NOTIFICATION (If checked, enter No.) SITE I.D.
    3. FOR STATE AGENCY USE ONLYA. SITE I.D.
    B. DATE RCVD BY D.E.P.C. DATE ENTERED
    D. GRID COORDINATES X ___ Y ___E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO
    SECTION A/B
    4. LOCATION OF FACILITYSITE NAME: East Hampton Service CenterNO. AND STREET: 22 East High StreetNEAREST INTERSECTING STREET: Route 2CITY OR TOWN: East HamptonSTATE: CT5. LATITUDE: 41° 34' 56"LONGITUDE: 72° 30' 14"
    6. BUSINESS NAME AND MAILING ADDRESSNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 061410270
    7. FACILITY OWNERNAME: The Connecticut Light & Power CompanyNO. AND STREET: P.O. Box 270CITY OR TOWN: HartfordSTATE: CTZIP CODE: 061410270
    8. TYPE OF OWNERX PRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. ___)
    9. OPERATOR/CONTACT PERSON[redacted]NO. AND STREET: 22 East High StreetCITY OR TOWN: East HamptonSTATE: CTZIP CODE: 06424
    [redacted] SECTION C
    10. TANK ID.11a. DATE OF INSTALLATION (Mo./Yr.)11b. TANK LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)12b. STATUS: IN USEABANDONED IN PLACEEST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCTCHEMICAL LIQUID14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No. if known)15. CONSTRUCTION MATERIALS: STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify from list A)16. PROTECTION a. INTERNAL: LINEDUNLINED; b. EXTERNAL: CATHODIC PROTECTIONCOATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify from list B)17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION PROTECTION (See list B)b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES," enter DATE and attach results. If "NO," enter "NO")
    Example5/75305000XXXXH55/75UNO
    Example7/60-8000X8/78XXXE77/60U—
    A1/7215275XXXXXH7/72H092584
    B2/721510000XXXX7/72O092684 (10-14-86 / 092684 struck through)
    C3'303010000X011/84XX8/80O092684
    D4'7215275XXXX7/72U092584
    E5,7215550XXXX7/72U092884
    P6,7215550XXXX7/72U092884
    20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? X YES 21. COMMENTS: 16b coal tar epoxy. Tanks B2, D4, E5 & F6 budgeted for cathodic protection in 1986. A1 is also for [illegible] [illegible] SECTION D 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted.
    22a. SIGNATUREX [redacted]22b. DATE SIGNED5/5/86
    22c. NAME (Type or Print)[redacted]
    22d. OFFICIAL TITLE (of owner or authorized representative)Senior Vice President
    COPY 4

Text of RSR-038 Attachment 3.pdf

Extracted from the file · 1 page · 146 characters

Scanned pages and machine-read text of RSR-038 Attachment 4 REDACTED.pdf

Read by machine
This document is a scan with no text in it. The text shown with each page was read from the image by machine (an AI model), not typed or checked by a person. It may contain errors, especially in numbers, dates and names, and a hard-to-read spot can come out as plausible but wrong text. Check the page image before relying on any figure. Open the original PDF (opens in a new tab)
  1. Scan of page 82 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 82 of 126 21 ED2125 REV. 11-84 TELEPHONE MEMORANDUM
    PROJECTROUTING
    Madison AWC : UST Release[redacted]
    CALL DATETIMEAM / PMINCOMING / OUTGOING
    12-4-913:15AM / X PM[ ] INCOMING / [X] OUTGOING
    TELEPHONE CONVERSATION PARTICIPANTS
    NAMECOMPANY NAME
    Mark DeCaprioOil & Chemical Spills Group Conn. DEP
    [redacted][redacted]
    CALL REPORTER'S NAME: [redacted]NU Environmental Programs Dept.DATE 12-4-91
    cc: Chronological FileSUMMARY
    Called Mark DeCaprio, Conn. DEP Spill Group to update him on the status of the Madison Release project. I informed Mark, that the helium Testing Conducted on Monday 12-2-91 indicated that there is no leakage sources in the two (2) 5000gal Gastanks (USTs) at the site. I told him that we (NU) were investigating the possibility of either surface spillage or spillage during tank filling processes. Mark was informed regarding: (1) additional Monitoring Wells being installed Friday Dec. 6, 1991 – He requested a verbal report on Friday and he may request split Spoon Sampl[e] based on info recieved from Drill filling decriptions. (2) V-droot System being installed Next Wk. (Week of 12-9-91). (3) Tank Calibration work to generate tank charts Dec. 16th or 17th. (4) Tank Testing Dec. 17th or Dec. 18th – Mark requested to review inventory records when he comes to site to look at Tank Testing (Precis[ion] Hydrostatic Test by Outside Vendor).
  2. Scan of page 83 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 83 of 126 22 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
    FACILITY: MadisonCODE: BGNLETTER NO: D05094
    TITLE/SUBJECT: Amended UST NotificationAGENCY: CDP
    SPECIAL INSTRUCTIONS:LETTER DATE: 12-10-91
    SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.
    DSAPERSONSODISCIPLINELOC.EXTINIT.DATECOMMENTS
    R.P. KlattenbergXEnviro. Svcs.B3F34628✓Sat 12-5
    R.C. NicholsEnviro. AuditB3F34645
    W.C. RenfroEnviro. Prog.B3F34620
    T.J. ButwillCivil HydraulicsN2065403
    D.R. WadeFH Programs EngngN2265460
    W.J. KornackiFH Improv. EngngN2263792
    R.N. SmartFH Eng. & Const.N2075362
    XXXRHPershonXLegalE2173175Dsp12/4/91
    Land PlanningSBS
    N.J. LanzalottaProd. Opns. Svcs.W2395657
    Project Engineer
    Facility Mgr./Supt.
    XXC.A. EdgeFac. Opns. & EngngSBS6750
    P.C. RobothamTransportation33336677
    J. BarresiSupt. - CT&M33336662
    W.V. ReicheltSys. Supt. - FossilW2395467
    R.G. ChevalierSys. Supt. - HydroW2395064
    XXSzymanskiXOriginator/LeadB3F34614✓CKS10-4-91
    XXChatlic SmithXGEL LeadW2185340
    XSupvsr - NLW218
    R. OsellaXSupvsr - GELW218544812-9-91NRC ☐ Yes ☐ No
    OTHER DISTRIBUTIONGEL CLERK INSTRUCTIONS
    XXFacilities FileGEL ClerkW218XORIGINAL AND ___ COPIES
    XXT. BeltzTest Build.NOTARY REQUIRED
    XXS. MartinMadisonXATTACHMENTS (X in "A" Column)
    FEE CHECK
    FEDERAL EXPRESS
    REGISTERED MAIL
    TELECOPY
    COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C_____ or FORCOM # F_____ DUE DATE: _____ Number of Calendar days in Advance (+) or Late (-) of Due Date_____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91
  3. Scan of page 84 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    * DEC-* 5-91 THU 13:03 | GEN. FACIL. LICENSING | FAX NO. 2036665890 | P. 02 The Connecticut Light and Power Company REDACTED | d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 84 of 126 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
    FACILITY: MadisonCODE: BGNLETTER NO: DO5094
    TITLE/SUBJECT: Amended UST NotificationAGENCY: CDP
    SPECIAL INSTRUCTIONS:LETTER DATE:
    SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.
    DSAPERSONSODISCIPLINELOC.EXTINIT.DATECOMMENTS
    R.P. KlattenbergXEnviro. Svcs.B3F34628RPK12-5-91
    R.C. NicholsEnviro. AuditB3F34645
    W.C. RenfroEnviro. Prog.B3F34620
    T.J. ButwillCivil HydraulicsN2065403
    D.R. WadeFH Programs EngngN2265460
    W.J. KornackiFH Improv. EngngN2263792
    R.N. SmartFH Eng. & Const.N2075362
    RHPershanXLegalE2173725PRP12/4/91
    Land PlanningSBS
    N.J. LanzalottaProd. Opns. Svcs.W2395657
    Project Engineer
    Facility Mgr./Supt.
    XXC.A. EdgeFac. Opns. & EngngSBS6750
    P.C. RobothamTransportation33336677
    J. BarresiSupt. - CT&M33336662
    W.V. ReicheltSys. Supt. - FossilW2395467
    R.G. ChevalierSys. Supt. - HydroW2395064
    XJTszymanskiXOriginator/LeadB3F34614[signature]12-5-91
    XChaillic SmithXGEL LeadW2185340CLS12-5-91
    XSupvsr - NLW218
    R. OsellaXSupvsr - GELW2185448
    NRC ☐ Yes ☐ No
    OTHER DISTRIBUTIONGEL CLERK INSTRUCTIONS
    XXFacilities FileGEL ClerkW218XORIGINAL AND ___ COPIES
    XXT. BetzTest Build.NOTARY REQUIRED
    XXS. MartinMadisonXATTACHMENTS (X in "A" Column)
    FEE CHECK
    FEDERAL EXPRESS
    REGISTERED MAIL
    TELECOPY
    COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C_______ or PORCOM # F_______ DUE DATE:_______ Number of Calendar days in Advance (+) or Late (-) of Due Date_______ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91
  4. Scan of page 85 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 85 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 [redacted] December 10, 1991 D05094 UST Coordinator Department of Environmental Protection 165 Capitol Avenue Hartford, CT 06106 Reference: Letter and Notification (D03879), [redacted] dated October 16, 1990. Dear Sir or Madam: Madison Service Center Amended UST Notification Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits an amended Underground Storage Facility Notification for CL&P's Madison Service Center. This notification supersedes the notification submitted on October 16, 1990 (referenced). The following changes have been made: o Removal of Tank A1, 550-gallon hydraulic fluid UST o Removal of Tank B2, 550-gallon motor oil UST o Removal of Tank F6, 550-gallon waste oil UST If you have any questions, please call Ms. Cynthia Karlic-Smith, NUSCO Generation and Environmental Licensing, at 665-3740. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company FOR: [redacted] Vice President BY: [redacted] Vice President cc w/Copy No. 2: Mr. Arthur W. Cunningham Town Hall 8 Meeting House Lane Madison, CT 06443
  5. Scan of page 86 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    REDACTED The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 86 of 126 UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. FACILITY NOTIFICATION 1a. FIRST NOTIFICATION OR SUBSEQUENT NOTIFICATION | (If checked, enter No.) SITE I.D. 3. FOR STATE AGENCY USE ONLY A. SITE I.D.
    B. DATE RCVD BY D.E.P.C. DATE ENTERED
    D. GRID COORDINATES XY
    E. DOES FACILITY MEET NEW REQUIREMENTS? YESNO
    SECTION A/B
    4. LOCATION OF FACILITYSITE NAME: MADISON REGIONAL SERVICE CTRNO. AND STREET: 135 NEW RDNEAREST INTERSECTING STREET: DUCK HOLE RDCITY OR TOWN: MADISONSTATE: CTS. LATITUDELONGITUDETELEPHONE
    5. BUSINESS NAME AND 6. MAILING ADDRESSNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    7. FACILITY OWNERNAME: THE CONNECTICUT LIGHT + POWER CO.NO. AND STREET: P.O. Box 270CITY OR TOWN: HARTFORDSTATE: CTZIP CODE: 06141-0270[redacted]
    8. TYPE OF OWNERPRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. ____)
    9. OPERATOR/CONTACT PERSONNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE[redacted]
    SECTION C (TANK TABLE)
    10. TANK ID.11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)12b. STATUS: IN USEABANDONED IN PLACEEST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCTCHEMICAL LIQUID14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS: a. STEELFIBERGLASS REINFORCED PLASTICOTHER (Specify)b. INTERNAL: LINEDUNLINED16. PROTECTION: a. INTERNAL: CATHODIC PROTECTIONCOATED/WRAPPEDCATHODIC PROTECTIONOTHER (Specify)b. EXTERNAL17. INTEGRAL PIPING SYSTEM: a. CONSTRUCTIONPROTECTIONb. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results. If "NO", enter "NO")
    Example5/75305000XXHeating fuel #2XXH3H5/75UNO
    Example7/60-8000X8/78X1, 1, 1 - Trichloroethane CAS #79016XXE7W7/60U—
    A1/73-550X11/91XHYDRAULIC FLUID
    B2/73-550X11/91XMOTOR OIL
    C3/73305000XXUNLEADED GASOLINEXXXE A8W C10/89I,O8-15-90
    D4/73305000XXUNLEADED GASOLINEXXXE A8W C10/89I,O7-24-90
    E5/73-10000X8/89XUNLEADED GASOLINE
    F6/73-550X11/91XWASTE OIL
    G7/7330170XXHYDRAULIC FLUIDXXXE F8W C/73RNO
    H8/73-1500X/89XDIESEL
    20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? ☐ YES 21. COMMENTS: All tanks - 16b + 17a - Impressed current system G7 - 16b - Tank is vaulted 22. CERTIFICATION: [certification text, not fully legible at this resolution] | 22a. SIGNATURE [redacted] | 22b. DATE SIGNED 12-10-91 | 22d. OFFICIAL TITLE (of owner or authorized representative): Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 06106
  6. Scan of page 87 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 87 of 126 23 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
    FACILITY: MadisonCODE: BGNLETTER NO: DD5094/
    TITLE/SUBJECT: Amended UST NotificationAGENCY: CDP
    SPECIAL INSTRUCTIONS:LETTER DATE: 12-10-91
    SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.
    DSAPERSONSODISCIPLINELOC.EXTINIT.DATECOMMENTS
    R.P. KlattenbergXEnviro. Svcs.B3F34628✓Sept 12-5
    R.C. NicholsEnviro. AuditB3F34645
    W.C. RenfroEnviro. Prog.B3F34620
    T.J. ButwillCivil HydraulicsN2065403
    D.R. WadeFH Programs EngngN2265460
    W.J. KornackiFH Improv. EngngN2263792
    R.N. SmartFH Eng. & Const.N2075362
    XX[illegible]XLegalE2173/25PdP12/4/91
    Land PlanningSBS
    N.J. LanzalottaProd. Opns. Svcs.W2395657
    Project Engineer
    Facility Mgr./Supt.
    XXC.A. EdgeFac. Opns. & EngngSBS6750
    P.C. RobothamTransportation33336677
    J. BarresiSupt. - CT&M33336662
    W.V. ReicheltSys. Supt. - FossilW2395467
    R.G. ChevalierSys. Supt. - HydroW2395064
    X[illegible]XOriginator/LeadB3F34614✓
    X[illegible]XGEL LeadW2185440[illegible]12-4-91NRC ☐ Yes ☐ No
    XSupvsr - NLW218
    R. OsellaXSupvsr - GELW2185448[illegible]12-9-91
    OTHER DISTRIBUTION
    XXFacilities FileGEL ClerkW218XGEL CLERK INSTRUCTIONS
    J. BetzTest Build.ORIGINAL AND ___ COPIES
    S. MartinmadisonXNOTARY REQUIRED
    ATTACHMENTS (X in "A" Column)
    FEE CHECK
    FEDERAL EXPRESS
    REGISTERED MAIL
    TELECOPY
    COMMITMENT / ACTION TRACKING INFORMATION Pull/Partial Response To: COTRAP # C_____ or FORCOM # F_____ DUE DATE: _____ Number of Calendar days in Advance (+) or Late (-) of Due Date_____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91
  7. Scan of page 88 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 88 of 126 DEC- 5-91 THU 13:03 | GEN. FACIL. LICENSING | . | FAX NO. 2036655896 | P. U2 GEL CORRESPONDENCE SIGNOFF AND DISTRIBUTION FORM PLEASE HELP EXPEDITE - REVIEW PROMPTLY AND HAND CARRY TO NEXT PERSON FOR ASSISTANCE CALL EXTENSIONS 5296 OR 3056
    FACILITY: MadisonCODE: BGNLETTER NO: D05094
    TITLE/SUBJECT: Amended UST NotificationAGENCY: CDP
    SPECIAL INSTRUCTIONS:LETTER DATE:
    SIGNOFF/DISTRIBUTION Signoff indicates your written concurrence for your discipline with statements and commitments made in the attached documents.
    DSAPERSONSODISCIPLINELOC.EXTINIT.DATECOMMENTS
    R.P. KlattenbergXEnviro. Svcs.B3F34628RPK12-5-91
    R.C. NicholsEnviro. AuditB3F34645
    W.C. RenfroEnviro. Prog.B3F34620
    T.J. ButwillCivil HydraulicsN2065403
    D.R. WadeFH Programs EngngN2265460
    W.J. KornackiFH Improv. EngngN2263792
    R.N. SmartFH Eng. & Const.N2075362
    RHPershanXLegalE2173723?[illegible]12/4/91
    Land PlanningSBS
    N.J. LanzalottaProd. Opns. Svcs.W2395657
    Project Engineer
    Facility Mgr./Supt.
    XXC.A. EdgeFac. Opns. & EngngSBS6750
    P.C. RobothamTransportation33336677
    J. BarresiSupt. - CT&M33336662
    W.V. ReicheltSys. Supt. - FossilW2395467
    R.G. ChevalierSys. Supt. - HydroW2395064
    XJ SzymanskiXOriginator/LeadB3F34614[illegible]12-7-91
    XChatlic SmithXGEL LeadW2185946CKS12-5-91NRC ☐ Yes ☐ No
    XSupvsr - NLW218
    R. OsellaXSupvsr - GELW2185448
    OTHER DISTRIBUTIONGEL CLERK INSTRUCTIONS
    XXFacilities FileGEL ClerkW218XORIGINAL AND ___ COPIES
    XXJ. BetzTest Build.NOTARY REQUIRED
    XXS. MartinMadisonXATTACHMENTS (X in "A" Column)
    FEE CHECK
    FEDERAL EXPRESS
    REGISTERED MAIL
    TELECOPY
    COMMITMENT / ACTION TRACKING INFORMATION Full/Partial Response To: COTRAP # C____ or FORCOM # F____ | DUE DATE:____ Number of Calendar days in Advance (+) or Late (-) of Due Date____ Commitment Number | GEL Lead | Discipline Lead | Response Date | DESCRIPTION REV. 5 7-91
  8. Scan of page 89 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 89 of 126 NORTHEAST UTILITIES THE CONNECTICUT LIGHT AND POWER COMPANY WESTERN MASSACHUSETTS ELECTRIC COMPANY HOLYOKE WATER POWER COMPANY NORTHEAST UTILITIES SERVICE COMPANY NORTHEAST NUCLEAR ENERGY COMPANY General Offices • Selden Street, Berlin, Connecticut P.O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 ([redacted]) December 10, 1991 D05094 UST Coordinator Department of Environmental Protection 165 Capitol Avenue Hartford, CT 06106 Reference: Letter and Notification (D03879), [redacted] o F. Wacht, dated October 16, 1990. Dear Sir or Madam: Madison Service Center Amended UST Notification Northeast Utilities Service Company (NUSCO), as agent for The Connecticut Light and Power Company (CL&P), submits an amended Underground Storage Facility Notification for CL&P's Madison Service Center. This notification supersedes the notification submitted on October 16, 1990 (referenced). The following changes have been made: o Removal of Tank A1, 550-gallon hydraulic fluid UST o Removal of Tank B2, 550-gallon motor oil UST o Removal of Tank F6, 550-gallon waste oil UST If you have any questions, please call Ms. Cynthia Karlic-Smith, NUSCO Generation and Environmental Licensing, at 665-3740. Very truly yours, NORTHEAST UTILITIES SERVICE COMPANY As Agent for The Connecticut Light and Power Company FOR: [redacted] Vice President BY: [redacted] Vice President cc w/Copy No. 2: Mr. Arthur W. Cunningham Town Hall 8 Meeting House Lane Madison, CT 06443
  9. Scan of page 90 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is below it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 90 of 126 REDACTED FACILITY NOTIFICATION UNDERGROUND STORAGE FACILITIES PROGRAM HAZARDOUS MATERIALS MANAGEMENT UNIT 165 Capitol Avenue, Hartford, CT 06106 TEL. 566-4630 PLEASE TYPE. ALL THREE COPIES MUST BE LEGIBLE! Refer to INSTRUCTIONS FOR FILING NOTIFICATION before completing form. SITE I.D. A. SITE I.D. POR STATE AGENCY USE ONLY B. DATE RCVD BY D.E.P C. DATE ENTERED D. GRID COORDINATES X ___ Y E. DOES FACILITY MEET NEW REQUIREMENTS? YES NO 1a. FIRST NOTIFICATION OR SUBSEQUENT NOTIFICATION (If checked, enter No.) SECTION A SECTION B
    4. LOCATION OF FACILITYSITE NAME: MADISON REGIONAL SERVICE CTRNO. AND STREET: 135 NEW RDNEAREST INTERSECTING STREET: DUCK HOLE RDCITY OR TOWN: MADISONSTATE: CT5. LATITUDELONGITUDETELEPHONE
    6. BUSINESS NAME AND MAILING ADDRESSNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    7. FACILITY OWNERNAME: THE CONNECTICUT LIGHT + POWER CO.NO. AND STREET: P.O. Box 270CITY OR TOWN: HARTFORDSTATE: CTZIP CODE: 06141-0270[redacted]
    8. TYPE OF OWNERPRIVATESTATEMUNICIPALFEDERAL (G.S.A. No. ___)
    9. OPERATOR/CONTACT PERSONNAMENO. AND STREETCITY OR TOWNSTATEZIP CODETELEPHONE
    SECTION C
    10. TANK ID11a. DATE OF INSTALLATION (Mo./Yr.)11b. LIFE EXPECTANCY (# of years)12a. TOTAL CAPACITY (Gals.)12b. STATUS: IN USEABANDONED IN PLACEEST. QUANTITY LEFT STORED (if any) (Gals.)REMOVEDDATE TANK LAST USED (Mo./Yr.)13. TYPE OF CONTENTS: OIL/PETRO-LEUM PRODUCTCHEMICAL LIQUID14. CONTENTS: CHEMICAL NAME OF PRINCIPAL SUBSTANCE (not trade name.) (Enter C.A.S. No., if known)15. CONSTRUCTION MATERIALS a. INTERNAL: STEEL, FIBERGLASS REINFORCED PLASTIC, OTHER, LINED, UNLINEDb. EXTERNAL: CATHODIC PROTECTION, COATED/WRAPPED, CATHODIC PROTECTION, OTHER16. PROTECTION17. INTEGRAL PIPING SYSTEM a. CONSTRUCTION MATERIAL, b. DATE OF INSTALLATION OR REPLACEMENT (Mo./Yr.)18. MONITORING SYSTEM (Specify type from list B)19. FAILURE DETERMINATION CONDUCTED? (If "YES", enter DATE and attach results. If "NO", enter "NO")
    Example5/75305000XXXH3H5/75UNO
    Example7/60-8000X8/78XXE7W7/60U—
    A1/73-550X11/91XHYDRAULIC FLUID
    B2/73-550X11/91XMOTOR OIL
    C3/73305000XXUNLEADED GASOLINEXXXE ABW C10/89I,O8-15-90
    D4/73306000XXUNLEADED GASOLINEXXXE ABW C10/89I,O7-24-90
    E5/73-10000X8/89XUNLEADED GASOLINE
    F6/73-550X11/91XWASTE OIL
    G7/7330170XXHYDRAULIC FLUIDXXXE F8W C/73RNO
    H8/73-1500X/89XDIESEL
    20. HAVE YOU ATTACHED SKETCH OF TANKS AND LOCATION? ☐ YES 21. COMMENTS: All tanks - 16b + 17a - Impressed current system G7 - 16b - Tank is vaulted 22. CERTIFICATION: I certify under penalty of law that I have personally examined and am familiar with the information submitted in this and all attached documents and that based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the submitted information is true, accurate and complete. Penalties: any owner who knowingly fails to notify shall be subject to a civil penalty not to exceed $10,000 for each tank for which notification is not given or for which false information is submitted. 22a. SIGNATURE [redacted] 22b. DATE SIGNED 12-10-97 22d. OFFICIAL TITLE (of owner or authorized representative) Vice President COPY 1: SEND TO DEP: 165 CAPITOL AVE. HARTFORD, CT 06106
  10. Scan of page 91 of 126 of RSR-038 Attachment 4 REDACTED.pdf. The machine-read text is beside it.
    The scanned page

    Machine-read text

    The Connecticut Light and Power Company REDACTED d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 29, 2026 RSR-038 Attachment 4 REDACTED Page 91 of 126 24 [redacted] ED2125 REV. 11-84 TELEPHONE MEMORANDUM PROJECT
    Madison AWC: Notice of Site ConditionsROUTING
    NAMEINITIALS
    CALL DATETIMEAM PM☐ INCOMING ☒ OUTGOING
    01/08/92
    TELEPHONE CONVERSATION PARTICIPANTS
    NAMECOMPANY NAME
    Elsie PettlonDEP, Water Management
    [redacted][redacted]
    NU EPD
    [redacted]
    CALL REPORTER'S NAMEDATE
    cc: Chronological File SUMMARY I called Elsie P. to explain the history of the recent problems at the Madison site including presence of free product, efforts to identify the source of the gasoline, helium test results and UST failure of the tank tightness tests on Jan 7. She was very interested in the current situation with the groundwater treatment system and infiltration galley. I described the installation of the air stripper and tests performed to ensure that gasoline was not leaving the treatment system back to groundwater. She felt that NU was doing "everything we should have done." She requested a copy of all test results, notifications and followup reports.

As listed on the current system

Question(s) Answered 38 (The Connecticut Light and Power Company) Date Filed: 10/20/2026

This filing on the current system (opens in a new tab)