Interrogatory responses
Answers to questions 59
Files6
RSR-059_Final.pdf
PDF · 234 KB · 4 pagesText searchable
Download RSR-059_Final.pdfRead the text of RSR-059_Final.pdf
RSR-059 Attachment 1.pdf
PDF · 858 KB · 2 pagesText searchable
Download RSR-059 Attachment 1.pdfRead the text of RSR-059 Attachment 1.pdf
RSR-059 Attachment 2.pdf
PDF · 1.2 MB · 6 pagesText searchable
Download RSR-059 Attachment 2.pdfRead the text of RSR-059 Attachment 2.pdf
RSR-059 Attachment 3.pdf
PDF · 3.5 MB · 19 pagesText searchable
Download RSR-059 Attachment 3.pdfRead the text of RSR-059 Attachment 3.pdf
RSR-059 Attachment 4.pdf
PDF · 74 KB · 1 pageText searchable
Download RSR-059 Attachment 4.pdfRead the text of RSR-059 Attachment 4.pdf
RSR-059 Attachment 4.xlsx
Excel · 23 KBText searchable
Download RSR-059 Attachment 4.xlsxRead the text of RSR-059 Attachment 4.xlsx
Page 6 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 6 of 19 EPR Cable Removed (17 yr; 2001) EPR Cable Removed (25 yr; 2010) Galleria Mall TR-XLPE Cable Removed (40 yr; 2025 TR-XLPE Cable Removed (17yr;2001)Page 7 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 7 of 19 TEAM REMOVES CABLES FROM THE GALLERIA MALL LOOP 7Page 8 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 8 of 19 SIMILAR 35 KV CABLE DESIGNS Cable Component TR-XLPE EPR No. 1/0 Copper Conductor (strand fill*) No. 1/0 Copper Conductor (strand fill*) XLPE Semi-Conductive Conductor Shield EPR Semi-Conductive Conductor Shield 345 mils TR-XLPE Insulation 345 mils EPR Insulation Insulation Shield Strippable XLPE Insulation Shield EPR Semi-Conductive Insulation Shield Concentric Neutral 16 x #14 Copper Concentric Neutral 16 x #14 Copper Concentric Neutral Jacket 80 mils Semi-Conductive PE Jacket 80 mils PE Insulating Jacket Conductor Conductor Shield Insulation *TR-XLPE Cable used a viscous fill material within and over the conductor strands with a semi-con tape layer over the filled conductor. EPR Cable used a soft rubber strand fill material. 8Page 9 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 9 of 19 TEST PROGRAM ▪ TR-XLPE and EPR 35kV cables with 40 years of field service ▪ 300 circuit feet from each cable removed for stress testing was done by NEETRAC an independent 3rd party testing organization ➢ HVTT (Ambient) ➢ Impulse (90 °C) ➢ DF 60Hz versus Temp Performed by NEETRAC ➢ Treeing analysis ➢ VLF tan d ➢ TR additive analysis Performed by Dow ➢ Moisture Analysis 9Page 10 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 10 of 19 ST A B L E TR E E RE T A R D A N T AD D IT IV E DIS T R IB U T IO N IN TR-XLPE 3.00 2.50 Intensity 2.00 1.50 1.00 0.50 0.00 0 1000 2000 Cable A Intensity 3000 4000 5000 Distance (micrometer) Cable B Intensity 6000 7000 8000 Cable C Intensity ▪ Normalized absorbance of a peak assigned to the TR additive relative to one assigned to PE ▪ The spectra were collected in 11 evenly spaced steps (about every 800 µm) along each slice from the insulation shield to the conductor shield 10Page 11 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 11 of 19 WATER TREE ANALYSIS – ONLY SMALL NUMBER PRESENT AFTER 40 YRS TR-XLPE EPR Volume Analyzed: 0.6 in3 Area Analyzed: 23.7 in2 Vented Trees 10-12 mils: 1 21-30 mils: 1 10-12 mils: 0 21-30 mils: 0 Bowtie Tress 6-10 mils: 3 11-20 mils: 1 6-10 mils: 1 11-20 mils: 1 TR-XLPE Small Bow-Tie Tree Phase A EPR Vented Tree Phase B Small Bow-Tie Tree Phase A ▪ No indication that water treeing became any more severe even as the cables reached the end of the projected life ▪ Maintained breakdown strength characteristics several times greater than the nominal stress level Pelissou, S., et al, “A Review of Possible Methods for Defining Tree Retardant Crosslinked Polyethylene (TRXLPE)”, IEEE Electrical Insulation Magazine, v.24, n.5 (2008). 11Page 12 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 12 of 19 BREAKDOWN STRENGTH WELL ABOVE OPERATING STRESS AFTER 40 YRS Nominal operating stress 12Page 13 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 13 of 19 HOT IMPULSE BREAKDOWN AT ELEVATED TEMP AFTER 40 YRS TR-XLPE EPR 13Page 14 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 14 of 19 DISSIPATION FACTOR OF TR-XLPE REMAINS WELL BELOW 0.5% 3.0 TRXLPE - 17y TRXLPE - 40y 2.5 EPR - 17y Tan Delta, % EPR - 40y 2.0 1.5 1.0 0.5 0.0 0 30 60 90 Conductor Temperature, °C 120 Dielectric losses in TR-XLPE remain minimal with temperature and age 14Page 15 of 19
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 16, 2026 RSR-059 Attachment 3 Page 15 of 19 VLF TAN D (CDFI) – CABLE DIAGNOSTIC ASSESSMENT ▪ CDFI-based VLF tan δ evaluation (0.1 Hz) ▪ Test stress levels: 0.5, 1.0, 1.5U₀ ▪ Action guidance informed by multi-diagnostic data ▪ Asset decision support (replace / monitor / no action) Insulation Material TR-XLPE EPR Phase VLF tan δ at 0.5 U₀ VLF tan δ at 1.0 U₀ VLF tan δ at 1.5 U₀ Std. Dev. @ 1.0 U₀ Tip-Up (TU) A 0.2355 0.2116 0.1953 0.0037 −0.04 B 0.3655 0.3400 0.3268 0.0000 −0.03 C 0.4989 0.4716 0.4526 0.0037 −0.05 A 7.0200 7.1000 7.1979 0.0000 0.18 B 7.8672 7.9884 8.1226 0.0037 0.26 C 8.0300 8.1400 8.2600 0.0000 0.23 “Tip-Up” is the change in tan δ at 1.5Uo compared to 0.5Uo. CDFI Action Guidance: ✅ TR-XLPE: No action required — low tan δ, negative tip-up possible ✅ EPR: No action required — higher tan δ, positive tip-up expected 15
Text of RSR-059 Attachment 4.pdf
Extracted from the file · 1 page · 426 characters
Text of RSR-059 Attachment 4.xlsx
Sheet names, column headings and text cells; numbers left out
As listed on the current system
Question(s) Answered 59 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 11/06/2026