Interrogatory responses
Answers to questions 1 thru 1
Files14
UPA-001-SP01_Final.pdf
PDF · 109 KB · 1 pageText searchable
Download UPA-001-SP01_Final.pdfRead the text of UPA-001-SP01_Final.pdf
UPA-001-SP01 Attachment 13 REDACTED.pdf
PDF · 4.6 MB · 14 pagesText searchable
Download UPA-001-SP01 Attachment 13 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 13 REDACTED.pdf
UPA-001-SP01 Attachment 12 REDACTED.pdf
PDF · 3.3 MB · 15 pagesText searchable
Download UPA-001-SP01 Attachment 12 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 12 REDACTED.pdf
UPA-001-SP01 Attachment 11 REDACTED.pdf
PDF · 3.9 MB · 24 pagesText searchable
Download UPA-001-SP01 Attachment 11 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 11 REDACTED.pdf
UPA-001-SP01 Attachment 10 REDACTED.pdf
PDF · 3.7 MB · 19 pagesText searchable
Download UPA-001-SP01 Attachment 10 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 10 REDACTED.pdf
UPA-001-SP01 Attachment 9 REDACTED.pdf
PDF · 3.9 MB · 24 pagesText searchable
Download UPA-001-SP01 Attachment 9 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 9 REDACTED.pdf
UPA-001-SP01 Attachment 8 REDACTED.pdf
PDF · 4.0 MB · 17 pagesText searchable
Download UPA-001-SP01 Attachment 8 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 8 REDACTED.pdf
UPA-001-SP01 Attachment 7 REDACTED.pdf
PDF · 3.7 MB · 14 pagesText searchable
Download UPA-001-SP01 Attachment 7 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 7 REDACTED.pdf
UPA-001-SP01 Attachment 6 REDACTED.pdf
PDF · 3.3 MB · 13 pagesText searchable
Download UPA-001-SP01 Attachment 6 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 6 REDACTED.pdf
UPA-001-SP01 Attachment 5 REDACTED.pdf
PDF · 3.6 MB · 14 pagesText searchable
Download UPA-001-SP01 Attachment 5 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 5 REDACTED.pdf
UPA-001-SP01 Attachment 4 REDACTED.pdf
PDF · 3.6 MB · 16 pagesText searchable
Download UPA-001-SP01 Attachment 4 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 4 REDACTED.pdf
UPA-001-SP01 Attachment 3 REDACTED.pdf
PDF · 3.7 MB · 12 pagesText searchable
Download UPA-001-SP01 Attachment 3 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 3 REDACTED.pdf
UPA-001-SP01 Attachment 2 REDACTED.pdf
PDF · 3.7 MB · 11 pagesText searchable
Download UPA-001-SP01 Attachment 2 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 2 REDACTED.pdf
UPA-001-SP01 Attachment 1 REDACTED.pdf
PDF · 2.8 MB · 13 pagesText searchable
Download UPA-001-SP01 Attachment 1 REDACTED.pdfRead the text of UPA-001-SP01 Attachment 1 REDACTED.pdf
Page 13 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 13 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 13 of 24 It was noted during the assessment that the site Auditorium could likely utilize this type of scheduling, with possibilities in conference rooms and other areas. The example below summarizes a potential before and after schedule – assuming average consistent use in the 10 AM – 2 PM period of weekdays. This model is likely conservative; many of these spaces are experiencing virtually no use and could remain in unoccupied mode for the majority of the operating schedule. Sunday 12:00 AM 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM 6:00 AM 7:00 AM 8:00 AM 9:00 AM 10:00 AM 11:00 AM 12:00 PM 1:00 PM 2:00 PM 3:00 PM 4:00 PM 5:00 PM 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM Occ Hrs UnOcc Hrs Intermittent Spaces HVAC Operation - Existing and Proposed with Occupancy Control Existing - Typcial Schedule Proposed - Occupancy Control Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday Tuesday Wednesday Thursday Friday 12:00 AM 1:00 AM 2:00 AM 3:00 AM 4:00 AM 5:00 AM X X X X X 6:00 AM X X X X X 7:00 AM X X X X X 8:00 AM X X X X X 9:00 AM X X X X X 10:00 AM X X X X X X X X X X 11:00 AM X X X X X X X X X X 12:00 PM X X X X X X X X X X 1:00 PM X X X X X X X X X X 2:00 PM X X X X X X X X X X 3:00 PM X X X X X 4:00 PM X X X X X 5:00 PM X X X X X 6:00 PM 7:00 PM 8:00 PM 9:00 PM 10:00 PM 11:00 PM 0 13 13 13 13 13 0 Occ Hrs 0 5 5 5 5 24 11 11 11 11 11 24 UnOcc Hrs 24 19 19 19 19 Saturday 5 19 Implementation of this strategy should be possible via programming within the proposed BMS and the addition of occupancy sensors. Table below shows estimated cost and savings from the implementation of this type of control: 0 24Page 14 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 14 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 14 of 24 Occupancy Control of Intermittent Use Spaces Description Number Unit Notes Building footprint, SF 5,000 SF Estimated area affected Average Ceiling Ht, Ft 10 LF Average Estimated office volume, CF 50,000 CF Typical Air Change per Hour (ACH) 1.75 ACH Estimated Average Outdoor Air Intake, CFM 1,458 CFM Estimated Existing Operation Estimated Annual Cooling Energy 8,000 kWh Estimated Annual Natural Gas Heating Energy 500 CCF Estimated Annual Electric Heating Energy 13,000 kWh WSHPs Proposed Operation Proposed Annual Cooling Energy 7,000 kWh Proposed Annual Natural Gas Heating Energy 200 CCF Proposed Annual Electric Heating Energy 5,000 kWh Estimated New Control Strategy Savings Estimated Annual Electrical Savings 9,000 kWh Estimated Annual Natural Gas Savings 300 CCF Estimated Annual Cost Savings $ 1,615 $ @$0.1428/kWh and $1.10/CCF Change Cost - Programming $ 5,000 $ Simple Payback - no incentives 3.1 yrs Estimated Annual GHG Reduction 4 MT CO2e $/Lifetime GHG Reduction $117.04 $/MT CO2e 10 year measure life Recommended next steps for this project involve working with controls vendor to develop a scope of work and cost quotation, then working to implement as a facet of BMS installation/upgrade. EEM – 06 – Building Envelope Age of the building was noted during site walkthrough. Relatively low heating energy use indicates the structure is sound and retains heat well, and staff is active in reducing unneeded air infiltration and movement via sealing ducts and openings not in use. Aged doors, garage area bay doors, windows, and building plane transitions (e.g., roof/wall joint) likely have deteriorated seals simply due to building age. Diagram below summarizes the possible heat transfers due to infiltration and thermal envelope deficiencies:Page 15 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 15 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 15 of 24 Site is recommended to engage with a vendor to perform a full building shell assessment of the site and to follow the recommendations regarding thermal envelope and air infiltration. The table below shows a high-level estimate of potential cost and savings from this measure: Building Shell Savings Calculation Description Value Unit Existing Electric Heating and Cooling Load 102,000 kWh Existing Natural Gas Heating Load 7,250 CCF Proposed Electric Heating Cooling Load 87,000 kWh Proposed Natural Gas Heating Load 5,900 CCF Estimated Building Shell Remediation Savings (Electric) 15,000 kWh Estimated Building Shell Remediation Savings (Natural Gas) 1,350 CCF Annual Cost Savings $ 3,627 $ Estimated Annual GHG Reduction 11.8 MT CO2e Estimated Install Cost $ 30,000 $ Simple Payback 8.3 $ Estimated $/Lifetime MT CO2e $ 170 $ Notes @ $0.1428/kWh & $1.10/CCF @ 0.0055 MT/CCF & 0.000291 MT/kWh Including survey cost estimated 15 yr measure lifetime Next steps involve working with a local vendor to obtain a building shell assessment and recommendations, determining path forward with regard to performing remediations, then working with a local vendor to remediate gaps and cracks. EEM – 07 – Building Heating Electrification Existing heating and cooling are primarily via WSHPs, served for heating by basement boiler plant. This system is both efficient and has shifted a portion of the building heating load to electricity. Backup boiler is additionally electric – the 150 kW boiler is reported to be able to meet WSHP loop heating needs for some portions of the year. This site has made great strides towards electrification of heating loads. Full heating electrification could potentially be achieved with the installation of larger (heat pump) electric boilers to replace the primary natural gas fired boilers. Note that existing boilers are condensing (high efficiency)Page 16 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 16 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 16 of 24 and recent installation, and such and addition to the building electric load would require additional electrical service to the building at significant cost. Heat pump boiler technology is available. However, boilers at the size required to meet the WSHP loop demand are likely not on the market yet, or at significant cost if available. Site would need to stage multiple boilers with associated plumbing to meet heating loop needs. In addition to the equipment cost and additional electrical service, there would likely be significant engineering and design costs, with an undetermined path forward to implementation. Energy and GHG emissions savings would be realized via: - Associated site Greenhouse Gas emissions reduction the switch from natural gas to lower GHG emissions grid electricity Additionally, this would require a switch to electricity as a heating fuel, with possible higher energy costs to achieve site heating than existing natural gas (increased heating efficiency/COP but also higher $/btu cost fuel). Table below estimates costs and associated GHG reduction from electrification of all existing natural gas heating applications: Convert Natural Gas Building Heating Systems to Electric Description Value Unit Notes Estimated Annual Natural Gas Heating Usage 16,000 CCF Estimated Annual Natural Heating Gas Cost $ 17,600 $ Annual Associated GHG Emissions 90 MT CO2e Electric Boiler Efficiency 2# Average ASHP boiler efficiency Proposed Annual Heating Energy 193,000 kWh Proposed Area Heating Cost $ 27,600 $ Proposed Associated GHG Emissions 60.0 MT CO2e Estimated Annual Natural Gas Savings 16,000 CCF Estimated Annual Electric Savings (193,000) kWh Estimated Annual Cost Savings $ (10,000) $ Estimated Change Cost - Add't'l Electric Boilers $ 1,500,000 $ New service into building needed Simple Payback - no incentives n/a yrs GHG Emissions Reduction 30 MT CO2e Lifetime Cost per MT CO2e $ 2,500 $/MT 20 year measure life QGM can recommend installation vendors if desired for a more precise cost and scope of work, and site is encouraged to work with utility representatives to determine incentive/rebate eligibility and potential cost offsets. Additional Opportunities Zero loss drains for compressor plantPage 17 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 17 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 17 of 24 Timed drains utilize compressed air from the plant to purge moisture; site is recommended to investigate replacement with zero-loss drains which use no air to purge moisture, thereby eliminating a source of air consumption from the plant. Site may want to consider replacement of exiting timed drain with zero loss. Ensure proper functioning of Economizers Estimates indicate that only about one in four economizers works properly, with the remaining three providing sub-par performance or wasting energy. A 1995 survey of commercial buildings in the U.S. shows that about 461,000 buildings have economizers assisting HVAC systems that condition more than 16 billion square feet of building space. Proper economizer operation enhances energy efficiency, reduces costs, and extends equipment life. See the following online resources for more information: https://www.energytocare.org/system/files/media/file/2020/11/17 Perform Economizer Maintenance.pdf https://www.cedengineering.com/userfiles/M02-014%20%20Economizers%20in%20Air%20Handling%20Systems%20-%20US.pdf Sustainability Considerations Background Site and portfolio sustainability is best guided by the framework and methodology set forth in ASHRAE Standard 228-2023 Standard Method of Evaluating Zero Net Energy and Zero Net Carbon Building Performance (available for purchase here: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-228-standardmethod-of-evaluating-zero-net-energy-and-zero-net-carbon-building-performance). The site is not known to have a present net-zero strategy; however, the ASHRAE standard presents a strong method to: - Assess current building energy use and carbon emissions Establish a baseline Develop milestones Develop a plan to reach milestones The data and information shown below is intended to help develop an understanding of where current portfolio sustainability goal aligns with current position. Emissions Scopes Emissions reporting is generally addressed across three Emissions Scopes, as seen below:Page 18 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 18 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 18 of 24 An important aspect of developing a sustainability plan is the determination of which emissions scopes will be targeted for reduction. The majority of sustainability planning at the time of this report is focused on Scopes 1 and 2, although large corporations with significant supply and delivery chains have begun to address Scope 3 as well. The focus of the sustainability plan in this report is on Scope 1 and 2 emissions. ASHRAE Standard 228-2023 Standard Method of Evaluating Zero Net Energy and Zero Net Carbon Building Performance ASHRAE 228-2023 includes the following diagram illustrating energy flows into, from, and out of a site:Page 19 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 19 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 19 of 24 The difference between energy flow into a site, and energy flow out, is site net energy. The primary goal of sustainability is to reduce this net energy, and therefore, net carbon emissions associated with the site and its operation. ASHRAE 228-2023 – examples of data gathering and forms ASHRAE 228-2023 recommends site conduct an all-energy and associated carbon emissions accounting as seen in the tables shown below. Known values are filled in as a beginning of the process: Form 1 General Building and Site Description ID: Address: City, State, Country, ZIP Code: Primary Year of Construction: 250 Freight St 250 Freight St Waterbury, CT 06072 c. 1920 Gross Floor Area (GFA): Physical site area, SF: Non-green-roof building footprint area: Other Physical site area not requiring landscape care: Landscape area (LA): Secondary: 117,810 On-site renewable energy system type: Compliance Type Portion of building: Building: Part of a Commnuity? If "Yes," Community Name? Measurement Start Date: On-site renewable energy system design max output, kW: ~25,000 SF (2) 9/25/2024Page 20 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 20 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 20 of 24 Form 2 Annual Site Energy Conversion Calculation 1a 1b 2a 2b 3 4 5 6a 6b 7a 7b 8 9 10 11 12 13 14 15 16 17 18 19 Imported grid electricity Imported specific electricity Imported grid natural gas Imported renewable natural gas Imported steam Imported hot water Imported chilled water Imported grid fuel oil Imported renewable fuel oil Imported grid propane Imported renewable propane Imported coal or other Imported biomass On-site nonrenewable energy Imported transportation vehicle energy Imported landscape energy Exported nonrenewable electricity Exported renewable electricity Exported steam Exported hot water Exported chilled water Exported other Exported transportation vehicle energy Energy Use Numercial Value 891,911 15,951 Units kWh Conversion Factor to kWh 1 Annual site Energy, kWh/yr 891,911 CCF 30.2 481,061Page 21 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 21 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 21 of 24 Form 3 Annual Site Energy Conversion Calculation 1a 1b 2a 2b 3 4 5 6a 6b 7a 7b 8 9 10 11 12 13 14 15 16 17 18 19 20 Energy Form Imported grid electricity Imported specific electricity Imported grid natural gas Imported renewable natural gas Imported steam Imported hot water Imported chilled water Imported grid fuel oil Imported renewable fuel oil Imported grid propane Imported renewable propane Imported coal or other Imported biomass On-site nonrenewable energy Imported transportation vehicle energy Imported landscape energy Exported nonrenewable electricity Exported renewable electricity Exported steam Exported hot water Exported chilled water Exported other Exported transportation vehicle energy Qualified off-site renewable energy *Source energy factors typically available from local utilities Energy Use Numercial Value 891,911 481,061 Source Energy Annual Source Conversion Factor Energy, kWh/yr 891,911 481,061Page 22 of 24
The Connecticut Light and Power Company d/b/a Eversource Energy REDACTED Docket No. 26-05-10 Date Issued August 07, 2026 UPA-001-SP01 Attachment 11 REDACTED Page 22 of 24 250 Freight Street – Waterbury, CT QGM Scoping Study October 2024, page 22 of 24 Form 4 Annual Greenhouse Gas Emissions (GHG) Net Calculation 1a 1b 2a 2b 3 4 5 6a 6b 7a 7b 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Energy Form Imported grid electricity Imported specific electricity Imported grid natural gas Imported renewable natural gas Imported steam Imported hot water Imported chilled water Imported grid fuel oil Imported renewable fuel oil Imported grid propane Imported renewable propane Imported coal or other Imported biomass On-site nonrenewable energy Imported transportation vehicle energy Imported landscape energy Exported nonrenewable electricity Exported renewable electricity Exported steam Exported hot water Exported chilled water Exported other Exported transportation vehicle energy Qualified off-site renewable energy Refrigeration Loss (Form 4A) Annual GHG Net Emissions Previous Measurement Period Sum, Two-Year GHG Net Emissions Annual Site Energy, kWh/yr 891,911 GHG Emissions Factor, kg CO2e/kWh 0.291 Annual GHG Emissions, kg CO2e/yr 259,546 481,061 0.183 88,034 Annual GHG Net Emissions, kg CO2e Previous GHG Net Emissions, kg none CO2e Sum, Two-Year GHG Net 347,580 Emissions kg CO2e 347,580 *Refrigerant loss form not included as not relevant at site. 347,580 none 347,580
Text of UPA-001-SP01 Attachment 10 REDACTED.pdf
Extracted from the file · 19 pages, 4 without text · 27,484 characters
Text of UPA-001-SP01 Attachment 9 REDACTED.pdf
Extracted from the file · 24 pages, 5 without text · 30,898 characters
Text of UPA-001-SP01 Attachment 8 REDACTED.pdf
Extracted from the file · 17 pages, 5 without text · 22,701 characters
Text of UPA-001-SP01 Attachment 7 REDACTED.pdf
Extracted from the file · 14 pages, 4 without text · 17,187 characters
Text of UPA-001-SP01 Attachment 6 REDACTED.pdf
Extracted from the file · 13 pages, 3 without text · 14,512 characters
Text of UPA-001-SP01 Attachment 5 REDACTED.pdf
Extracted from the file · 14 pages, 4 without text · 17,555 characters
Text of UPA-001-SP01 Attachment 4 REDACTED.pdf
Extracted from the file · 16 pages, 4 without text · 19,788 characters
Text of UPA-001-SP01 Attachment 3 REDACTED.pdf
Extracted from the file · 12 pages, 4 without text · 11,899 characters
Text of UPA-001-SP01 Attachment 2 REDACTED.pdf
Extracted from the file · 11 pages, 4 without text · 10,526 characters
Text of UPA-001-SP01 Attachment 1 REDACTED.pdf
Extracted from the file · 13 pages, 3 without text · 17,141 characters
As listed on the current system
Question(s) Answered 1 thru 1 (Connecticut Light and Power Company dba Eversource Energy)(Supplemental/Revision) Date Filed: 10/07/2026