Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Files5

Search terms highlighted
Eversource rate increase is on 13 pages across 2 files of the text below, highlighted. Go to the first matchClear highlighting
12 pages match
  1. Page 23 of 107

    1 That result reflects a basic physical reality on the Company’s distribution system: there is 2 massive spare capacity in the feeders that deliver electricity to customers. Figure 11 ranks every 3 feeder on Eversource’s distribution system by how close its peak demand comes to its rated 4 capacity, from most to least utilized: 14 Eversource's feeders have massive headroom— only 0% exceed capacity at peak 160% 140% 0.2% exceed rated capaci ty Peak load (% of rated capacity) 120% 100% 80% 60% Median utilization: 49% 40% 20% 0% 0 250 500 750 Feeders (ranked by peak load as % of capacity) Figure 11: Peak demand as a percentage of rated capacity for every feeder on Eversource CT’s distribution system, ranked from most to least utilized. The gray line marks 100% of rated capacity. Source: Eversource response to System Data Requirement No. 2. Of the 918 feeders with loading data, only 2 feeders — 0.2% — have peak demand that 5 6 exceeds their rated capacity. Those feeders serve just 4,903 customers, or 0.4% of the 7 Company’s 1,218,177 customers on feeders with data. The median feeder operates at just 49% of 8 capacity, meaning the typical feeder has 51% headroom even at its annual peak. Data from the Company’s response to System Data Requirement No. 2, OCC-365, Attachment 28, Docket No. 26-05-10. Peak demand is the most recent available annual maximum loading (2025 where reported, otherwise 2024). Capacity is the feeder’s rated capacity in KVA. 14 21
  2. Page 24 of 107

    1 The Company has not yet provided data identifying whether each feeder’s peak occurs in 2 summer or winter. 15 Until that data is produced, I have conservatively assumed that the peaks 3 shown in Figure 11 are summer peaks. 16 Under that assumption, the chart depicts the distribution 4 system at its most stressed — and even then, the vast majority of feeders have substantial spare 5 capacity. 6 In winter, the headroom is certainly even greater. Connecticut is a summer-peaking 7 system: virtually every home and business has air conditioning, which drives the summer peak. 8 By contrast, fewer than 18% of Connecticut households heat with electricity — the vast majority 9 heat with natural gas and fuel oil, loads that the electric grid does not carry at all. 17 The winter 10 electric peak is therefore almost certainly well below the summer peak across the Company’s 11 distribution system, which means the headroom shown in Figure 11 — already substantial — 12 would be even larger in winter. This is consistent with the MCOS study assigning near-zero 13 marginal distribution costs to winter hours: there is simply no capacity pressure on the 14 distribution grid during the heating season. 15 Q. Is the bill increase that customers pay for distribution and transmission after installing 16 heat pumps under Rate 1 justified by the additional T&D costs they cause after making 17 this transition? We requested summer and winter peaks through discovery but the Company has not yet provided it. What was provided is each feeder’s annual maximum and minimum demand across the past five years, without identifying the date, hour, or season at which the peak occurred. 15 The Company reported each feeder’s annual maximum demand but did not identify the season. Connecticut is a summer-peaking system, so most feeders’ annual peaks almost certainly occur in summer. Even if some turn out to be winter peaks, this makes our headroom estimate more conservative, not less: the annual maximum is by definition higher than the winter peak alone, so the true winter headroom on those feeders would be even greater than what Figure 11 shows. 16 U.S. Census Bureau, American Community Survey 1-Year Estimates (2023), Table B25040, “House Heating Fuel.” In Connecticut, 34% of occupied housing units heat with utility gas, 32% with fuel oil, and 18% with electricity (including both heat pumps and electric resistance). 17 22
  3. Page 25 of 107Match

    1 A. No, these customers are being overcharged. 2 Under the cost-causation principle, these customers should pay for that additional $10 in 3 new T&D costs they cause, on average — but no more. Yet under proposed Rate 1, their 4 distribution and transmission charges increase by $1,051 per year — roughly 102 times the new 5 T&D costs they actually cause. 6 Figure 12 shows the gap between the incremental T&D charges that the average fossil 7 fuel-heated customer pays after installing heat pumps, and the incremental marginal T&D costs 8 they cause. 18 Figure 12: Change in annual T&D costs caused vs. T&D charges paid when a fossil fuelheated home installs a heat pump under proposed Rate 1. 9 At present, fossil fuel-heated customers that install heat pumps overpay by an average of 10 $1,040 a year — an amount equal to 44% of their entire post-heat-pump T&D bill. 19 This is a 11 gratuitous surcharge that penalizes customers who electrify their heating, in order to lower the Charges computed by applying Eversource’s proposed Rate 1 tariff to the same representative sample of residential load profiles. Costs from the hourly marginal-cost schedule described in Exhibit JPV-2, Section 3. See Exhibit JPV-2, Section 4 for the full methodology. 18 19 $1,040 overcharge ÷ $2,377 total post-heat-pump T&D bill = 44%. 23
  4. Page 26 of 107

    1 bills of customers who continue to heat with fossil fuels. (See next question for an explanation of 2 how this transfer occurs.) 3 Q. You’ve shown that fossil fuel-heated customers are overpaying for T&D by $1,040 a 4 year — on average. Does the overpayment vary by customer? 5 A. Yes, it varies significantly. Figure 13 shows the entire distribution of annual T&D 6 overpayments across all fossil fuel-heated customers in the Company’s territory after switching 7 to heat pumps, under the proposed Rate 1 tariff. 20 8 Overpayments are defined as each customer’s incremental T&D charges (from Rate 1 9 being applied to their heat pump’s incremental load), minus their incremental T&D marginal cost 10 (the additional new T&D costs caused by that incremental load during peak hours). Figure 13: Annual delivery overpayment for all fossil fuel-heated CT Eversource homes switching to heat pumps, under proposed Rate 1. 11 The overpayment here is calculated as their total delivery bill after they install heat 12 pumps, minus the sum of the incremental marginal costs caused by the installation and their total Per-building overpayment = incremental delivery revenue − incremental delivery marginal cost. Positive values indicate the customer is being overcharged; negative values indicate the customer is being undercharged. See Exhibit JPV-2, Section 4. 20 24
  5. Page 27 of 107

    1 delivery bill before the installation. Positive values indicate overpayment — that customer is 2 being charged above their incremental marginal cost; negative values indicate underpayment. 0 3 indicates a customer whose post-heat pump bill only increases by the costs they cause due to the 4 heat pump, their incremental marginal costs. Under a perfectly fair rate (from a cost-causation 5 perspective), all customers would be at 0. 6 Figure 13 confirms that overcharging is the norm, not the exception: virtually all fossil 7 fuel-heated homes that switch to heat pumps are being overcharged for transmission and 8 distribution, with most overpaying between several hundred and well over a thousand dollars per 9 year. 10 The overpayment distribution is right-skewed — some homes overpay far more than the 11 average — because homes with larger heating loads add more incremental kWh, and each of 12 those kWh is charged at the full volumetric rate regardless of whether it causes new 13 infrastructure costs. 14 Q. Why do fossil fuel-heated customers who install heat pumps end up being overcharged 15 for T&D under Rate 1? 16 A. Under the cost-causation principle, if a customer’s usage does not cause new costs, they 17 should not be charged as though it does. Rate 1 does exactly that: it charges the same volumetric 18 rate for every kWh — whether that kWh flows over the grid at 2 a.m. in January, when the 19 system has abundant spare capacity, or at 5 p.m. on the hottest day of the year, when the system 20 is strained. 21 22 When a customer installs a heat pump and adds 6,432 kWh per year, the tariff treats every one of those kWh as though it triggers new infrastructure investment. But 97% of those 25
  6. Page 28 of 107

    1 new kWh fall between October and April, when there are no peak hours and therefore zero 2 marginal T&D cost. The tariff does not distinguish — it charges the same rate regardless. 3 Q. Is the Company aware that fossil fuel-heated customers who adopt heat pumps are 4 being overcharged under Rate 1? 5 A. Yes. Though the Company does not use the term “overpayment” or “overcharge”, it is indeed 6 aware of the large gap between the incremental revenue that Rate 1 extracts from heat pump 7 customers, and the incremental cost those customers actually impose on the grid, as the proposed 8 discount under Rate 6 is justified by the existence of, and applied directly to, this gap. 9 When asked how it determined the level of the Rate 6 discount, the Company responded: “The 10 discounted rate is set to cover the incremental cost of serving the additional load the converting 11 customer adds, which establishes the floor; the standard residential rate establishes the reference 12 point above it. The discount is the space between those two, and it is sized to be no deeper than 13 that space.” 21 14 In other words, the Company is claiming that the discount could legitimately be set 15 anywhere within the gap between the incremental revenue produced by applying Rate 1 to 16 incremental heat pump load, and the incremental marginal T&D cost associated with that load. 17 (As will be shown in Section VII, the Company’s proposed Rate 6 sets the discount far closer to 18 the “ceiling” than the “floor”.) 19 20 Why does the Company see incremental marginal T&D cost as the floor? Because it guarantees that the discount does not shift costs to non-heat pump customers: “A Rate 6 21 Response to CLF-003(b), Docket No. 26-05-10 (Sept. 3, 2026) (Eversource 2026b). 26
  7. Page 29 of 107

    1 customer pays to cover the incremental cost of serving that customer, such that no portion of that 2 customer’s cost of service is redistributed to non-adopting customers.” 22 3 The implication is clear: everything that Rate 1 collects from a heat pump customer’s 4 incremental load above that customer’s incremental cost of service is revenue in excess of what 5 cost causation requires — an overpayment, in our terminology. The Company could eliminate all 6 of the entire overpayment — discount the rate all the way down to the floor — and customers 7 newly installing heat pumps would still be paying their full incremental cost of service, still 8 satisfying cost causation, without negatively affecting the bills of non-heat-pump customers. 9 Q. What is a cross-subsidy, and how do volumetric rates create one within the residential 10 customer class? 11 A. A cross-subsidy within a rate class arises when one identifiable group of customers 12 systematically pays more than their cost of service, and that excess revenue allows the customers 13 of another identifiable group to pay less than their cost of service. 14 The mechanism is straightforward: when fixed costs — like the embedded costs of the 15 transmission and distribution system — are predominantly recovered through volumetric 16 charges, customers with higher-than-average usage pay a greater share of those fixed costs, 17 effectively subsidizing the customers with lower-than-average usage. 23 22 Response to CLF-003(b), Docket No. 26-05-10 (Sept. 3, 2026) (Eversource 2026b). This principle is well established in the cost-of-service and rate-design literature. Bonbright explains that a uniform per-kWh rate, “in treating the total cost of the business as if it varied directly with changes in the kilowatthour output of energy — a grossly false assumption — violates the most widely accepted canon of fair pricing, the principle of service at cost,” because many costs (capacity and customer costs) are not a function of kWh output. James C. Bonbright, Principles of Public Utility Rates (Columbia Univ. Press, 1961), at 304–305, 345–346 (Ch. XVI and XVIII). The NARUC cost allocation manual establishes the foundational framework, classifying transmission and distribution costs as primarily demand-related (varying with kW peak demand, not kWh consumption), so that recovering them through volumetric energy charges violates cost-causation principles. NARUC, Electric Utility Cost Allocation Manual (1992), Ch. 2 §V, Ch. 6. Most directly, the RAP manual identifies this as “essentially a question of a potential intraclass cross-subsidy between types of residential customers” — specifically between electric-heating and non-heating customers — and notes that “seasonally differentiated rates, if based appropriately on cost causation, can achieve the same distributional impact as separate rate classes.” Jim 23 27
  8. Page 30 of 107Match

    1 The Company’s own MCOS witness, Amparo Nieto, addresses how volumetric cost 2 recovery creates cross-subsidies, noting that current rate structure produces “existing cross- 3 subsidies within the class (higher usage customers disproportionally paying more than cost of 4 service)” and recommending that the Company “reduce the over-reliance of fixed distribution 5 cost recovery through usage charges” in order to “increase equity across customers within the 6 class.” 24 (We address the relationship between intra-class cross-subsidies and intra-class equity 7 below.) 8 Q. You’ve established that heat pump customers are overpaying for T&D. Why do these 9 overpayments contribute to a cross-subsidy within the residential customer class? 10 A. The fossil fuel-heated homes that install heat pumps become higher-usage customers, on 11 average, because they effectively shift their largest energy load — space heating — from fossil 12 fuels to electricity. 13 With their significantly higher kWh, volumetric T&D rates lead these customers to pay 14 significantly higher T&D bills — $1,051 more per year, on average (Figure 12). 15 If these higher bills equaled the new T&D costs they were causing after switching to heat pumps 16 — $10 per year — not only would the cost-causation principle be satisfied, but these higher bills 17 would not contribute to a cross-subsidy: their incremental T&D bills of customers installing heat 18 pumps would simply be covering the incremental T&D costs caused by that transition. 19 However, as I have established, heat pump customers are actually overpaying for T&D 20 by $1,040, and this overpayment contributes directly to a cross-subsidy to electric customers that 21 heat with fossil fuels, via the exact mechanism described in the preceding question. Lazar, Paul Chernick & William Marcus, Electric Cost Allocation for a New Era: A Manual (RAP, 2020), §5.2; see also §6.1.2, Ch. 28. 24 Direct Testimony of Amparo Nieto, Exhibit CLP-MCOS-1 at p. 8 (Eversource 2026c). 28
  9. Page 31 of 107Match

    1 Q. Why is the cross-subsidy associated with heat pump adoption a problem that the 2 Authority should address? 3 A. Because it represents a significant violation of intra-class equity, and directly undermines 4 Connecticut’s building electrification policies. I will address each in turn. 5 Q. Why does the cross-subsidy you’ve identified represent a significant violation of intra- 6 class equity? 7 A. While the overpayments heat pump customers experience violate the cost-causation principle, 8 the cross-subsidy they produce violates intra-class equity — the principle that rates should not 9 produce significant cross-subsidies between identifiable groups of customers within the same 10 rate class. 25 11 The Company’s own witness identifies intra-class equity as a foundational rate design 12 objective. Witness Nieto lists “ensuring equitable rates or mitigating intra-class cross-subsidies” 13 as one of “the major ratemaking objectives,” 26 and ACOS witness Nieto identifies “intra-class 14 equity” as a core rate design objective. 27 15 I claim that the cross-subsidy from heat pump to non-heat pump customers represents a 16 significant violation of intra-class equity because it is systematic, substantial, and will continue 17 to grow with electrification. 18 Q. Why is the cross-subsidy from heat pump to non-heat pump customers systematic, 19 substantial, and growing with electrification? The Company shares this definition of intra-class equity as the absence of intra-class cross-subsidies, because MCOS witness Nieto recommends that the Company “reduce the over-reliance of fixed distribution cost recovery through usage charges” in order to both “increase equity across customers within the class” and reduce “existing cross-subsidies within the class.” Exhibit CLP-MCOS-1 at p. 8. 25 26 Direct Testimony of Amparo Nieto, Exhibit CLP-MCOS-1 at p. 5 (Eversource 2026c). 27 Direct Testimony of Amparo Nieto, Exhibit CLP-ACOS-1 at p. 8 (Eversource and Nieto, n.d.). 29
  10. Page 32 of 107

    1 A It is true that under any volumetric rate, some customers will subsidize others. But the cross- 2 subsidy I have identified is not incidental, it is systematic. Installing a heat pump means shifting 3 a home’s largest energy load — space heating — from fossil fuels to electricity. This is a 4 fundamental transformation of a customer’s load shape, and it virtually guarantees that the heat 5 pump customer is now subsidizing electricity customers who heat with fossil fuels. 6 The cross-subsidy is also substantial. Because space heating is the single largest 7 residential energy end use, the overpayment per household is not marginal — it is hundreds of 8 dollars per year. 9 Finally, the cross-subsidy grows with electrification itself. The overpayment is not 10 limited to a few customers making unusual choices — it is a built-in consequence of a retrofit 11 that the State of Connecticut is asking every fossil fuel-heated household to undertake over the 12 next couple of decades. Every household that embraces clean heat by installing a heat pump 13 overpays, and will continue to overpay, for as long as Rate 1 remains structured this way. 14 In summary, the cross-subsidy I have identified is not a random distribution of small 15 over- and underpayments. It is a large and growing flow of excess revenue from one identifiable 16 group of customers to another — a systematic and substantial transfer that grows with every heat 17 pump adopted, at a time when the state is gearing up to accelerate adoption. 18 Q. Is the Company aware that overpayments from heat pump customers contribute to a 19 cross-subsidy within the residential customer class which violates intra-class equity? 20 A. Yes. The Company demonstrates an acute awareness of cross-subsidy risk, from heat pump to 21 non-heat pump customers, as well as in the other direction. But it only explicitly discusses the 22 latter risk, despite the fact that the former is the overwhelming reality under Rate 1. 30

Text of JPV-1.pdf

Extracted from the file · 2 pages · 2,718 characters

1 page match
Words on different pages
Words on different pages

As listed on the current system

Prefiled testimony: 10/21/2026 - Sponsor: TBD / Witness: Juan-Pablo Velez [26-05-10]

This filing on the current system (opens in a new tab)