The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 42 of 52 1 transformer plant required per residential customer is actually larger than the average 2 residential customer’s actual demand. The cost per kVA may also be smaller in any 3 case for a commercial-serving transformer, given the economies of scale of larger 4 transformers. 5 6 Q. Do you agree with Ms. Whited’s proposed reclassification of AMI meters based on customer and demand to be more cost-reflective? 7 A. AMI meters do serve an important role in distribution operations, remote disconnects, 8 and support of demand response programs and tariffs. However, given that AMI meters 9 are practically the new standard in today’s modern utility, and the fact that there is no 10 direct correlation between demand growth and AMI meter need, the cost driver should 11 be the customer additions as in the current ACOS study filed by the Company. 12 V. ADVANCED METERING INFRASTRUCTURE 13 14 Q. Did the Rates Panel submit testimony as part of the Company’s initial filing regarding the proposed Advanced Metering Infrastructure (“AMI”) project. 15 A. No. As part of the Company’s initial filing, Company witnesses Jared Lawrence and 16 Douglas Horton provided testimony regarding the technology and implementation of 17 advanced metering infrastructure, as well as regarding a new cost recovery framework 18 for technology and implementation costs. However, Ms. Whited, on behalf of OCC, 19 recommends that, as part of the AMI implementation, PURA direct the Company to 20 (1) retain hourly interval data from AMI meters in a form suitable for equipment-level 21 aggregation, and (2) in its next base rate case, file an equipment-level allocation study 22 alongside its conventional class cost of service study, so the Authority can compare thePage 45 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 43 of 52 1 results before adopting a new method. 40 Ms. Whited argues that the Company’s 2 demand allocation method for distribution system infrastructure does not reflect 3 localized variance in cost causation. 41 4 Further, Mr. Dauphinais on behalf of CIEC, recommends, to the extent PURA allows 5 CL&P to recover AMI costs, whether through the PBMRP or another mechanism, that 6 PURA reject CL&P’s proposal to allocate those costs on the basis of class distribution 7 revenue and instead, AMI costs should be separately identified and allocated on a cost 8 basis by using the weighted meter cost allocator used in CL&P’s ACOS to allocate 9 Account 370 meter plant. 42 Mr. Dauphinais argues that allocating AMI costs on the 10 basis of class distribution revenue shifts AMI costs to classes whose share of 11 distribution revenue is large relative to the number and cost of their meters, which are 12 primarily the larger commercial and industrial classes. 43 13 Mr. Dauphinais further recommends that PURA direct CL&P to use the same cost- 14 based allocation for the deferred AMI-related O&M expense and stranded AMR meter 15 costs when it seeks recovery of those costs, unless CL&P demonstrates that a different 16 cost-based method is more appropriate. 44 40 Whited at 8, 20-22. 41 Id. 42 Dauphinais at 29-31. 43 Id. 44 Id.Page 46 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 44 of 52 1 2 Q. Do you agree with Mr. Dauphinais’s recommendations regarding allocation of AMI costs? 3 A. For purposes of cost of service analysis, the Company expects that AMI meter costs 4 will be properly classified as customer-related costs, consistent with treatment of meter 5 costs in the allocated cost-of-service study conducted and submitted in this docket as 6 part of the Company’s rate application. The Company’s further expectation is that 7 capital costs and expenses associated with AMI implementation would be collected 8 from customers consistent with allocation of costs allowed in this proceeding for 9 distribution rates or another applicable rate mechanism. While we agree with Mr. 10 Dauphinais in that the classification of costs as customer-related is appropriate, we 11 disagree not necessarily on what the cost-of-service study produces, but that the 12 proposed allocation of such costs and their recovery through the PBMRP, or otherwise 13 as determined by PURA, is appropriate. Please see also the following rebuttal to Ms. 14 Whited’s recommendation. 15 16 Q. Do you agree with Ms. Whited’s recommendation regarding the AMI implementation? 17 A. Similarly, for purposes of cost-of-service analysis, the Company expects AMI meter 18 costs to be properly classified as customer-related costs. The results of the allocated 19 cost of service study serve as a guide to inform the allocation of costs and design of 20 rates. Additionally, there are specific ratemaking requirements and methodologies that 21 perhaps Ms. Whited is not aware of which derive key data from properly classified 22 customer costs in the cost-of-service study. For example, the MMRC calculation forPage 47 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 45 of 52 1 determining the residential Rate 1 customer charge, designated per statute and 2 regulation, requires the use of the cost of a meter, among other customer related costs, 3 in its development. With regard to class cost of service (i.e., revenue) allocation, PURA 4 determines the ultimate allocation of revenue among classes, along with the portion of 5 such revenue attributable to customer charges and to demand charges (which are 6 assimilated through volumetric or demand charges, depending on the class). These 7 allocations do not match precisely to the cost-of-service study and further, the portion 8 of customer and demand revenue within each class do not match precisely the 9 respective customer and demand allocations of costs within the allocated cost-of- 10 service study. 11 Therefore, regarding AMI implementation, the Company disagrees with Ms. Whited’s 12 recommendation. The Company’s expectation is that AMI costs would properly be 13 classified as customer costs, and that capital costs and expenses associated with AMI 14 implementation would be collected from customers consistent with allocation of costs 15 allowed in this proceeding for distribution rates or another applicable rate mechanism. 16 The proposed allocation of AMI implementation costs to each class through the 17 PBMRP would be based on such authorized distribution rate revenue, which notably 18 includes both customer and demand components.Page 48 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 46 of 52 1 VI. OTHER RATE DESIGN 2 3 Q. Please describe the testimony regarding rate design submitted by Mr. Eben Perkins on behalf of the University of Connecticut. 4 A. Mr. Perkins advocates for a Connecticut CPT rate, relying on prior implementation of 5 a CPT at other utilities as a basis for carrying forward a similar proposal into this rate 6 case. 45 It is unclear whether he is a proposing a temporary or more permanent proposed 7 rate design. He also advocates for a change in the rate design itself without specifying 8 whether he is advocating for both such rate redesign and the option to participate in the 9 new rate, regardless of whether a customer ends up paying more or less due to their 10 success or failure to reduce load at the one hour of the month. Most importantly, Mr. 11 Perkins does not consider what costs may be shifted to other customers as a result. 12 The “fixed costs” that he discussed are a reminder that, in the context of the distribution 13 and transmission rates he is seeking to change, the rates we design are for charges to 14 customers for the recovery of fixed costs of the systems they utilize. 46 A change in 15 either distribution or transmission rate structures, especially for the rate classes Mr. 16 Perkins references, would directly implicate the prospect of cost shifting, both 17 intraclass and interclass, among the smaller customers that the Company provides 18 service to. For transmission services, the potential for cost shifting translates to other 19 utilities throughout ISO-NE, and may be shifting costs to CL&P as a result of CPT 45 Perkins at 31-38. 46 Perkins at 29-30.Page 49 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 47 of 52 1 customers in the other jurisdictions referenced by Mr. Perkins. 47 This cost shifting 2 would occur in terms of both cost allocation and the setting of rates for transmission 3 service. A reduction in transmission service load from, for example, a large C&I 4 customer, for one hour of a month would reduce the revenue for service that they take, 5 causing an under-recovery of revenue expected from the rate being charged. Under a 6 CTP rate, a customer could “chase” the hour of the ISO-NE transmission system peak 7 demand for RNS service in order to reduce their billing demand and thereby bypass the 8 obligation to pay for service they receive – shifting those costs to other, smaller 9 customers. It may be likely that such customer uses the transmission system in all 10 hours of the month but that one hour. Although their load in all other hours may be 11 equal to or greater than that of the peak hour load, they may pay little or nothing for 12 transmission service despite taking transmission service in all other hours. 13 Transmission owners construct, maintain and operate the transmission grid to provide 14 firm, reliable service to that customer. The costs of that system do not change – they 15 are fixed. The fixed cost of the transmission grid spread over a smaller load due to the 16 avoidance of demand for one hour will, all else being equal, increase transmission 17 service rates to all customers. 47 Id. at 19-20.Page 50 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 48 of 52 1 2 Q. How much cost shifting and what additional insights can we gain regarding existing CPT rates and participation? 3 A. Given the prevalence of the CPT rate at other utilities advertised by Mr. Perkins, it 4 would be informative to know the extent of avoided transmission charges by customers 5 participating in this type of rate mechanism, and magnitude and extent of service they 6 receive for all other hours. It would also be informative to understand the impacts of 7 cost shifting due strictly to changes in rate design, such as that contemplated by Perkins 8 for CL&P (e.g., due to a change in peak hours; the change in billing units during which 9 transmission rates apply). The answers to these and many other questions would be 10 important to explore in an investigation or consideration for developing such a rate 11 mechanism. 12 While Mr. Perkins is calling for an update to transmission rate design and time-of-use 13 periods, he is centrally focused on a retail CPT rate mechanism. 14 transmission service may be reduced for individual customers; however, the 15 complexity in their development and basis should be unwrapped and understood. It is 16 important to note, unlike the billing of demand charges that occur at the transmission 17 service level and as allocated down to rate classes and designed into rates, the 18 underlying costs of transmission service itself may not be reflected in these allocations 19 or design. The impact of single hour load reduction and avoided charges by an 20 individual retail customer translates to an increase in transmission rates and a shift in 21 who pays for that customer’s transmission service. This concern prompts several 22 questions that need to be addressed regarding the proposed CPT rate. For example, to Charges forPage 51 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 49 of 52 1 what extent should a customer not have to pay for the system they use? For the rate 2 designs advocated, what are the underlying costs, structures and mechanisms that 3 support potential rate designs being advocated? Should transmission service rates be 4 revised from the current single monthly peak demand approach? Should a hybrid or 5 other approach applied in other regulatory jurisdictions be considered for development 6 of wholesale level transmission level service? The Company recommends that PURA 7 not simply adopt the proposals being advanced or direct the Company to develop them 8 without further examination. Rather, PURA should first seek answers to these and 9 other relevant questions and proceed deliberately, ensuring that any resulting directives 10 are informed by a thorough understanding of the issues and their potential implications. 11 12 13 Q. Do you agree with Mr. Perkins’s recommendation that the Company examine time-of-day and seasonal differentiation of distribution demand charges for large customers and propose a tariff supported by class-specific evidence? 14 A. No, we do not. Mr. Perkins has clearly misunderstood the time-of-day provisions of 15 various CL&P rate schedules. The plain meaning of “prevailing time” is for residential 16 customers to simply be aware that the peak period is the same hours, whenever they 17 look at a clock. For non-residential customers, it is simply a matter of understanding 18 that peak hours during EST are different than the peak hours under DST. This was 19 deliberately developed through stakeholder collaboration and in response to customers’ 20 needs, as ultimately authorized by PURA in the Company’s previous distribution rate 21 cases.Page 52 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 50 of 52 1 Although Mr. Perkins is critical of the consultant recommendations, it is important to 2 note that the marginal cost study in this case was commissioned to evaluate and provide 3 initial insight into the marginal costs of the Company’s distribution system. It is the 4 first study of this type that has been conducted for CL&P since pre-restructuring. We 5 have gained new, current insight from this study, and have been able to apply the results 6 in updating current rate designs under current TOU structures, including where 7 distribution and transmission demand charges apply (i.e., rate differentials the 8 Company’s EV TOU rates), and in development of new rate design proposals (e.g., 9 marginal, volumetric marginal costs for Rate 6). This study has also been instrumental 10 in examining efficient pricing by better aligning marginal costs for fixed customer or 11 local facilities costs. Mr. Perkins has blended conclusions or implications from the 12 distribution marginal cost study in arguments related to both distribution and 13 transmission. This study and potential future versions of this study may be relied upon 14 to inform future Distribution rate design; however, the Company cautions the use or 15 application of results or conclusions in transmission rate design. 16 17 Q. Are Mr. Perkins’s recommendations or concerns regarding rate design more appropriately addressed in other proceedings or through other initiatives? 18 A. Yes. First, the Company’s proposed AMI deployment plan is intended to support 19 advanced rate design, including structures like those Mr. Perkins contemplates. 20 Second, the Company must submit proposed TOU rate designs by October 1, 2027, 21 under Public Act No. 25-173 (2025), and those designs will be informed by metering 22 and billing capabilities. Third, the Company expected to participate in a working groupPage 53 of 54
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-RATES-REBUTTAL-1 November 18, 2026 Page 51 of 52 1 from March 2027 through December 2027 regarding front-of-the-meter storage rate 2 design and that may address some of the issues Mr. Perkins raises. Fourth, the ongoing 3 investigation into rate designs for MHD EV facilities is expected to address many of 4 the same issues, including the distribution demand ratchet and more complex time- 5 varying rates. 6 VII. PBMRP Tariff 7 8 Q. Please describe the tariff changes being submitted to address the claims of various parties and intervenors in their rebuttal testimony. 9 A. As discussed in the Company’s Leadership Panel rebuttal testimony (see Exhibit CLP- 10 LEADERSHIP-REBUTTAL-1), the Company is herein submitting a redlined version 11 of the PBMRP tariff (EXHIBIT CLP-RATES-REBUTTAL-2). The purpose of this 12 exhibit is to assist in responding to the claims of the various parties and 13 intervenors. The original version of the PRMRP tariff was submitted by the Company 14 in its Application, in Exhibit CLP-RATES-3. 15 The Company’s initial filing in this proceeding originally anticipated that rate year 16 capital would be reflected in base rates effective July 1, 2027, and that the first F Factor 17 would take place a year later on July 1, 2028. In order to both conform to the design 18 contemplated by the CT Bar, and in order to assure that plant additions included in base 19 rates as a result of this proceeding have sufficient time for review in this proceeding, 20 the Company has modified the PBMRP Tariff to reflect the fact that the F Factor would 21 go into effect on July 1, 2027, commensurate with new base rates in this proceeding 22 and would capture the prospective revenue requirement on plant additions after the base
As listed on the current system
Prefiled testimony: 11/18/2026 - Sponsor: TBD / Witness: EDWARD DAVIS, KIMBERLY R. PARSONS, AMPARO NIETO [26-05-10]