    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 17 of 33 1 proposal is based on selecting an unusual L0 curve type. Both his estimate and mine 2 are similar through 60 years of age but my estimate more accurately reflects the 3 maximum life indicated by a considered interpretation of the statistical data. In contrast 4 as Figure 1 illustrated, the L0 curve selected by Mr. Garrett has an exceptionally long 5 tail and projects that some poles will remain in service beyond 120 years. The L0 curve 6 is very uncommon for utility pole accounts. Mr. Garrett has not identified any other 7 utility for which this curve was used for poles. 8 9 Q. Why do you disagree with Mr. Garrett’s proposed 55-L0 survivor curve for Account 367.00? 10 A. His recommendation presents the same fundamental problem as his L0 selection for 11 poles: an exceptionally long tail that does not reasonably represent the expected 12 retirement characteristics of the property. Mr. Garrett increases the Company’s 13 proposed average service life from 50 years to 55 years and changes the dispersion 14 from R0.5 to L0. The increase in average service life he recommends is driven entirely 15 by changing to an L0 curve. 16 Figure 3 shows the resulting extension of projected survival to advanced ages. Similar 17 to Account 364.00, Mr. Garrett extrapolates a long tail beyond the indications of the 18 historical data. A more reasonable trend from the actual data would extrapolate to a 19 maximum life of close to 100 years. Mr. Garrett’s projection would assume extending 20 the lives of certain assets by an additional 50 years beyond this age, resulting in 21 conductors remaining in service to approximately 150 years of age. I do not believe it
  2. Page 20 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 18 of 33 1 is reasonable to assume that conductors could remain in service for 150 years while 2 continuing to provide safe and reliable electric service to customers. 3 Figure 3: Account 367.00 - Underground Conductors and Devices 4 5 Underground conductors and devices are subject to both physical and functional forces 6 of retirement. In my experience, L0 is very uncommon for this type of property, and I 7 do not consider the extended survival represented by Mr. Garrett’s curve a reasonable 8 prospective expectation. 9
  3. Page 21 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 19 of 33 1 2 Q. Why do you disagree with Mr. Garrett’s proposed 25-O3 survivor curve for Account 373.00? 3 A. I have discussed the problems with the O3 curve in detail in the previous section. 4 Figure 4 below also shows that Mr. Garrett has not considered more recent data for this 5 account. Additional information and analysis, which Mr. Garrett does not appear to 6 have considered, supports the Company’s proposal. The Company began converting 7 its street lighting to LED technology in 2016, resulting in a change in the composition 8 and expected retirement characteristics of this account. The operating characteristics of 9 the newer LED fixtures are also different from the street lighting equipment they 10 replaced. The LED light source cannot be replaced independently, such that 11 replacement of the LED requires replacement of the fixture, and the Company expects 12 LED fixtures to have lives in approximately the 15-year range. 13 Accordingly, additional weight should be placed on the more recent retirement 14 experience. The overall experience band includes substantial experience associated 15 with the older street lighting technology, while the more recent experience increasingly 16 reflects the LED fixtures that will drive future retirements. Therefore, the 2001–2025 17 experience band should be considered along with the overall band when estimating the 18 future retirement characteristics of the account. As Figure 4 illustrates, the more recent 19 experience supports a shorter service life and provides additional support for the 20 Company’s proposed 18-L0 curve.
  4. Page 22 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 20 of 33 1 Figure 4: Account 373.00 - Street Lighting and Signal Systems 2 3 4 5 Q. Why do you disagree with Mr. Garrett’s proposed 52-R0.5 survivor curve for Account 365.00? 6 A. Mr. Garrett’s recommendation extends the projected retirement pattern beyond the 7 maximum life indicated by the life analysis. Both the Company and Mr. Garrett select 8 an R0.5 dispersion, but he increases the average service life from the Company’s 9 proposed 46 years to 52 years. As Figure 5 illustrates, that change extends the tail of 10 his curve beyond the approximately 90-year maximum life indicated by the analysis.
  5. Page 23 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 21 of 33 1 Figure 5: Account 365.00 - Overhead Conductors and Devices 2 3 The historical data for this account does not have a pattern that closely follows a single 4 Iowa curve throughout the observed experience. That limitation makes it particularly 5 important to consider the reasonableness of the entire projected retirement pattern, 6 including its endpoint. My recommendation matches the data better than Mr. Garrett’s 7 through age 40 and declines to 0 percent surviving at the approximate age that the 8 historical data does the same. Moreover, Mr. Garrett’s estimate does not fit the data 9 particularly well for any range, but it does project that assets will survive longer than 10 the maximum life indicated by the historical data.
  6. Page 24 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 22 of 33 1 Company information regarding the actual forces of retirement for this account further 2 supports my recommendation. Reliability and capacity are important drivers of 3 overhead conductor retirements, and the Company has an ongoing program to replace 4 older copper conductor. As conductors reach advanced ages, physical survival is not 5 the only factor affecting whether they remain in service and it is common for utilities 6 to have programmatic replacement of older assets which tend to limit the maximum 7 life of assets in an account. There are several reasons to replace older conductor, 8 including condition, reliability, capacity or other system needs. These considerations 9 further support a retirement pattern that approaches zero surviving at a reasonable 10 maximum life rather than continuing to extrapolate survival beyond the maximum life 11 indicated by the historical analysis. 12 13 Q. Why do you disagree with Mr. Garrett’s proposed 82-year average service life for Account 366.00? 14 A. In my experience, an 82-year average service life is outside the typical industry range 15 for electric utility underground conduit. The Company’s proposed 75-year average 16 service life already recognizes that conduit is long-lived property. Mr. Garrett’s 17 recommendation extends that estimate by another seven years while retaining the same 18 R1.5 dispersion. Figure 6 compares the two curves. 19 approximately one third of the account will be in service more than 100 years and 20 around 15 percent will be in service more than 120 years. These are very long lives, 21 and there is not historical data demonstrating that a large share of assets will be in 22 service for that long. My recommendation is already for a fairly long service life. Mr. Mr. Garrett projects that
  7. Page 25 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 23 of 33 1 2 Garrett has not provided justification for an even longer life. Figure 6: Account 366.00 - Underground Conduit 3 E. Account 370.48 Meters 4 5 Q. What does Mr. Garrett propose for Account 370.48, Meters? 6 A. Mr. Garrett proposes to retain the Company’s Iowa survivor curves and net salvage 7 estimates but remove the shorter-term probable retirement date used in the Company’s 8 depreciation calculation. He instead calculates remaining lives using a mass-property 9 approach. Mr. Garrett acknowledges that the Company currently plans to replace its
  8. Page 26 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 24 of 33 1 existing meters with AMI meters in the short-term 6 but argues that the Company’s use 2 of a probable retirement date accelerates depreciation recovery beyond what is 3 supported by a normal mass-property analysis. He further recommends waiting for the 4 AMI program to progress and actual retirement experience to develop, at which point 5 PURA could recognize shorter remaining lives in a future depreciation study or rate 6 proceeding. 7 Q. Do you agree with Mr. Garrett’s proposed treatment? 8 A. No. His recommendation is fundamentally inconsistent with the prospective nature of 9 depreciation. The purpose of estimating service lives and remaining lives is to forecast 10 when the property currently in service is expected to retire. We should not wait until 11 an expected retirement has occurred before incorporating it into the depreciation 12 estimate. Such a delay could result in the customers of tomorrow paying for the 13 equipment used by the customers of today. If Mr. Garrett believes a mass property 14 approach is most appropriate for the account, he would need to incorporate the planned 15 retirement of meters into his recommended survivor curve and average service life. He 16 did not do so. 17 18 Q. Why should the planned AMI conversion be reflected in the depreciation calculation? 19 A. Depreciation should reflect the period over which the property is expected to provide 20 service. A planned technology replacement can shorten that period even where the 6 See Garrett at 78:15-16.
  9. Page 27 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 25 of 33 1 existing equipment remains physically capable of operating. Obsolescence and 2 management decisions concerning replacement are forces of retirement, just as 3 deterioration and failure are forces of retirement. Mr. Garrett’s proposal would result 4 in future customers paying the unrecovered costs of legacy meters in addition to the 5 cost of new meters. This would be inequitable. 6 7 Q. Do you agree that PURA should wait until the AMI program progresses before recognizing its effect on depreciation? 8 A. No. Mr. Garrett acknowledges that the Company currently plans to replace its existing 9 meters in the short-term, which means he proposes to recover the costs of these assets 10 over a longer time than they will be in service. His recommendation to calculate 11 depreciation without that expected retirement date and to recognize any shortening of 12 remaining lives in a future depreciation study or rate proceeding if the retirement 13 experience develops would defer cost recovery to future customers who will have to 14 pay for retired meters and the new AMI meters. 15 16 Q. Do you agree that PURA should wait until the AMI program progresses before recognizing its effect on depreciation? 17 A. No. Mr. Garrett acknowledges that the Company currently plans to replace its existing 18 meters with AMI meters in the short-term. Nevertheless, he recommends calculating 19 depreciation without that expected retirement date and recognizing shorter remaining 20 lives in a future study or rate proceeding if the retirement experience develops. Mr. 21 Garrett’s approach is not appropriate because it ignores known information concerning 22 the expected retirement of the legacy meters. Historical retirement data cannot reflect
  10. Page 28 of 35

    Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Exhibit CLP-DEPRECIATION-REBUTTAL-1 November 18, 2026 Page 26 of 33 1 a replacement program that has not yet occurred, and waiting for that experience to 2 develop would extend remaining lives beyond the period the meters are expected to 3 provide service. This would leave costs unrecovered at retirement and shift those costs 4 to future customers who are also paying for the replacement AMI meters. 7 Moreover, 5 delaying recognition of the meter retirement date does not avoid the cost; it merely 6 compresses recovery into fewer years and creates a larger future increase in 7 depreciation expense. Recognizing the short-term probable retirement date now more 8 appropriately aligns cost recovery with the expected service period and provides a more 9 gradual recovery. If the AMI program timing changes, the remaining life calculation 10 can be updated accordingly. 11 12 Q. Have other regulators recognized the need to align legacy meter depreciation with planned AMI replacement? 13 A. Yes. There are examples of cost recovery for AMI programs. For example, the 14 Company’s affiliates used a similar probable retirement date and approach in 15 Massachusetts. 8 16 The Florida Public Service Commission addressed Florida Power & Light Company’s 17 meters that were being made obsolete by AMI by establishing capital recovery 18 schedules. Under that mechanism, “the investment and associated reserve of 19 installations facing near-term retirement are separated out as sub-accounts, and the As outlined in Exhibit CLP-AMI-1, the Company is also proposing to securitize stranded meter costs, as permitted by Public Act No. 25-173, Section 10. 8 Massachusetts Order D.P.U. 22-22 (pp.186) 7

As listed on the current system

Prefiled testimony: 11/18/2026 - Sponsor: TBD / Witness: NED W. ALLIS [26-05-10]