Application supplement
Exhibit CLP-ADDITIONS-4 Supplemental 2
Files3
Docket No. 26-05-10 Exhibit CLP-Additions-6 Supplemental Filing October 19 2026.pdf
PDF · 157 KB · 2 pagesText searchable
Download Docket No. 26-05-10 Exhibit CLP-Additions-6 Supplemental Filing October 19 2026.pdfRead the text of Docket No. 26-05-10 Exhibit CLP-Additions-6 Supplemental Filing October 19 2026.pdf
Exhibit CLP-ADDITIONS-4 Supplemental 2.pdf
PDF · 2.1 MB · 77 pagesText searchable
Download Exhibit CLP-ADDITIONS-4 Supplemental 2.pdfRead the text of Exhibit CLP-ADDITIONS-4 Supplemental 2.pdf
Exhibit CLP-ADDITIONS-4 Supplemental 2.xlsx
Excel · 613 KBText searchable
Download Exhibit CLP-ADDITIONS-4 Supplemental 2.xlsxRead the text of Exhibit CLP-ADDITIONS-4 Supplemental 2.xlsx
This spreadsheet is large. Its searchable text keeps the sheet names, column headings and text cells and stops at 300,000 characters, so search may miss words further in. Download the file for every cell and figure.
Part 59 of 78
CD02437:Colony St, Meriden Mixed Use Dev | A developer is rehabbing five existing mixed use buildings on Colony St, Meriden. The buildings will have apartments on upper floors and retail at street level. The buildings are currently fed by the N194 network in Meriden._x000D__x000D_ _x000D__x000D_ The buildings will be all electric for heating, cooling, water heating and cooking. Heating will be a combination of heat pumps and resistance elements. _x000D__x000D_ CD02462:Tilcon NS on Black Rock 11H Sub | Tilcon at Loon Lake Road in Plainville is requesting a new 5 MVA service. They are requesting a primary meter service with one connection point. CD02497:New Service Uline Plainfield | Uline J6 is a new commercial warehouse building located on Plainfield Pike, Plainfield, CT. The current construction design has projected a new load of 2679kW, or 71 Amps, which will be added to circuits 13B10 and 13B21 out of Frybrook 13B substation. Without system upgrades, the existing 13B10 and 13B21 circuits in the area do not have the capacity to support this commercial warehouse. CD02505:Tomasso Loon Lake Rd Plainville NS | Tomasso has purchased 95 areas off Look Lake Road in Plainville. Their plan is to install approximately six buildings for a total estimated load of 21 MVA. CD02522:6A3 New Load Berlin Tpke | A large mixed use development is being built on the Berlin Tpke on the 6A3._x000D__x000D_ Developer provided loads are as follows: club house (110 kVA), hotel or bank (230 kVA), retail (125 kVA), and five apartment buildings (591 kVA each). The total load is 3,420 kVA._x000D__x000D_ The first phase includes the club house (110kVA) and two apartment buildings (591kVA each). _x000D__x000D_ CD02528:74 Broad St– New Service | A new customer will be constructing a new 8-story residential/commercial building at 74 Broad St, Stamford, CT. The building will consist of 280 residential apartment units. Spaces for parking garage, amenities, restaurant will be located throughout the footprint of the building. The total area of the building is 435,269 sf.To serve the building load the customer is requesting a total of (4) 3,000A 120/208V residential services for the base building loads and commercial spaces. The customer’s load letter estimates their demand to be 3.3 MVA.Eversource is required to provide service to customers in its territory upon request and may need to upgrade/extend its facilities to serve the customer. CD02572:Amazon Distribution Warehouse Wtbry | This project is being established to cover the costs associated with providing service to the new proposed Amazon Distribution Warehouse which will be located in the city of Waterbury. The preliminary anticipated load is estimated to be about 9.6 MW. CD02573:Refeed 490 Capital Ave, Hartford | Project CD02573 is established to provide a new Distribution service to the customer, Capital District Energy Commission (CDEC). Currently, CDEC is connected to the Transmission System, but Eversource Transmission project 144531 removes the supply to the customer with a completion date of Q4 2026. This project will determine the distribution design for supplying this customer. CD02614:1700 Asylum Ave Apts NS | Project CD02614 – 1700 Asylum Ave Apartments - is established to provide power to a new customer. This customer has a projected load of 3.76MVA. CD02648:1679 King St, Enfield NS | This project is being established account for the costs associated with a new service. A 420,000 ft2 warehouse is being constructed at 1679 King St, Enfield with cold storage, automation, and robotics for an estimated 8.6 MVA load. The existing electrical facilities along King St do not have the capacity to serve this size load. Also, due to the size of the projected load, 2 circuits will be required to supply the facility. CD02667:Nordic Spa Portland CT | Project CD02667 was established to address a Nordic Spa new service coming on the 21H15 circuit in Portland CT.Part 60 of 78
CD02682:11H77 Contingency Overload NS | The purpose of the project is to address the circuit overload which occurs during contingency with the 7L90 circuit in New Britain. The 11H77 circuit feeds 2,574 customers out of the Blackrock substation in New Britain. During contingency with the 7L90 circuit, the 11H77 circuit picks up the 7L90-72S Zone through the 7L90-92T. This brings the normal rating of the 11H77 circuit to 121% and emergency rating to 87%. CD02721:25 Holy Dr, Newington NS | This project is for a 10 MVA new service. The site is currently supplied by the 4A1 circuit. The 10 MVA load will be supplied by switch gear, fed by the 4A1 and 4A11 from the Newington 4A substation. Both circuits can now supply 5 MVA, but neither can back up the other in contingency. CD02747:1499 Silas Deane Hwy, Rocky Hill NS | CD02747 is created to provide power to an Electric Vehicle (EV) charging station, at 1499 Silas Deane Hwy in Rocky Hill, CT on the 3R03 circuit. The 3R03 circuit does not have capacity to support the requested 2,700 KVA load addition. CD02755:Install New Service & Repl. Swgr | Project CD02755 has been established to address new service to two rehabilitated office buildings in Norwalk. These offices 201 and 101 Merritt 7 will be converted to residential buildings consisting of 150 units in each building for a total of 300 new residential customers. FRNEWSVC:FORECAST PROJECT FOR NEW SERVICE | FORECAST PROJECT FOR BUDGETING NEW SERVICE Distributed Generation DISTRIBUTED GENERATION-L4 CD02167:Endurant, N.Colony Rd, Meriden | This project was established for Endurant Meriden, which is in the Central Division, in the Cheshire AWC, in the town of Meriden.Endurant Meriden is proposing a 4.9 MW battery energy storage system (BESS) at 508A N Colony Road, Meriden CT which is currently fed from the Hanover St 12F44 feeder. This BESS will adhere to a charging schedule to prevent exceeding the thermal limits of any conductors on the Eversource distribution system. A distribution impact study determined that the proposed battery has no negative impact on voltage or thermal violations on the distribution system if the battery adheres to the charge and discharge limits. Peak Load / Capacity-ED Distribution Line Capacity OVERLOADS-SPECIFIC PROJECTSPart 61 of 78
CD01451:Ridgefield 22N Contingency Overload | This project has been established to address the contingency overloads on several circuits at the Ridgefield 22N S/S. This proposal involves the 22N2, 22N3, 22N4 & 22N5 circuits. Substation Project CS00637 was established to create two additional breaker positions at Ridgefield to help alleviate the current overloads at Ridgefield 22N.The 22N2 feeds 1679 customers in the Ridgefield area. The circuit has a peak load of 250A and a summer normal rating of 450A. The 22N2 exceeds it summer normal rating for a 22N A2 bus fault in which the 22N4 & 22N5 loses power and the 22N2 picks up some of their load. The 22N2-2 zone has 815 customers which exceeds Eversource’s 500 customer per zone planning criteria. The 22N3 feeds 1,992 customers in the Ridgefield/Wilton area. The circuit has a peak load of 422A and a summer normal rating of 490A. This puts the 22N3 at 86% of normal load. The 22N3 exceeds it summer normal rating for the contingent loss of the 22N4 or the 22N7. The 22N3-2 zone has 698 customers which exceeds Eversource’s 500 customer per zone planning criteria. The 22N3-91T loop scheme is currently disabled during summer peak periods to guard against overloading the circuit. The 22N4 feeds 1,900 customers in the Ridgefield area. The circuit is currently overloaded with a peak load of 378A and a summer normal rating of 423A. This puts the 22N4 at 89% of normal load and exceeds the 80% of UG summer normal criteria. Project CD01558 was created to resolve the UG issues for the 22N4 and 22N1. The portion of the project to replace 750 AL UG cable between MH#10 and riser pole# 550-23 was halted due to leaking transformers and deteriorated structure in Vault#9. Project CD01810 was created to replace the leaking transformers with a UTC, replace the deteriorated structure and replace the remaining 22N4 cable with 1000 CU. CD02381:Convert 15L46 to 23kV & getaway wor | Bokum 15L is being converted from 27.6kV to 23kv and adding more capacity. CD02440:14R31 ROW Rebuild | CD02440 seeks to address reliability issues and aging infrastructure on the 14R31 ROW near Goshen, CT. The 14R31 circuit is responsible for feeding the 33M1, 33M2, 37J1, & 42J1 circuits, which when combined, serve over 3,100 customers. The identified portion of the 14R31 ROW is comprised of roughly 39,000’ of 3-ph 1/0 ACSR conductor. The identified segment includes 152 poles with an average age of 45 years. The 14R31 ROW has experienced 4 reliability related outages in the last 4 years and has seen multiple instances where the segment of 1/0 ACSR was burnt down due to overload under contingency. CD02459:Bokum 15L12, 15L68, 15L69 23kv geta | Bokum 15L substation is going through an expansion to increase capacity. The station voltage is now 27.6 kV, and this project will convert the voltage to 23 kV. The two existing transformers, 15L-1X and 15L-2X, will be replaced with 62.5 MVA transformers, a third 62.5 MVA transformer (15L-3X) will be added to the bus. All 3 transformers will be 115 kV to 23 kV._x000D__x000D_ The new 15L-3X transformer is on site as well as the 23 kV switchgear, the plan is to energize the new 15L- 3X transformer and build a new duct bank for the 15L12 and 15L68 across Bokum Road and connect the 15L12, 15L68, and 15L69 circuits to their new breaker positions._x000D__x000D_ 15L12 currently comes out of the station at 27.6 kV and gets stepped down to 23 kV through two sets of 3,000 kVA poletop autos on Essex Road. The 15L12 out of the station will be converted to 23 kV and the two sets of 3,000 kVA autos will be removed. The existing getaway cable is 3-1/C 750 kcmil Cu cable in three 3-inch ducts. This cable will be replaced with 1000 kcmil Cu cable._x000D__x000D_Part 62 of 78
The 15L68 is stepped down from 27.6 kV to 23 kV through a 29 MVA auto inside the station and bifurcates east and north. The 15L68 going east over the Connecticut River to the New London District will remain the 15L68. The 15L68 going north to Deep River will become the 15L69. There is no work required outside the fence on the 15L68 circuit other than replacing the parallel 500 kcmil Cu getaway cable going east with 1000 kcmil Cu. _x000D__x000D_ The Bokum 15L substation is in the Madison Area Work Center in the Eastern Region._x000D__x000D_ CD02470:28M1 Contingent Overload | CD02470 seeks to address a contingent overload within the 28M1-2 zone when supporting the 11A53-70S zone. The 28M1 is fed out of Middle River 28M sub in Danbury CT. The 28M1-2 zone is comprised entirely of 336 AAC T.W. beginning at P#1172 and extends until the 28M1-50Z on P#372. The 336 AAC T.W. serves as the primary limiting factor with a normal limit of 460A and an emergency rating of 520A. Under contingency with the 28M1 picking up the 11A53-70S zone, the 28M1-2 reaches 104% of its normal limit. CD02473:11A55 Contingency Overload | This project was created to address a contingency overload created on the 11A55 breaker zone when recovering the 11A51-70S zone. The 11A55 is fed out of the Triangle 11A substation in Danbury, CT. The existing limiting factor is the 500 CU PILC, from MH 2 to riser pole 8491 on Federal Rd, Danbury, CT. This project will investigate solutions to either redistribute load or increase the existing load limit for this zone. CD02513:Uncasville 1Q01 Getaway Overload Pr | The purpose of this project is to prevent a contingency overload on the Uncasville 1Q01 feeder. The contingency overload is caused by a 3.7 MVA load swap between the Williams Street 9L09 feeder and the Uncasville 1Q01 feeder that was requested by Substation Engineering to relieve a capacity issue at Williams 9L substation. This overload will occur on the 1Q01 getaway cable and the downstream OH conductors up to a bifurcation point while picking up the 1Q6 during contingency. CD02618:15L69 Contingency Overload | This project proposes to solve a contingent overload between the Bokum 15L69 circuit and the Haddam 11C12 circuit. A load study showed that the Haddam 11C12 adds a load of 277A and causes the Bokum 15L69 ROW to experience a 120% overload at normal and 100% at emergency. FROVRLDS:FORECAST OVERLOADS BUDGET PROJECT | FORECAST BUDGET PROJECT FOR SPECIFIC PROJECT OVERLOADS VOLTAGE CORRECTION-DK ANNUAL DK1B:MAINTAIN VOLTAGE NEWTOWN | MAINTAIN VOLTAGE ANNUAL NEWTOWN DK1N:MAINTAIN VOLTAGE NORWALK | MAINTAIN VOLTAGE ANNUAL NORWALK DK1S:MAINTAIN VOLTAGE STAMFORD | MAINTAIN VOLTAGE ANNUAL STAMFORD DK2L:MAINTAIM VOLTAGE TORR CLP | MAINTAIN VOLTAGE ANNUAL TORRINGTON DK2M:MAINTAIN VOLTAGE CHESHIRE/N.B. | MAINTAIN VOLTAGE ANNUAL CHESHIRE DK2W:MAINTAIN VOLTAGE WATERBURY | MAINTAIN VOLTAGE ANNUAL WATERBURY DK3H:MAINTAIN VOLTAGE HARTFORD | MAINTAIN VOLTAGE ANNUAL HARTFORD DK4D:MAINTAIN VOLTAGE MADISON | MAINTAIN VOLTAGE ANNUAL MADISON DK4M:MAINTAIN VOLTAGE E Hampton | MAINTAIN VOLTAGE ANNUAL EAST HAMPTON DK4N:MAINTAIN VOLTAGE N LONDON | MAINTAIN VOLTAGE ANNUAL N LONDON DK5T:MAINTAIN VOLTAGE TOLLAND | MAINTAIN VOLTAGE ANNUAL TOLLAND DK5W:MAINTAIN VOLTAGE DANIELSON | MAINTAIN VOLTAGE ANNUAL DANIELSON FRDK:DKCT Projection Forecast Project | DKCT Forecast project Substation Capacity SUBSTATION OVERLOADS-SPEC PROJ CS00364:Falls Village 9A XFMR Reliability | The project eliminates the single contingency load loss (SCLL) conditions for Falls Village 9A, Salisbury 21J, and North Canaan 5L, located in Falls Village, Salisbury, and North Canaan, CT, respectively. CS00365:Bokum 15L Transformer & Reconfig SS | The project converts Bokum 15L substation from a 27.6kV to 23kV and adds a third transformer and switchgear, including primary and secondary line protection.Part 63 of 78
CS00382:Southington 4C Add Transformer | This project adds a third 115-13.8kV transformer rated 62.5MVA to Southington 4C Substation to address potential load growth that could result in future overloading of the existing bulk transformers. CS00383:Hopewell 22R Replace Xfrmr | This project addresses the current and future distribution load growth at Hopewell 22R Substation located in Glastonbury, CT. It replaces the 2X and 3X transformers with the Eversource 62.5 MVA standard. CS00392:Beacon Falls 11N Replace Xfrmr | This project replaces the Beacon Falls substation 1X and 2X transformers with the Eversource 62.5 MVA standard. CS00603:West Side 7A SS Overload | This project addresses substation capacity deficiencies at the 115-13.2kV West Side Substation located in Middletown, CT. CS00636:Saybrook 22D Conversion | To convert both the 22D-1X and 22D-2X from 27-6.kV to 23kV at Saybrook, the taps inside the transformers will need to be changes. This will require draining the oil, changing taps, and refilling oil. The lightning arresters and potential transformers will also need to be removed and replaced. CS00676:UConn System Upgrade #900 | The objectives are to reliably and cose-effectively accommodate the near term and long term UConn peak load forecasts and address asset condition concerns. CS00683:Berlin 6A Incr Capacity | This project will increase the load carrying capacity (LCC) of Berlin 6A substation. It will replace the 52 year-old 46.7 MVA 6A-1X and the 50 year-old 46.7 MVA 6A-2X to increase the substation LCC by replacing them with two 115-13.8kV 62.5 MVA transformers and associated transformer foundations. CS00703:Westbrook 20S Conversion | This project is to support the conversion of Westbrook 20S substation, located in Westbrook, CT, from 27.6kV to 23kV. FROVRLSS:FORECAST PROJ FOR OVERLOAD SUBSTATI | FORECAST PROJECT FOR SUBSTATION OVERLOADS Regulatory Commitments-ED Regulatory Commitments-Other 4.8KV GROUNDING 468601:4.8KV GROUNDING FOR CODE COMPLIANCE | CORRECT GROUNDING ON 4.8KV DELTA EQUIPMENT IN THE STATE OF CONNECTICUT TO BRING TO PRESENT CODE, AS REQUIRED BY DPUC ORDER. TRMSN DISTR RELIABILTY PERFRM CD02192:12J5 - Reliability Improvements | As part of Eversource’s plan to address the worst performing circuits (WPC) in Connecticut, project CD02192 was created to focus on the high impact zones of the 12J5 circuit. CD02193:12J4 WPC - Reliability Improvement | CD02193 focuses on infrastructure replacement to improve the reliability of the 12J4 circuit.The 12J4 is a 13.8 kV circuit out of Mansfield 12J, serving 3143 customers in Ashford and Willington. The 12J4 was ranked #9 on the worst performing circuits list in CT. CD02193 addresses the five high impact zones on the 12J4 where Eversource has experienced outages within the past four years. CD02207:11C14 WPC Reliability Improvement | CD02207 focuses on infrastructure replacement and creating a loop to improve the reliability of the 11C14 circuit.The 11C14 is a 23 kV circuit out of Haddam 11C, serving 3052 customers in Chester, Haddam, Higganum, Killingworth, and Middletown. The 11C14 was ranked #1 on the worst performing circuits list in CT. CD02207 addresses high impact zones on the 11C14 where Eversource has experienced outages within the past four years. This includes aging infrastructure replacement, upgrading conductor sizes to increase reliability and ampacity as well as extensive vegetation trimming.Part 64 of 78
CD02208:15L68 WPC Reliability Improvement | CD02208 focuses on infrastructure replacement and vegetation management, which includes trimming and removals.The 15L68 is a 23 kV circuit out of Bokum 15L in Old Saybrook which is split between the Madison and New London districts and supplies a total of 5,184 customers. The district jurisdictional boundary is the Connecticut River. The 15L68 serves 2,309 customers in the Madison district and supplies the towns of Old Saybrook, Essex, Deep River, Ivoryton, and Westbrook. In the New London district, the 15L68 serves 2,875 customers and supplies the towns of Lyme, Old Lyme, East Lyme, Hadlyme, and East Haddam. The 15L68 was ranked #5 on the worst performing circuits list in CT. CD02208 addresses three high impact zones on the 15L68 where Eversource has experienced outages within the past four years. This includes aging infrastructure replacement, upgrading conductor sizes to increase reliability and ampacity as well as extensive vegetation trimming. CD02213:12Y9 WPC Reliability Improvement | Project CD02213 focuses on infrastructure replacement to improve the reliability of the 12Y9 circuit.The 12Y9 is a 13.8 kV circuit out of the Rocky River 12Y S/S and serves 2,758 customers in Sherman and New Milford. The 12J5 was ranked #7 on the worst performing circuits list in CT. CD02213 addresses four high impact zones on the 12Y9 where Eversource has experienced outages within the past four years. This includes aging infrastructure replacement, upgrading conductor sizes to increase reliability and ampacity as well as extensive vegetation trimming. CD02214:30R8 WPC Reliability Improvement | Project CD02214 focuses on infrastructure replacement to improve the reliability of the 30R8 circuit.The 30R8 is a 23 kV circuit out of the Green Hill 30R S/S and serves 3,791 customers in the Killingworth, Madison, and Clinton areas of Connecticut. The 30R8 was ranked #3 on the worst performing circuits list in CT. CD02214 addresses four high impact zones on the 30R8 where Eversource has experienced outages within the past four years. This includes aging infrastructure replacement, upgrading conductor sizes to increase reliability and ampacity as well as extensive vegetation trimming. CD02215:35L9 WPC Reliability Improvement | Project CD02215 focuses on infrastructure replacement to improve the reliability of the 35L9 circuit.The 35L9 is a 13.8 kV circuit out of the Stepstone 35L S/S and serves 2,234 customers in Guilford, Connecticut. The 35L9 was ranked #9 on the worst performing circuits list in CT. CD02215 addresses two high impact zones on the 30R8 where Eversource has experienced outages within the past four years. This includes aging infrastructure replacement, upgrading conductor sizes to increase reliability and ampacity as well as extensive vegetation trimming. FRTDRP:FORECAST PROJECT FOR TDRP PROJS | FORECAST PROJECTS FOR TDRP PROJECTS Reliability-ED Distribution Line Reliability RELIABILITY IMPROVE-DR ANNUAL DR1B:OH RELIAB IMPROVE NEWTOWN | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL NEWTOWN DR1N:OH RELIAB IMPROVE NORWALK | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL NORWALK DR1S:OH RELIAB IMPROVE STAMFORD | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL STAMFORD DR2L:OH RELIAB IMPROVE TORR CLP | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL TORRINGTON DR2M:OH RELIAB IMPROVE CHESHIRE/N.B | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL CHESHIRE DR2W:OH RELIAB IMPROVE WATERBURY | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL WATERBURY DR3H:OH RELIAB IMPROVE HARTFORD | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL HARTFORD DR4D:OH RELIAB IMPROVE MADISON | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL MADISON DR4M:OH RELIAB IMPROVE E Hampton | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL EAST HAMPTON DR4N:OH RELIAB IMPROVE NEW LONDON | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL NEW LONDON DR5D:OH RELIAB IMPROVE DANIELSON | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL DANIELSONPart 65 of 78
DR5T:OH RELIAB IMPROVE TOLLAND | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL TOLLAND DR5W:OH RELIAB IMPROVE Danielson | OVERHEAD RELIABILITY IMPROVEMENT ANNUAL DANIELSON FRDR:PROJECTION PROJECT DR ANNUAL | PROJECTION PROJECT DR ANNUAL RELIABILITY IMPROVE SPEC PROJ CD02116:Roxbury Rd Reconductoring | CD02116 addresses reliability concerns and aging infrastructure for the 21K2 & 21K3 backbone on Roxbury Rd in Southbury. These circuits both originate at Bates Rock 21K substation and operate at 13.8kV. This segment of double circuit pole line consists of predominately 1970 vintage infrastructure and is responsible for hosting a combined 2250 customers. There have been 3 outages along this segment of the 21K2 and 6 outages on this segment of the 21K3. Additionally, this segment of the 21K3 experienced a burn down due to ringed spacer cable and a lightning strike. The proposed work suggests reconductoring on the 21K2 and 21K3. This work involves reconductoring the 21K2 with 6,800’ of 556 spacer cable from P#S43 to P# S3 and reconductoring the 21K3 with 7,000’ of aerial cable from P#S42 to P# C3798. In addition, the side tap originating at P# S22 will be swapped from the 21K3 to 21K2 circuit creating a complete express for the 21K3 from the station to P#12176. The reconductoring of these segments will increase future reliability and load growth through the replacement of aging infrastructure, existing ringed spacer cable and the installation of upgraded overhead conductor. CD02405:12C4 Equip Conversion and Replace | This project adresses deficiencies on the Enfield 12C4 circuit. Ringed spacer cable was found on N. River St., Whitworth St., and Alden Ave. The project replaces this cable prone to failure. To reduce several large customer zones on the 12C4 feeder, a 4.8kV portion of the circuit will be converted to 23kV to allow for recloser installation. CD02480:30R15-Reconductor 336 ringed SC wit | The 336 AL spacer cable is vintage and is ringed. This area has very poor reliability and has had eleven (11) interruptions over the last four years. Removing the 336 AL ringed spacer cable and installing 477 AL tree wire will improve the performance of this circuit. CD02723:Town Scorecard – Eastern Region | Project CD02723 was established to address the Town Scorecard Initiative which identifies the top 10 SADI and SAFI worst performing towns in Eversource, CT. CD02749:UCONN Health Protection Coord | Project CD02749 was established to address reliability concerns impacting operations at UConn Health in Farmington, CT. The affected infrastructure is served by the 1C01 overhead feeder, which supplies power to several critical facilities, including UConn Health Center, UConn Health Warehouse, UConn Fire Safety Complex, State of Connecticut Medical Examiner’s Office, Town of Farmington Sewer Pumping Station, and various hospital support buildings, such as parking areas and the UConn Health Childcare Center. FRSPRELI:FORECAST SPEC REL IMPROVEMENTS | FORECAST PROJECT FOR SPECIFIC RELIABILTY IMPROVEMENT PROJECTS S/S ELIMINATION-LINE WORKPart 66 of 78
CD00654:Eliminate 4.8 kV 12F-6X Islanded SS | Hanover 12F-6X Substation is located in Meriden, Connecticut, and consists of a single, 5/6.25 MVA transformer that supplies three, 4.8 kV circuits (12F2, 12F4 and 12F5) and 1,793 customers.The 12F-6X transformer and 4.8 kV switchgear was installed in 1957. If the 5/6.25 MVA transformer were to fail, then 1,793 customers would be out of power for +/- 24 hours until a mobile transformer was installed. There are no other 4.8 kV sources in the area that can be used to restore customers.Hanover 12F-6X Substation and much of its associated overhead distribution system is 60+ years old.1,793 customers on 12F-6X will be converted and transferred to new 13.8 kV circuit 12F50 and existing 13.8 kV circuit 12F52. 700 feet of 1000 MCM Cu and 4,900 feet of 556 AL TW will be installed to create the 12F50 backbone. Twenty, single phase, bare copper laterals with six or fewer transformers will be reconductored with 1/0 ASCR TW and converted to 13.8 kV.New recloser loop schemes will be created to split the number of customers per zone to approximately 500. Three new recloser loop schemes on the 12F50 which will be backed up by the 12F44, 12F52 and 12F55. The three loops will employ multiple reclosers creating six zones to limit the customer count. The six zones will have 142, 226, 241, 477, 479 and 550 customers. A new field tie with the 12F49, and an existing tie with the 12F51, will back up the 453 customers in the first zone of the 12F50.The new feeder, 12F50, will take some load from the 12F55 to mitigate a contingency overload condition that exists on the 12F55.A large, 958 customer zone on the 12F52 will be eliminated by creating a new recloser loop with the 12F50. The resulting zones will have 456 and 502 customers.The replacement of the 12F2, 1000 kcmil AL get-a-way cable (500 feet) with 1000 Cu mitigates a contingency overload on the 12F52. FRSSLNWK:S/S Elim-Line Work Forecast Project | FORECAST PROJECTS FOR OVERHEAD WORK TO ELIMINATE SUBSTATIONS. Network Reliability NETWORK XFMR + PROTECTOR REPL CD00412:CL&P Repl Net. Xfmrs Blanket | This project is for replacement of inoperable/condemned/failed network transformers and network transformer protectors. UG CABLE & EQUIPMNT REPLACEMNT CD02229:145 PILC Cable Replacement | Project CD02229 is being established to replace the remaining paper-insulated lead covered (PILC) cable on the South Meadow 145 circuit. This project is part of an overall strategy to address poor performing PILC cable in the underground distribution system. CD02393:NW Hartford 2N18 PILC Cbl Repl | Project CD02393 is being established to replace the 19,803’ of paper-insulated lead covered (PILC) cable on the Northwest Hartford 2N18 circuit. This project is part of an overall strategy to address poor performing PILC cable in the underground distribution system FRUGCBLR:FORECAST PROJECT FOR NETWORK CBL RE | FORECAST BUDGET PROJ FOR NETWORK CABLE REPLACEMENTS UG Network Automation CD01276:New Switchgear for SMH Waterbury | This project proposes installation of a set of 4-way solid dielectric switchgear on the line side of the existing feed to the existing switchgear at St Mary's Hospital 201B.The existing switchgear at St Mary's Hospital 201B is owned by the customer, but operated by Eversource, based on an agreement made years ago. This switchgear must be operated periodically, since both incoming feeders at St Mary's Hospital 201B are network feeders.Procedure NB-150 (in CT) discourages utility employees from operating customer-ownedhigh-voltage equipment. Because it does not own or maintain this equipment, the utility does not know its condition, nor can the utility be responsible for it. Installation of the new switchgear enables the utility to disconnect, test, and ground its system at switchgear it owns and maintains, without the need to access or operate non-utility-owned equipment.Part 67 of 78
CD01537:25 Laurel St Htfd - Automate Svc | The primary electric service at 25 Laurel Street in Hartford consists of two manual PMH-5 switches (309B) which serve seven pad-mounted transformers (3,850 KVA Connected) and 607 customers (586 residential / 21 commercial). The manual switches are fed by two underground feeders (47N9 - normal, 47N7 - alternate) out of Southwest Hartford 47N substation (23 KV).In the past five years, these customers have experienced three feeder outages averaging approximately 150 minutes/outage.This project proposes to automate the service to this location by replacing the manual switches with automatic switches.The expected benefits upon completion of this project include improved reliability and customer satisfaction. CD02059:Man to Auto Tuttle Rd Middletown | This project was established to address the manual switchgear at Tuttle Rd., Middletown. This project will replace one of the two existing PMH-9 switchgear units with a new DSCADA capable PME-9 switch, to be operated as a single unit auto-transfer switch. This proposal will automate 121 customers on Tuttle Rd., Middletown.The preferred feeder is the Westside 7A79 circuit and the alternate feeder is the Westside 7A71 circuit. The 7A71 has the capacity to accept the automatic transfer from the 7A79 without causing overload.This project is part of an overall program to eliminate manual switchgear in order to eliminate the need to manually transfer customers to their alternative source for loss of the preferred source. CD02092:Make 13H93 & 13H94 Non-Network | This project is being established to convert the Noera 13H93 and 13H94 feeders into non-network feeders. This will allow the 13H93 and 13H94 feeders to have multi-grounded primary connections, such as automatic switchgear or line-to-ground connected load, without the exposure of high voltage that can happen if a network feeder were to fault and a network protector failed to open.The Palace Theater 225P and UCONN 256D switchgear are both automatic switchgear that have the Noera 13H94 circuit as the alternate source. Under a separate project, the preferred source to these switchgear locations will become a non-network feeder via transfer to the Freight 11W44 circuit.The scope of this project includes transferring the two existing network transformers on the N185 network from the 13H94 & 13H93 to the Freight 11W43 and 11W76 respectively. This will require extending the 11W76 to manhole 147 on E Main St., a distance of 1,320’. The total load on the N185 network is less than 300kVA. The 11W43 and 11W76 has the capacity to accept the added load without causing overload. CD02107:Switch Gear Autom 21P1 Kirkland Pl | This project replaces a manual PMH 3 pair switch gear, located on Kirtland Place, Meriden, with an automatic PME 5 pair. PMH gear is live front while PME switch gear is dead front and is DSCADA capable offering both safety and operational flexibility.The switch gear is fed by the East Meriden 21P1 and the backup is the 21P4. 121 customers are fed from this switchgear. CD02543:Chelsea Piers Switchgear Isolation | This project addresses single point failures on feeders (Glenbrook 1K08 & 1K18) feeding NBC. A splice failed on the overhead system on Maher Rd causing an outage at the NBC facility during the Olympics. On post event investigation, it was deemed necessary to eliminate single point failures by isolating customer owned switchgear feeding Chelsea Piers with Vista Green 422’s to avoid future failures. UNDERGROUND STRUCTURE ISSUE 101610:REPAIR & REPL OF CL&P UG STRUCTURES | REPAIR & REPLACE MANHOLE AND VAULT (STRUCTURE) ROOFS AND DUCTLINE DUE TO OBSOLESCENCE &/OR WEAR & TEAR.Part 68 of 78
CD01821:Greenwich Ave Structural Upgrade | The Town of Greenwich is planning a streetscape project along Greenwich Avenue where they will reconstruct sidewalks and completely repave Greenwich Avenue from Putnam Avenue to Railroad Avenue. The Town has made it quite clear to all subsurface utility owners that all underground infrastructure must be installed or upgraded as necessary prior to their planned project. After careful review of Eversource’s existing infrastructure, it was determined that 2 manhole enlargements, 4 service box enlargements, and 5 lateral duct banks should be installed given the opportunity described above. The locations that were chosen for manhole enlargements are locations where there is insufficient room to properly splice and rack the three 27.6 kV feeders within the manhole, and to properly support the secondary mains and limited crab joints. The service box enlargements are required for potential service upgrades. The lateral duct bank extensions are required for two purposes. First, these ducts will accept additional or replacement secondary cable as required for network secondary voltage service. Second, each new duct bank will be extended to a side street where there is the potential to install a primary voltage loop cable that may eventually be used to convert the existing network to load loops from the existing open wire overhead distribution system. CD02332:Tresser Blvd Duct Bank | During a new service project, the contractors encountered blocked/ insufficient conduits between MH#700 and MH#731 on Tresser Blvd when trying to tap 1G02 feeder to the customer’s switchgear on Tresser Blvd. Repairs were attempted but to no avail. Furthermore, blocked ducts were encountered in the past in other sections of the duct bank on Tresser Blvd between Canal Street and Elm Street. A more accessible feeder (1G19) was used to complete the new service project. However, the fear is that should the need arise to install cable in this area in the future, it cannot be done because of issues with the duct bank.This project is being initiated to install a new 8-position duct bank along Tresser Blvd between Canal Street and Elm Street to facilitate future needs. CD02511:Manchester Bridge Conduit Replace | The project is for electrical conduit replacement on two Manchester bridges that are over the I-384 highway. The State notified the Civil Engineering team of steel conduit bank deficiencies. CD02580:Stamford Vault 292 Replacement | This project replaces vault #292 which is in the roadway at the very busy junction of North St. and Summer St. in Stamford, CT. An inspection revealed that vault #292 deteriorated extensively. CD02619:Cedar Heights Rd Shallow Duct Bank | This project has been created to address the shallow duct bank that occurred on Cedar Heights Rd in Stamford CT during work performed under CD00728. CD02691:Franklin Drive 1B Duct-bank Repair | This project address the replacement of deteriorated steel conduits that are location within an existing duct-bank with a horizontal 2 x 4 array on Main Street in Torrington, CT. This duct-bank spans the Naugatuck River and is located under the bridge. These conduits presently penetrates through a concrete support structure of the bridge which is adjacent to manholes MH# 9 and MH# 21 and has a span length of 110' with very limited room. The age of the duct-bank is over 65 years old and due to its exposure to a harsh environment, these conduits within the duct-bank have deteriorated to the point of either having large, elongated holes in their perimeter or they have deteriorated to the point of becoming separated into two pieces. Substation Reliability GENERAL MODERNIZATION CS00023:GOODWIN LANE 22 - REMOVE SUBSTATION | This project is to complete equipment removals, environmental monitoring, remediation, and site restoration for the de-energized Goodwin Lane 22 substation located in East Hartford, CT.
As listed on the current system