The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Set OCC-15 Date Issued September 09, 2026 OCC-600 Page 1 of 1 Date Filed: September 23, 2026 Witness: Lavelle A. Freeman and Juan F. Martinez Request from: Office of Consumer Counsel Question: Refer to Exhibit CLP-TSP-3, at 24. Define “stranded load” as used on page 24, including its unit of measurement and the conditions under which load is classified as stranded. Response: Stranded load is defined as mega-watts (MW) of load that is at risk of not being restored following a single failure or emergency event until extensive repairs are completed. Customer load will be classified as stranded when a substation’s forecasted load exceeds its emergency rating, also referred to as Load Carrying Capacity “LCC”. Exhibit CLP-TSP-3, page 24, and this definition, are limited in scope to substation planning.