Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Interrogatory responses

Answers to questions 379, 380, 381, 382, 383

ResponseFiled by Connecticut Light and Power Company dba Eversource Energy11 files
Part of docket 26-05-10Open
  • Electric
Application of The Connecticut Light and Power Company d/b/a Eversource Energy to Amend its Rate Schedules

Files11

Search terms highlighted
Eversource rate increase is on 18 pages across 3 files of the text below, highlighted. Go to the first matchClear highlighting
Words on different pages
Words on different pages
Words on different pages

Text of EOE-381_Final.pdf

Extracted from the file · 2 pages · 3,490 characters

Words on different pagesRead the text of EOE-381_Final.pdf

Text of EOE-382_Final.pdf

Extracted from the file · 1 page · 2,648 characters

Words on different pagesRead the text of EOE-382_Final.pdf

Text of EOE-383_Final.pdf

Extracted from the file · 4 pages · 10,383 characters

Words on different pagesRead the text of EOE-383_Final.pdf

Text of EOE-383 Attachment 1.pdf

Extracted from the file · 125 pages · 401,903 characters

5 pages match
  1. Page 1 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 1 of 182 Report on the Preparation for and Response to the August and October 2011 Storms by The Connecticut Light and Power and The United Illuminating Companies Presented to the: Staff of the Connecticut Public Utilities Regulatory Authority By: 65 Main Street P.O. Box 1237 Quentin, Pennsylvania 17083 [phone removed] (voice) [phone removed] (facsimile) [email removed] (e-mail) April 16, 2012
  2. Page 2 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 2 of 182 Table of Contents Summary of Findings...................................................................................................................... 1 I. Introduction............................................................................................................................. 3 A. Background ......................................................................................................................... 3 B. List of Recommendations ................................................................................................... 3 II. Emergency Plans..................................................................................................................... 7 A. Background ......................................................................................................................... 7 B. CL&P .................................................................................................................................. 8 C. UI ...................................................................................................................................... 24 III. Routine Maintenance and Inspections .............................................................................. 28 A. CL&P ................................................................................................................................ 28 B. UI ...................................................................................................................................... 41 IV. Storm Monitoring and Predicting ..................................................................................... 48 A. CL&P ................................................................................................................................ 48 B. UI ...................................................................................................................................... 49 V. Storm Preparations................................................................................................................ 51 A. CL&P ................................................................................................................................ 51 B. UI ...................................................................................................................................... 57 VI. Emergency Organization .................................................................................................. 59 A. CL&P ................................................................................................................................ 59 B. UI ...................................................................................................................................... 67 VII. Emergency Alerts and Mobilization ................................................................................. 71 A. CL&P ................................................................................................................................ 71 B. UI ...................................................................................................................................... 73 VIII. Recruitment and Deployment of Outside Resources ........................................................ 76 A. CL&P ................................................................................................................................ 77 B. UI ...................................................................................................................................... 81 IX. Damage Assessment and Restoration Status .................................................................... 84 1. CL&P ................................................................................................................................ 84 2. UI ...................................................................................................................................... 91 X. Communications and Outage Information............................................................................ 94 A. CL&P ................................................................................................................................ 96 B. UI .................................................................................................................................... 130 XI. Support Organizations .................................................................................................... 155 A. CL&P .............................................................................................................................. 155 B. UI .................................................................................................................................... 157 XII. Field Restoration............................................................................................................. 158 A. CL&P .............................................................................................................................. 158 B. UI .................................................................................................................................... 169 XIII. Post-storm Activities....................................................................................................... 176 A. CL&P .............................................................................................................................. 176 B. UI .................................................................................................................................... 178 April 16, 2012 The Liberty Consulting Group page i
  3. Page 3 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 3 of 182 Acronym List ACD AMR AWC CCC CE CIS CL&P CSR EDS EEI EMG EOC EPE EPOPS EPP ERP ESO ETR ETT FTE GIS IAP ICC ICS IR IVR MAMA NEMAG NESC NU NU EOG NWS NYMAG OMS PURA RCM RFI ROW SCADA SEE SMS SOC TFCC TL TVM UI VM WCSU April 16, 2012 Automatic Call Distributor Automated Meter Reading Area Work Center Customer Care Center Customer Experience Customer Information System The Connecticut Light and Power Company Customer Service Representatives Electronic Dispatch System Edison Electric Institute CL&P Emergency Management Group Emergency Operations Center Engineering & Project Excellence Emergency Plan Operating Procedures UI Emergency Preparedness Plan CL&P Emergency Response Plan Electric System Operations Estimated Time of Restoration CL&P Enhanced Tree Trimming specification Full-Time Equivalent Geographic Information System Incident Action Plan Incident Command Center Incident Command Structure Infrared scan Interactive Voice Response Mid-Atlantic Mutual Assistance New England Mutual Aid Group National Electric Safety Code Northeast Utilities Northeast Utilities Emergency Operations Group National Weather Service New York Mutual Aid Group Outage Management System Connecticut Public Utilities Regulatory Authority Reliability Centered Maintenance Request for Information Right-of-Way Supervisory Control and Data Acquisition Southeast Electric Exchange Short Messaging Service System Operations Center Twenty First Century Communications Town Liaison Transmission Vegetation Management The United Illuminating Company Vegetation Management Western Connecticut State University The Liberty Consulting Group page ii
  4. Page 4 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 4 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 Summary of Findings The August and October 2011 storms were significant, and the early snowstorm was unprecedented. Liberty found that The Connecticut Light and Power (CL&P) and The United Illuminating (UI) each performed some things well in the preparation for and response to the storms. Liberty also found that aspects of both companies’ performance made worse the severity and duration of the storms’ effects. Liberty concluded that the items listed below were beneficial aspects of CL&P’s performance. 1. CL&P’s systems and methods enabled customers to communicate easily with the company during the storms. 2. CL&P has a superior distribution pole specification and groundline inspection program. CL&P has been purchasing one of the more durable types of poles since the mid-1980s. The percentage of reject poles is low. 3. The CL&P district emergency organization provides the framework to support an effective response. In both storms, CL&P opened and staffed the district commands in good time. 4. CL&P proactively communicated with the media, public officials, customers, and the public before, during, and after the storms. 5. CL&P’s emergency plans provide clear expectation of employee involvement in support activities. This is a very important aspect of any successful response effort. 6. The Classification of Service Outage Events in CL&P’s emergency plans provides helpful guidance in determining the amount of required resources. However, and overall, Liberty found that CL&P’s storm performance was below average. The following lists the most important items in this category. 1. CL&P’s distribution tree trimming program contributed significantly to the extent of 2011 storm damage and the duration of storm service interruptions. CL&P should institute a four-year, full-cycle trim program, a more aggressive overhang trimming process, and a more aggressive hazard-tree removal program. 2. CL&P could not provide restoration estimates or restoration status to customers on a timely basis. CL&P should pursue the technology enhancements that will facilitate realtime updates of restoration status information into the outage system. It should also develop specific, measurable goals and objectives for improving the accuracy and timeliness of outage related information provided to its constituents. 3. CL&P’s implementation of the Incident Command System (ICS) did not set up the strong, top-down management response that is necessary in reacting to major outages. CL&P should modify its storm management structure, placing more direct authority and responsibility at the System, Area, and Division level. 4. CL&P made a determined effort in acquiring outside resources, but the results were disappointing. CL&P should work with EEI and other Mutual Assistance Groups to improve the present process. April 16, 2012 The Liberty Consulting Group page 1
  5. Page 5 of 182Match

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 5 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 5. CL&P management did not have proper control over the “Cut/Clear, Make Safe” work done with the towns. CL&P should work with the towns, other utilities, and emergency agencies to establish specific guidelines as to the work CL&P will do in this effort with the towns. The effect of the storms on UI was not as severe as experienced by CL&P, primarily because of UI’s smaller and more compact service territory. Liberty concluded that the items listed below were beneficial aspects of UI’s performance. 1. UI well organized its response to the two storms. 2. UI proactively communicated with the media, public officials, customers, and the public before, during, and after the storms. 3. UI managed the alert and mobilization processes well in both storms. 4. UI has an aggressive distribution-pole groundline program. 5. UI used automatic meter reading technologies to communicate with installed meters during the storm to confirm restoration status. The most significant aspects of UI’s performance that need improvement were the following. 1. UI could not handle the large volume of customers trying to communicate with the company during the storm. UI should create a call center storm staffing process to facilitate quick ramp-up of call takers during a large outage. It should redesign its call center technology to improve communications with customers during a large outage or storm. Moreover, it should rigorously test call-handling technology, website, and the outage management system to ensure the technologies operate to expectations and specifications. 2. The results of UI’s efforts to procure outside resources were disappointing. UI should affiliate with more than one mutual assistance group and work with EEI and other Mutual Assistance Groups to improve the present process. 3. UI could not provide restoration estimates or restoration status to customers in a timely basis. UI should pursue technology and process enhancements that will facilitate realtime update of restoration status information in the outage system and enable more timely estimated restoration times. 4. UI management did not have proper control over the “Cut/Clear, Make Safe” work done with the towns. It should work with the towns, other utilities, and emergency agencies to establish specific guidelines as to the work to be done in the “Cut/Clear, Make Safe” effort with the towns. 5. Hazard trees contributed to the effects of the storms. The hazard-tree removal budget has not had consistent funding in past years. The current budget rate allows the removal of only very high priority hazard trees. 6. UI tree trims single-phase circuits every eight years. While it conducts some reliabilitycentered maintenance on these lines, the eight-year cycle allows for increased vegetation density that will cause storm outages. April 16, 2012 The Liberty Consulting Group page 2
  6. Page 6 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 6 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 I. Introduction A. Background The Connecticut Public Utilities Regulatory Authority (PURA) contracted with The Liberty Consulting Group (Liberty) to assist its Staff regarding the investigation of the performance of The Connecticut Light and Power Company (CL&P) and The United Illuminating Company (UI) in storms that occurred 2011. Storm Irene, which hit Connecticut on August 28, and an unusual snowstorm at the end of October each caused an interruption of electric service to over 800,000 customers. Restoration of service took up to nine to eleven days. Both CL&P and UI experienced significant damage to their electric distribution systems. This is Liberty’s report to Staff on that investigation. Liberty began its review in mid-December 2011. Liberty interviewed personnel at both utilities, received written responses to requests for information, and relied on the significant amount of information provided by the utilities in response to questions asked by the various parties to this case. Liberty’s team comprised very experienced consultants. Liberty organized its report by the following topics: II. Emergency Plans III. Routine Maintenance and Inspections IV. Storm Monitoring and Predicting V. Storm Preparations VI. Emergency Organization VII. Emergency Alerts and Mobilization VIII. Recruitment and Deployment of Outside Resources IX. Damage Assessment and Restoration Status X. Communications and Outage Information XI. Support Organizations XII. Field Restoration (includes staffing) XIII. Post-Storm Activities The report addresses each of these topics separately for CL&P and UI. B. List of Recommendations This report provides conclusions and recommendations for each utility under the topics listed above. The following is a complete list of Liberty’s recommendations. II-CL&P-1 II-CL&P-2 II-CL&P-3 April 16, 2012 Re-format the EPOPS document into smaller segments to enhance the use of this information during emergencies................................................................ 22 Add language to the “Authority and Policies” subsection of the Basic plan that clearly describes and reaffirms top management’s ultimate authority for and complete support of the response to major outages. ........................................ 22 Include language in Sections 2.2 and 2.3 (safety and environment) that emphasizes a more proactive approach in these areas. .................................... 22 The Liberty Consulting Group page 3
  7. Page 7 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 7 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 II-CL&P-4 II-CL&P-5 II-CL&P-6 II-CL&P-7 II-CL&P-8 II-CL&P-9 II-CL&P-10 II-CL&P-11 II-CL&P-12 II-UI-1 III-CL&P-1 III-CL&P-2 III-UI-1 IV-CL&P-1 IV-CL&P-2 IV-UI-1 V-CL&P-1 VI-CL&P-1 VI-CL&P-2 April 16, 2012 Add language to the ERP to provide guidance for activation/escalation “from the top down” when the situation calls for it.................................................... 23 Change Level V in the Classification of Service Outage Events chart (Section 5.2, page 22, Basic Plan) to cover all outages of 80,000 customers and above. .......................................................................................................................... 23 Add a segment on clean-up activities in Subsections 6 – Post Incident Activities – in the Basic Plan, and Subsections 5 – Post Storm Activities – in the District and Division Plans......................................................................... 23 Place the responsibility for all drills and training with the EMG, and reword Section 2, District Plan, 3.13 to strengthen the process and place more emphasis on the training process...................................................................... 23 Provide specific guidance 3.2, Conference Calls, Section 2, District Plan, as to the frequency and time of day for conference calls. ........................................ 23 Modify the wording in 3.3, District Decentralization, Section 2, District Plan to provide for the activation of Area and Division Command anytime decentralization is being considered. ............................................................... 23 Strengthen the wording in 3.4, Activation and Staffing of the District Incident Command Post, Section 2, District Plan. The wording should provide specific guidelines for triggers of when it should use certain organizational structures. .......................................................................................................................... 23 Revise the ERP to provide for centralized training and drills, and firm up the wording concerning number of required drills................................................. 24 Address aggressively the concerns of the response team concerning the usefulness and use of the plan.......................................................................... 24 Initiate a process for regular updates to the EPP, document the updates, and conduct the necessary training to be sure all responders are familiar with the plan................................................................................................................... 25 Institute a four-year full cycle trim program, a more aggressive overhang trimming process, and a more aggressive hazard-tree removal program......... 35 Verify the condition of the wood cross arms on the system and put in place a program to replace them at a sustainable rate. ................................................. 41 Institute a four-year full cycle trim program and a more aggressive hazard-tree removal program. ............................................................................................. 44 Use a weather vendor that has the confidence of the storm team. ................... 49 Develop a pre-storm resource prediction process. ........................................... 49 Develop a pre-storm resource prediction process. ........................................... 50 Improve the organization, planning, and execution for satellite and staging area setup. ................................................................................................................ 56 Modify the storm management structure and processes to clarify the makeup and role of System Command and place more direct authority and responsibility at System Command.................................................................. 66 Strengthen the Area Command structure with regard to its direct functional control in key areas. ......................................................................................... 66 The Liberty Consulting Group page 4
  8. Page 8 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 8 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 VI-CL&P-3 VII-CL&P-1 VII-UI-1 VIII-CL&P-1 VIII-CL&P-2 VIII-CL&P-3 VIII-UI-1 VIII-UI-2 IX-CL&P-1 IX-CL&P-2 IX-CL&P-3 IX-UI-1 IX-UI-2 X-CL&P-1 X-CL&P-2 X-CL&P-3 X-CL&P-4 X-CL&P-5 X-UI-1 April 16, 2012 Activate the division command posts in all major outage events as set forth in its emergency plan............................................................................................ 66 Develop a checklist for winter storms similar to the one it has for hurricanes and use the event classification levels to guide preparations during the alert phase................................................................................................................. 73 Amend the EPP and change UI’s practice to ensure that it opens the EOC prior to the onset of major events. ............................................................................ 75 Work with EEI and other Mutual Assistance Groups to improve the present process, and work with PURA in an attempt to avoid problems such as the one involving a governor not allowing crews to leave his state. ............................ 80 Adopt an aggressive plan to avoid the mistakes made in Irene and the October snowstorm in requesting outside help. ............................................................. 80 Follow the deployment point process as outlined in the EPP when large numbers of outside resources are incoming. .................................................... 81 Work with EEI and other Mutual Assistance Groups to improve the present process, and work with PURA in an attempt to avoid problems such as the one involving a governor not allowing crews to leave his state. ............................ 82 Join other mutual assistance groups................................................................. 83 Develop a process to use damage assessment information in a statistical manner for overall crew resource-requirement projections. ............................ 90 Improve the damage assessment processes at the district level. ...................... 90 Reinforce aggressively the need for accurate, timely damage and restoration updates from the field....................................................................................... 90 Develop a process to use damage assessment information in a statistical manner for overall crew resource-requirement projections. ............................ 93 Verify that the 2011 EPP adequately covers restoration status updates, and address the issues identified during the two storms. ........................................ 93 Create a call center staffing model to facilitate quick ramp-up and consider staging agents in nearby hotels in preparation for a large storm, especially one that makes travel to the center difficult or unsafe. ......................................... 129 Redesign the interface between the call center technologies and Twenty First Century Communications to improve communications with customers during a large outage or storm...................................................................................... 129 Enhance the Town Liaison program to create a more coordinated and consistent approach to keeping community leaders and municipal officials better informed of storm restoration status. ................................................... 129 Pursue technology enhancements that will facilitate real-time updates of restoration status information into the outage system.................................... 130 Develop specific, measurable goals and objectives for improving the accuracy and timeliness of outage related information provided to its constituents..... 130 Create a call center storm staffing process to facilitate quick ramp-up of call takers during a large outage. .......................................................................... 152 The Liberty Consulting Group page 5
  9. Page 9 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 9 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 X-UI-2 X-UI-3 X-UI-4 X-UI-5 XI-CL&P-1 XII-CL&P-1 XII-CL&P-2 XII-CL&P-3 XII-CL&P-4 XII-UI-1 XII-UI-2 XII-UI-3 XIII-CL&P-1 April 16, 2012 Redesign call center technology to improve communications with customers during a large outage or storm. ...................................................................... 152 Rigorously test call-handling technology, website, and Outage Management System to ensure the technologies operate to expectations and specifications. ........................................................................................................................ 153 Enhance the Municipal Liaison program to create a more consistent approach to keeping community leaders and municipal officials better informed of storm restoration status. ........................................................................................... 153 Pursue technology and process enhancements that will facilitate real-time updates of restoration status information in the outage system and enable more timely ETRs. .................................................................................................. 153 Reduce the number of support functions assigned to Area Logistics. (See also Chapter VI, Recommendation 2) ................................................................... 156 Strengthen procedures for getting regular, timely restoration status updates from crews in the field. .................................................................................. 168 Change the restoration practice in major events such as Irene and the October storm to limit the amount of time crews are moved from one circuit to another until work on the first circuit is completed. ................................................... 168 Assign crews to specific circuits in a major outage event. ............................ 168 Work with the towns, other utilities, and emergency agencies to establish specific guidelines as to the work to be done in the “Cut/Clear, Make Safe” effort with the towns. ..................................................................................... 169 Strengthen the procedures for getting regular, timely restoration status updates from crews in the field. .................................................................................. 174 Change the restoration practice in major events such as Irene to limit the amount of time crews are moved from one circuit to another until work on the first circuit is completed................................................................................. 174 Work with the towns, other utilities, and emergency agencies to establish specific guidelines as to the work to be done in the “Cut/Clear, Make Safe” effort with the towns. ..................................................................................... 175 Revise post-event process to accomplish the mutual goals of senior management involvement and timely completion, and to make the critiques of more value to the response team. ................................................................... 177 The Liberty Consulting Group page 6
  10. Page 10 of 182

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 10 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 II. Emergency Plans A. Background “Plan your work and work your plan,” is never more applicable than with the response of a utility to a major outage event. While all utilities have experience in responding to common outages, a major outage event brings more and greater challenges in both degree and complexity. For any utility to respond appropriately, it must begin with a comprehensive, user-friendly emergency plan. A comprehensive plan addresses all aspects of the response process beginning with pre-event activities, covering all aspects of the restoration, and concluding with the postevent period. It also addresses major outage events other than those related to storms, such as floods, catastrophic facility or equipment failures, overload emergencies, and terrorist activities. In addition to being user-friendly, a plan must be readily accessible to all response employees in both print and electronic format. To provide the intended guidance, response employees must use the plan. Response employees must have a good general knowledge of all aspects of the plan and a verified working knowledge of those sections of the plan dealing specifically with their functional area. To ensure that the employees have this degree of knowledge and are comfortable using the plan, utilities must conduct regularly scheduled drills and training activities. All key responders should be drilled or receive supplemental training at least once per year. Failing to keep the plan updated can have a significant negative effect on their usefulness. Not only does the out-of-date or lacking information cause confusion and lost efficiency, but also the signal sent to the responders is that company leaders do not put a high priority on the plan. A good test of a utility’s commitment to having an outstanding response organization is the quality of its emergency plan, and the resources expended in drilling and training their responders and in updating their plan. This chapter provides a description and evaluation of the emergency plans that Connecticut Light & Power (CL&P) and United Illuminating (UI) had in effect prior to the 2011 storms. Liberty’s objective for the work included in this chapter was to assess the companies’ emergency plans, including the companies’ training and drill procedures for emergency response. The chapter addresses: 1. The adaptability of the plans to address different sizes of events, including a method to categorize events by severity level and to detail activities required for each level 2. The accessibility of the plans to all response personnel 3. The extent to which the plans are user-friendly and provide necessary information in a clear, concise format 4. The extent to which response personnel have a good working knowledge of the plans 5. The comprehensiveness of the plans, covering all phases of emergency response – prevent, restoration, and post-event 6. The extent to which the plans contain recognized utility best practices 7. The frequency, comprehensiveness, and effectiveness of drills and training exercises on the plans and emergency response activities April 16, 2012 The Liberty Consulting Group page 7

Text of EOE-383 Attachment 3.pdf

Extracted from the file · 55 pages · 132,814 characters

Text of EOE-383 Attachment 4.pdf

Extracted from the file · 2 pages · 4,635 characters

Text of EOE-383 Attachment 5.pdf

Extracted from the file · 7 pages · 11,175 characters

As listed on the current system

Question(s) Answered 379, 380, 381, 382, 383 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 10/27/2026

This filing on the current system (opens in a new tab)