Interrogatory responses
Answers to questions 379, 380, 381, 382, 383
Files11
EOE-379_Final.pdf
PDF · 181 KB · 5 pagesText searchable
Download EOE-379_Final.pdfRead the text of EOE-379_Final.pdf
EOE-379 Attachment 1.pdf
PDF · 1.2 MB · 2 pagesText searchable
Download EOE-379 Attachment 1.pdfRead the text of EOE-379 Attachment 1.pdf
EOE-380_Final.pdf
PDF · 96 KB · 3 pagesText searchable
Download EOE-380_Final.pdfRead the text of EOE-380_Final.pdf
EOE-381_Final.pdf
PDF · 89 KB · 2 pagesText searchable
Download EOE-381_Final.pdfRead the text of EOE-381_Final.pdf
EOE-382_Final.pdf
PDF · 86 KB · 1 pageText searchable
Download EOE-382_Final.pdfRead the text of EOE-382_Final.pdf
EOE-383_Final.pdf
PDF · 133 KB · 4 pagesText searchable
Download EOE-383_Final.pdfRead the text of EOE-383_Final.pdf
EOE-383 Attachment 1.pdf
PDF · 1.3 MB · 125 pagesText searchable
Download EOE-383 Attachment 1.pdfRead the text of EOE-383 Attachment 1.pdf
EOE-383 Attachment 2.pdf
PDF · 3.5 MB · 182 pagesText searchable
Download EOE-383 Attachment 2.pdfRead the text of EOE-383 Attachment 2.pdf
EOE-383 Attachment 3.pdf
PDF · 3.5 MB · 55 pagesText searchable
Download EOE-383 Attachment 3.pdfRead the text of EOE-383 Attachment 3.pdf
EOE-383 Attachment 4.pdf
PDF · 715 KB · 2 pagesText searchable
Download EOE-383 Attachment 4.pdfRead the text of EOE-383 Attachment 4.pdf
EOE-383 Attachment 5.pdf
PDF · 730 KB · 7 pagesText searchable
Download EOE-383 Attachment 5.pdfRead the text of EOE-383 Attachment 5.pdf
Text of EOE-381_Final.pdf
Extracted from the file · 2 pages · 3,490 characters
Text of EOE-382_Final.pdf
Extracted from the file · 1 page · 2,648 characters
Text of EOE-383_Final.pdf
Extracted from the file · 4 pages · 10,383 characters
Text of EOE-383 Attachment 1.pdf
Extracted from the file · 125 pages · 401,903 characters
Page 147 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 147 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 • • • • • • The volume of emergency calls from the municipal EOC through municipal liaisons was much higher than anticipated during the storms, making it challenging to communicate with UI’s Storm Center to track and update status of these calls. More than half of the towns served by UI had never opened an EOC prior to the storms. As a result, many of the critical infrastructure priorities had not been coordinated within the municipality and UI’s storm restoration process was new to them. Municipalities expressed a need to have more control on where UI crews would be working within their towns, including the need to coordinate with public works and tree removal crews. ERTs should be provided sooner. Many residents were calling the municipalities because they could not get through to UI’s Customer Care Center and the lack of ERTs, in addition to the inability to access storm information on UI’s website, was making it difficult for municipal officials to answer resident questions. Municipal officers would like more information from UI regarding the location of crews working within their town and information about the circuits that are out. A map with trouble spots would help towns direct police patrols and other services to the right locations. The Municipal Liaison program worked more smoothly during the October snowstorm. Municipal Liaisons had become very familiar with their towns during Tropical Storm Irene— they knew who to work with and how to help. In addition, UI incorporated some changes to the program as a result of the lessons learned following Irene. One important change was to provide towns with a list of the streets where crews would be working the following day. This helped towns better coordinate resources to support the restoration process. Storm Center personnel, Municipal Liaisons, and other UI employees spent considerable effort to gather storm and restoration status information affecting towns so that it could be shared with Towns/Municipalities, the Contact Center, and other stakeholders. UI was also challenged to manage the high volume of emergency calls logged at EOCs and communicated through MLs to the Storm Center (due to Contact Center accessibility issues). The challenge was made more difficult with the difficulties getting through to UI’s Customer Care Center, the lack of ERTs and storm status information, and the need to balance the needs of one town versus many. In addition, many town officials shifted priorities of critical facilities during the storms, making it necessary to shift field resources, further delaying restoration. 4. Communicating Outage Information Traditionally, electric utility customers have called the utility to report problems or interruptions in their electric service. Nearly commonplace now, utilities have embraced the use of Interactive Voice Response (IVR) technology to allow self-service outage reporting via telephone and to allow customers to report outages as well as obtain customer-specific restoration status information from the utility. April 16, 2012 The Liberty Consulting Group page 144Page 148 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 148 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 Additionally, advanced metering technologies and distribution automation are presenting opportunities to identify customer locations that have lost power. Utilities with this level of notification can leverage these technologies during storms and proactively contact customers, especially critical care customers, to let them know that the company knows about the outage, provide the expected restoration time, and preempt a significant number of customer calls and website visits. a. Outage Management Systems OMS (Oracle Network Management System) is a detailed network model of the distribution system. Electrical Connectivity is provided from the Geographic Information System (GIS) that is the source of this network model. The system combines the locations of outage calls from customers, and uses a rules engine to predict the locations of outages. OMS facilitates outage prediction, identification, resource assignment, and restoration reporting. OMS also provides an internal workflow management tool and communication medium to various staff members associated with the restoration effort. OMS is integrated with UI’s SAP Customer Information System (CIS) and provides the outage count information depicted on the UI website. Following Tropical Storm Irene, UI issued a Request for Information (RFI) to several vendors to explore potential OMS technology improvements.221 The following activities can initiate electric trouble orders in the OMS: • Customers calling the company’s call center representatives • Customers self-reporting trouble through the Interactive Voice Response system • Dispatchers can manually create outage orders. OMS’s analyzer module interprets each outage call and creates outage trouble spots that are associated or “tagged” to likely electrical devices, such as a transformer. UI’s distribution electrical connectivity model groups devices using relational database tables that create the link for customers to transformers, transformers to fuses or other protective devices, devices to circuits, and so forth. As new trouble reports arrive, the system continues conditional grouping of devices automatically. OMS also provides tracking of the status of system isolating devices, i.e. switches, breakers and fuses that may be open and which are closed, network-tracing functions can be used to identify customers affected. OMS information is readily available to Call Center Representatives, the Interactive Voice Response system, UI’s website, dispatchers, and any UI field or office employee that has access and has been trained to use the system. Most utilities rely on outbound notification or callbacks to verify that power has been restored. During large outages there are often numerous trouble spots along a single circuit or part of a circuit. As circuits or portions of circuits are repaired, trouble tickets associated with that circuit are closed in the outage system. Power may still be off at a particular location, but since the tickets were closed by the outage system, the utility will not know that power is still off unless the customer calls back (or the utility can ping an automated meter). However, since UI has 221 Response to OCC-324. April 16, 2012 The Liberty Consulting Group page 145Page 149 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 149 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 deployed Automated Meter Reading (AMR) technologies, it has the capability to “ping” a meter to determine if the power is on or off. This capability was used extensively during both storms. This is a much more efficient way to determine service status, since the callback process can be confusing to customers, even anger customers who are still without power after many days, often creating escalated calls in the contact center. UI updated its critical facilities lists on August 27, 2011, just prior to Tropical Storm Irene. The list was updated through the Municipal Liaison program. The Municipal Liaison Team Coordinator meets with municipal officials on an annual basis to review priorities and changes. During an event, the Municipal Liaison will work with town contacts to determine the current status of priority facilities as well as communicate this status to the EOC. The EOC too maintains a copy of these critical facilities by town. This list is referred to as outages occur to identify if a priority facility has lost power. EOC then works through the Planning Team Leader to prioritize damage assessment and restoration priority.222 During Tropical Storm Irene, UI noticed capacity issues with OMS during the storm. For the remainder of the storm, UI limited access to key users to avoid issues. Since the storms, UI has issued an RFI to certain vendors for developing a methodology of integrating technology and process to enhance UI’s restoration processes.223 Otherwise, the performance and reliability of UI’s OMS during the 2011 storms was generally good. OMS performed well to provide trouble spot predictions and track asset conditions as well as predict customers affected. b. Estimated Restoration Times Another role of outage systems is to provide estimates for the time of restoration. Estimated Restoration Times (ERTs) are a critical information component of the restoration process. For day-to-day operations, UI’s outage management system calculates event-level ERTs based on area, order type, and active order volume. OMS uses historical outage records and predefined rules to create an initial ERT for each event. Field personnel can turn off the calculation of eventlevel ERTs at any point. Generally, UI disables ERT calculations during a large storm and did so at the beginning of both storms. UI has the capability to issue four levels of ERT projections—event-level, district, divisional, and global. During both storms, UI delivered a global announcement to customers in the first few days, via the phone system, to let customers know that ERTs would not be available until the damage assessment process was completed. Once damage assessment was complete and UI had a better idea of the level of resources available, UI’s EOC support staff was able to project estimates at the circuit level. As restoration progresses, UI was able to estimate to the feederlevel and ultimately at individual customer locations.224 222 Response to Liberty-57. Response to OCC-141 224 Response to AG-9. 223 April 16, 2012 The Liberty Consulting Group page 146Page 150 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 150 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 OMS is updated by the EOC to provide ERTs and completed repairs. These updates are based on the status of the notification within OMS, which indicates if crews are en-route, on-site, or if the outage has been restored. UI’s IVR attempts to deliver the status and ERTs to customers calling in during a storm, if the system can identify and match the caller to a CIS account.225 Earlier in 2011, UI made a focused effort to improve the process in the field and System Operations Center (SOC) to provide estimates of restoration during “blue-sky” outages and smaller storms. Beginning in June 2011, UI began measuring the frequency with which ERTs were recorded in OMS. This information was reported monthly as a Power Delivery and System Operations metric. Through November 2011, UI achieved an 85.2 percent success rate for reporting ERTs, well surpassing its goal of 75 percent.226 However, UI’s process to update OMS restoration status and provide estimates of restoration during blue-sky or normal outages, was not scalable in both of these storms, for several reasons: • Damage assessment process in large storms relies heavily on mobile patrols. Information collected during the patrols was handwritten, requiring manual entry into OMS. This can be a time consuming process, often delaying the process to project restoration estimates. • Once restoration was underway, restoration information was not updated in OMS, in many cases, until well after the crews were finished for the day. Similar to the field surveys, handwritten trouble order completion information had to be manually reconciled and reflected in OMS, which again can be time consuming and create backlogs. This too can delay the communications of restoration progress. In the post-storm customer research survey conducted following Irene, 91 percent of residential customers surveyed indicated that it was “very important” or “somewhat important” to receive an estimated outage duration when they call UI to report an outage. Of these, 50 percent indicated a preference for “real-time estimates” while another 35 percent preferred a “larger window of time up-front which incorporates unforeseen delays and issues”.227 While in both storms UI based restoration projections on damage patrols and work schedules, in the future UI plans to rely on OMS automation to calculate and provide ERTs up until the restoration crew is on-site. At that point, UI will require crews to provide and/or validate ERTs in OMS.228 UI has identified the need for an OMS upgrade. As part of the upgrade, additional allied projects were identified to enhance internal and external communications, including installing mobile data terminals in damage assessment and line construction vehicles, which would allow for faster communication for damage assessment from the field along with earlier and more accurate knowledge of completed restoration times. On November 1, 2011, UI released a request for information (RFI) to explore options.229 225 Response to OCC-158. Response to OCC-142. 227 Response to AR-Liberty-38-2. 228 Response to OCC-142. 229 Response to AG-9. 226 April 16, 2012 The Liberty Consulting Group page 147Page 151 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 151 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 c. Communicating Outage Information UI has leveraged its public website to provide outage-related information to customers and website visitors through its Storm Center. Customers can review general information on UI’s storm response, emergency preparedness, find out what number to call to report an outage, view a map of current outages, and view a table summarizing customer outages by town. The figure below provides a recent sample from UI’s outage mapping website.230 During the first three days of Tropical Storm Irene, UI received an abnormally high number of hits to its outage map, more than 10x normal hit rates. To alleviate a slowed response, UI took the outage map offline on August 28 and replaced it with a table of affected customers by town, which was manually updated on an hourly basis.231 In addition, UI replaced its normal home page with the outage table for the duration of the storm, thereby making it easy for visitors to view outage restoration progress. While the outage map was ultimately brought back online on August 30, UI continued to feature the outage table on its home page until restoration was completed on September 5. In total, UI’s website logged more than 200,000 page views during Tropical Storm Irene.232 UI’s website continues to feature the outage table today.233 230 uinet.com Response to EL-5. 232 Response to CSU-7. 233 Uinet.com. 231 April 16, 2012 The Liberty Consulting Group page 148Page 152 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 152 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 During the October snowstorm, UI website traffic peaked with 63,871 page views.234 UI did not experience any issues with regard to the outage map during the October snowstorm. The challenges that occurred during Tropical Storm Irene have been reviewed and the Company is implementing technology to address capacity constraints to avoid similar issues in future storms.235 UI used social media channels Facebook, Twitter, and YouTube to disseminate information during the storms. Generally the same information that was posted in media releases and on the website was posted to social media channels.236 UI is exploring ways to improve the outage information communicated through its website, specifically to increase the interactivity to allow customers to explore outage status information by hovering over a particular town on the map. This is part of the request for information for restoration process enhancements and technology that was issued on November 1 2011.237 5. 1. Conclusions UI’s call center was unable to ramp up staffing as quickly as needed to respond to the call volumes encountered during the October snowstorm. The UI Emergency Preparedness Plan, filed with PURA on December 1, 2011, includes a section dedicated to Customer Service. However, UI’s Customer Care Storm Plan does specify how the center will be staffed during an emergency or large storm. 234 Response to CSU-38. Response to OCC-148. 236 Response to CSU-37. 237 Response to AG-9. 235 April 16, 2012 The Liberty Consulting Group page 149Page 153 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 153 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 While UI did fully schedule Customer Care Center resources in advance of Tropical Storm Irene, this was not the case during the October snowstorm. Initially, UI predicted a much smaller storm and the Contact Center staffed the weekend accordingly. However, conditions changed on Saturday and call volumes climbed quickly as customers lost power. CCC management scrambled to call-in additional CSRs, a process that took several hours, and ultimately was not very successful. Still short of staff, management asked for and got volunteers from other departments. However, these employees had to be trained, further delaying the staffing ramp-up. As a result, UI was short staffed for the weekend, when call volumes were very high. Many callers received busy signals, experienced long waits, or abandoned before getting through to the Company. 2. UI customers had difficulties reaching the company to report a loss of power or to inquire about restoration status during both storms. UI did not have any high-volume overflow IVR options in place to accommodate the extremely high volume of customer calls it received in the early stages of these storms. Due to the volume of callers trying to reach UI and the unavailability of overflow options, UI’s telecom trunk capacity (lines into the call center) was exceeded for much of the storms, creating long wait times, a high level of abandons, and busy signals for many callers. Callers wishing to report an emergency situation, such as a downed line or burning wire, had to wait in queue along with other callers, or continue redialing to get through. Unable to get through to UI, many customers called town officials and 911 services. UI’s Storm Center web site experienced unprecedented usage during Tropical Storm Irene. While site access slowed down at several points during the storms, UI was able to temporarily remedy the problems. In addition, the website did not provide estimated restoration times, so customers were forced to call the Company to find out more about the outage. UI had not sufficiently “stress tested” its telephony system, website, or outage system prior to either storm to ensure that it could handle the high level of calls/visits typically encountered in a large storm or outage.238 3. UI’s Communications Storm Plan is incorporated into UI’s Emergency Preparedness Plan. Several subsections of the EPP address emergency communications, communications preparedness, and public communications. Specific elements and processes of the communications plan are referenced in Appendix 4, Liaison and Appendix 3, Public Information. The plan includes lines of authority, roles and responsibilities, procedural checklists, matrices to guide incident-level communications and recommended staffing levels for each storm duty role based on the severity of the storm. Sample communications log forms are also included as well as recommended equipment, tools, and supporting systems, scaled to the storm severity. 238 Response to Liberty-42. April 16, 2012 The Liberty Consulting Group page 150Page 154 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 154 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 4. UI proactively communicated with the media, public officials, customers, and the public before, during and after both storms. As defined in UI’s EPP, Corporate Communications assigned a Communications Manager to the EOC to develop strategies for communication and media-relations activities. UI’s Communications Lead was an active participant in EOC conference calls, and it took control of the “storm message” for the company. When possible, pressed Operations for anticipated restoration times and worked closely with the Municipal Liaison Lead to gather town-specific information. • • • • • UI had adequate pre-storm communications alerting customers to the impending storms and emergency preparedness concepts. UI actively engaged the media and the public throughout the storm to provide storm status and restoration progress. UI took advantage of social media outlets to expand the ways in which the public and customers could interact and communicate with the company. UI conducted post-storm research to better understand customer expectations and satisfaction with restoration performance. UI engaged town leaders and public officials in post-storm meetings to gather feedback and develop lessons learned following the storms. In essence, communications mechanics were in place. However, the extended duration of the restoration efforts and the lack of estimated restoration times inconvenienced and frustrated customers and municipal officials. 5. While UI’s Municipal Liaison approach enhanced communications between towns and the utilities during both storms, there is room for improvement. Storm Center personnel, Municipal Liaisons, and other UI employees spent considerable effort to gather storm and restoration status information affecting towns so that it could be shared with Towns/Municipalities, the Contact Center, and other stakeholders. UI was also challenged to manage the high volume of emergency calls logged at EOCs and communicated through MLs to the Storm Center (due to Contact Center accessibility issues). The challenge was made more difficult with the difficulties getting through to UI’s Customer Care Center, the lack of ERTs and storm status information, and the need to balance the needs of one town versus many. In addition, many town officials shifted priorities of critical facilities during the storms, making it necessary to shift field resources, further delaying restoration. 6. UI did not effectively provide Estimated Times of Restoration (ETRs) to customers in storms. UI suppressed ETR calculations in OMS early in both storms. ETR calculation was not reinstated until several days into the storms, well after the damage assessment was complete and restoration was underway. As a result, early communications were vague, leaving customers and municipal leaders with little information on which to plan. April 16, 2012 The Liberty Consulting Group page 151Page 155 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 155 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 UI’s day-to-day outage restoration process encourages field crews to set ETRs, provide status, and close outage tickets in a timely manner, albeit manually (via radio/phone). However, UI has not been successful scaling this process up during a large storm. UI is currently investigating technologies to improve the flow of outage restoration-status information and ERTs to/from the field. 7. UI successfully used its automated meter reading (AMR) technologies to ping meters to verify restoration status and update OMS. Storm Center personnel used the Utilinet AMR application to communicate with installed revenue meters during the storm to confirm restoration status. This was especially helpful in the later stages of the storm to address thousands of “wire down” trouble tickets received. 6. X-UI-1 Recommendations Create a call center storm staffing process to facilitate quick ramp-up of call takers during a large outage. To be adequately prepared for the high volume of calls into its call center during a large outage, UI should have adequate and experienced agents on hand to respond. UI should be prepared to staff up quickly to be most responsive. UI should develop a call-center resource plan that it can activate during major storms or large outage events, in concert with its current Emergency Preparedness Plan. The staffing model should provide guidelines for adding resources, based on the predicted severity of the event, projected call volumes, the timing, and expected duration. UI should also explore options to automated and expedite the call-in process for CSRs, as well as consider assigning rotating storm duty assignments to ensure that it can adequately staff the Customer Care Center during a storm. UI should also create a process to facilitate the addition of employees from other departments and the Gas Companies to the Customer Care Center, so that these employees can assist with outage calls during peak calling periods. Periodic outage call handling refresher training should be delivered to these employees to minimize the ramp-up lead-time. X-UI-2 Redesign call center technology to improve communications with customers during a large outage or storm. UI must make it easier and quicker for callers to report an emergency, especially during large outages. UI should alleviate telephony capacity restraints so more customers can report outages sooner and eliminate blocked calls (busies).UI should consider outsourcing or offloading overflow to a third-party IVR when call volumes exceed capacity—effectively renting the capacity when needed. Many large investor-owned electric utilities in the U.S. have adopted this approach to handle overflow. April 16, 2012 The Liberty Consulting Group page 152Page 156 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 156 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 Liberty understands that the Company is in the process of researching outsourced IVR technologies and has identified Twenty First Century Communications as a major vendor serving utilities across the country. UI is in the process of working with the vendor to determine next steps to implementing a solution.239 X-UI-3 Rigorously test call-handling technology, website, and Outage Management System to ensure the technologies operate to expectations and specifications. As UI implements options to improve Customer Contact Center telephony it should incorporate stress testing to ensure that the new technologies are working as expected and that UI is delivering a good customer experience. Equally important is the need to make sure the new technologies can handle the high call volumes typically associated with a Level 3 or Level 4 storm. UI should pursue a testing procedure or service to “stress” test call center technologies and supporting outage call handling systems to ensure they are capable of handling the high volume of transactions generated by extremely high call volumes. For example, confirming that OMS operates as desired while receiving and analyzing an extremely high volume of outage tickets. A holistic testing approach will eliminate failures in background systems as well as front-facing technologies, thereby creating a better company response and a better customer experience. X-UI-4 Enhance the Municipal Liaison program to create a more consistent approach to keeping community leaders and municipal officials better informed of storm restoration status. Dedicated Municipal Liaisons and staff at the State EOCs have proven to be very effective. UI should continue to build on the Municipal Liaison program, with a focus on consistency. Each town’s critical infrastructure priorities should be documented and easily identified in the outage management system. UI should develop tools to facilitate better communication between Mutual Liaisons and the EOC. Including tools to communicate crew deployments and outage restoration status. UI should expand post-storm follow-up to capture feedback on the quality of the Municipal Liaison relationship and services provided. X-UI-5 Pursue technology and process enhancements that will facilitate real-time updates of restoration status information in the outage system and enable more timely ETRs. During large outage events, UI should equip its damage assessors and restoration crews (and foreign crews) with mobile data terminals, laptops, or other devices that can communicate and interact with the outage system or develop a real-time process wherein outage information is communicated from the field to a skilled OMS user in a dispatch office, operating center, or other location using cellular telephone, radio, or other communications device. This will improve 239 Response to Liberty-41. April 16, 2012 The Liberty Consulting Group page 153
Text of EOE-383 Attachment 3.pdf
Extracted from the file · 55 pages · 132,814 characters
Text of EOE-383 Attachment 4.pdf
Extracted from the file · 2 pages · 4,635 characters
Text of EOE-383 Attachment 5.pdf
Extracted from the file · 7 pages · 11,175 characters
As listed on the current system
Question(s) Answered 379, 380, 381, 382, 383 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 10/27/2026