Interrogatory responses
Answers to questions 379, 380, 381, 382, 383
Files11
EOE-379_Final.pdf
PDF · 181 KB · 5 pagesText searchable
Download EOE-379_Final.pdfRead the text of EOE-379_Final.pdf
EOE-379 Attachment 1.pdf
PDF · 1.2 MB · 2 pagesText searchable
Download EOE-379 Attachment 1.pdfRead the text of EOE-379 Attachment 1.pdf
EOE-380_Final.pdf
PDF · 96 KB · 3 pagesText searchable
Download EOE-380_Final.pdfRead the text of EOE-380_Final.pdf
EOE-381_Final.pdf
PDF · 89 KB · 2 pagesText searchable
Download EOE-381_Final.pdfRead the text of EOE-381_Final.pdf
EOE-382_Final.pdf
PDF · 86 KB · 1 pageText searchable
Download EOE-382_Final.pdfRead the text of EOE-382_Final.pdf
EOE-383_Final.pdf
PDF · 133 KB · 4 pagesText searchable
Download EOE-383_Final.pdfRead the text of EOE-383_Final.pdf
EOE-383 Attachment 1.pdf
PDF · 1.3 MB · 125 pagesText searchable
Download EOE-383 Attachment 1.pdfRead the text of EOE-383 Attachment 1.pdf
EOE-383 Attachment 2.pdf
PDF · 3.5 MB · 182 pagesText searchable
Download EOE-383 Attachment 2.pdfRead the text of EOE-383 Attachment 2.pdf
EOE-383 Attachment 3.pdf
PDF · 3.5 MB · 55 pagesText searchable
Download EOE-383 Attachment 3.pdfRead the text of EOE-383 Attachment 3.pdf
EOE-383 Attachment 4.pdf
PDF · 715 KB · 2 pagesText searchable
Download EOE-383 Attachment 4.pdfRead the text of EOE-383 Attachment 4.pdf
EOE-383 Attachment 5.pdf
PDF · 730 KB · 7 pagesText searchable
Download EOE-383 Attachment 5.pdfRead the text of EOE-383 Attachment 5.pdf
Text of EOE-381_Final.pdf
Extracted from the file · 2 pages · 3,490 characters
Text of EOE-382_Final.pdf
Extracted from the file · 1 page · 2,648 characters
Text of EOE-383_Final.pdf
Extracted from the file · 4 pages · 10,383 characters
Text of EOE-383 Attachment 1.pdf
Extracted from the file · 125 pages · 401,903 characters
Page 45 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 45 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 With regard to overhang, UI’s specifications require that trees or limbs hazardous to the operation of the line be patrolled and every effort made to remove them. UI added hazard tree removal processes to the vegetation program in 2005. The tree contractor employs Permissions People who identify hazard trees. A different crew comes behind and does the tree takedowns. UI pays for hazard trees on unit rates from a budget separate from that for the cycle trimming. Some large trees are on time and materials rate. Other sources such as customer or local official requests, or UI reliability engineers may identify hazard trees. b. Program Results In the recent past, System Maintenance has been responsible for the vegetation management program. The Line Clearance staff has consisted of one arborist and two Line Clearance technicians. In December 2011, System Maintenance was moved from EPE (Engineering & Project Excellence) to ESO (Electric System Operations). Line Clearance has moved out from under System Maintenance and UI created a new position of Manager, Vegetation Management & Line Clearance. Lewis Tree has had the tree maintenance contract from 2008-2011. They are now on an interim contract for six months while UI negotiates a new four-year contract. Lewis Tree has 19, mostly two-person, crews working. There are three Permissions People and two General Forman. April 16, 2012 The Liberty Consulting Group page 42Page 46 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 46 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 The graph above shows the trim cycle for the past ten years.54 This cycle length is the annual trim-miles divided by the total circuit-miles. Due to the mixed four- and eight-year trim cycle, the cycle length period is high for the tree density. The number of non-storm tree caused interruptions is steady, with a possible upward trend.55 The year 2010 was a more active year in terms of outlier days (both those days that qualified as “major storm” and those days that were slightly below the “major storm” criteria). For 2010, there were about 14.4 tree-caused interruptions per 100 circuit miles. The graph above shows the percentage of non-storm interruptions due to trees.56 Less than 20 percent of all non-storm outages are due to trees. The next graph shows the hazard tree actual expenditures (year 2011 is a budget figure).57 The budget and expenditures have not been consistent. In 2007, UI reduced the budget by $30K due 54 Audit Request AG-14 2011 UI Transmission & Distribution Reliability Report 56 2011 UI Transmission & Distribution Reliability Report 57 Audit Request AG-15 55 April 16, 2012 The Liberty Consulting Group page 43Page 47 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 47 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 to overall budget constraints. It deferred approximately $100K from 2008 into 2009. The 2011 dollars reflect $23K that UI advanced from the 2012 budget. Based on the total circuit miles to be trimmed, the $176K 2011 funding would be about $53 per mile. c. 1. Conclusions Certain aspects of UI’s tree trimming program may have increased the severity of storm damage. UI trims single-phase circuit portions every eight years. While there is also some reliabilitycentered maintenance being conducted on these lines, the eight-year cycle allows for increased vegetation density that will cause storm outages. In addition, the hazard-tree removal budget has not had consistent funding in past years. The budgeted rate of $53 per mile allows the removal of only very high priority hazard trees. d. III-UI-1 Recommendations Institute a four-year full cycle trim program and a more aggressive hazardtree removal program. A more aggressive vegetation management program to reduce overhanging material, increase clearances and remove more hazard trees will improve both storm and non-storm reliability. 2. Wood Pole Maintenance a. Program Overview UI owns and maintains 84,481 wood poles. Starting in 1997, UI inspected poles on a 12-year cycle and continued through 2002. In 2002, the company completed 5,082 pole inspections in the sixth year of the 12-year cycle. In 2003, UI temporarily stopped to evaluate the program. In 2004, UI implemented a new comprehensive inspection and maintenance program as part of an asset management strategy for distribution wood pole infrastructure. In 2004 and 2005, UI completed a visual check and sounding on all UI custodian poles to determine physical condition and to identify deteriorated poles for replacement. In 2006, the Company implemented a new inspection and treatment program over a planned 6-year period. Beginning in 2012, the 6-year cycle will be complete and the pole inspection program will migrate to a 10-year cycle. b. Program Results The graphs below show the number and percentage of poles inspected since 2006.58 UI has been exceeding the 6-year target cycle schedule. 58 Audit Request AG-26 April 16, 2012 The Liberty Consulting Group page 44Page 48 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 48 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 The graph above shows the percentage of poles rejected.59 UI replaced about 44 poles each year in the 6-year cycle program. The reject rates are currently not high enough to be a concern. With a new inspection cycle starting in 2012, the reject rates should be at or below these levels. This graph shows the age distribution of the UI poles compared to the CL&P and AT&T poles.60 The reduced percentage of poles over 40 years old on the UI system is significant. The table below shows the number of wood pole failures during the two major 2011 storms.61 The failure percentages were minimal. Irene Snowstorm Poles Failed 84 17 % Replaced 0.099% 0.020% 59 Ibid Audit Request AG-22 61 Audit Request AG-170 & 171 60 April 16, 2012 The Liberty Consulting Group page 45Page 49 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 49 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 c. 1. Conclusions UI’s pole conditions did not appear to contribute materially to the effects of the 2011 storms. UI recently completed an aggressive six-year ground-line inspection and treatment program to improve the condition of its poles. The maintenance program in place is adequate to maintain the poles in the strength condition required by the NESC. These pole conditions did not contribute materially to the effects of the 2011 storms. d. Recommendations None. 3. Line Inspections & Maintenance a. Program Overview The same contractor, Utility Pole Technology, who does the pole groundline treatment program also performs the overhead circuit-inspection program. This contract was in place from 2009 to 2011. Osmose was the contractor prior to that period. Starting in 2006, the groundline treatment program, and hence the visual inspection program, was on a 6-year cycle. UI completed that cycle and is now evaluating whether to stay on the 6-year cycle or go to a 10-year cycle. The contractor uses a GIS extract loaded in a handheld data unit for the line inspections. It reports all data electronically to the Project Manager of Pole Inspection. They review the data and separate it according to VM, pole replacements, double poles, or repair items. The Line Department receives repair items. The contractor calls in priority items. Inspection entries are in an Access database for tracking. UI does not enter or track repair schedules. In addition to this line inspection, an infrared inspection is included in the Reliability Centered Maintenance (RCM) Program. UI inspects three-phase main lines and three-phase fused side taps annually. Single-phase fused side taps off main lines are on a performance basis. UI inspects bulk substations semi-annually and distribution substations annually. Internal work crews in the Test Department conduct an annual IR inspection of the three-phase portions of the circuits. The survey is a ride-by in a van. They are able to identify and capture some defective items as they ride by. They send the results to a contracted Maintenance Engineer. They forward the repair items to the Line Department by either calling or e-mail. There is no database of the repair or hot spot items logged. b. Program Results Similar to tree interruptions, the number of overhead equipment interruptions during non-storm periods is a general indication of the ability of the system to weather storm events. These data are April 16, 2012 The Liberty Consulting Group page 46Page 50 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 50 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 in the graphs below.62 The number of interruptions appears to be holding steady. The percentage of the total interruptions shows a steady decline. UI replaced 165 broken crossarms during Irene. Due to the amount of large conductors and the covered tree wire conductors it uses, some of this type of breakage is to be expected. c. 1. Conclusions UI’s overhead circuit conditions did not appear to contribute materially to the effects of the 2011 storms. A program for inspection and repair of defective items is in place and had held the number of non-storm overhead equipment caused failures steady. The amount of cross arms replaced during the storms also appears to have been reasonable for the conditions experienced. d. Recommendations None 62 2011 UI Transmission & Distribution Reliability Report April 16, 2012 The Liberty Consulting Group page 47Page 51 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 51 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 IV. Storm Monitoring and Predicting A. CL&P 1. Weather Monitoring Initial storm response begins with weather monitoring. It is an industry best practice to use a professional weather service to provide custom impact reports for the system. Telvent Corporation provided weather forecasting services for all Northeast Utilities companies, including CL&P.63 In addition to Telvent, CL&P also relied heavily on the forecasts from the National Weather Service (NWS), National Hurricane Center. These services were an input used by CL&P management in determining the appropriate readiness actions. CL&P started weather monitoring conference calls with their storm team four days64 in advance of Irene and one day in advance of the snowstorm.65 The Director - System Operations provides the weather forecast information to the CL&P storm organization. They provided two electronic weather reports each day. The weather forecaster will normally sit in on all conference calls where they anticipate the storm level to be level three66 or above. Telvent participated in conference calls with the Division Coordinators for the 2011 storms. The storm team is able to ask Telvent “what if” questions and other forecast questions. The storm team went through preparedness checklists on these calls. The CL&P storm team also had a conference call with the NWS on Thursday before the snowstorm, which occurred on the following Saturday. The CL&P storm team did not express full confidence in the Telvent forecasts. Some of the interview comments were: • Suspect that Telvent is being overly conservative or aggressive when their forecast is compared to other forecasts • They missed it • Telvent needs to have a better understanding of the damage to company facilities done by certain weather events. • Telvent has disappointed three times – “three strikes and you’re out.” Need to have conversation with the weather provider • Not comfortable with Telvent at this time. 2. Predicting Resource Requirements Based on a detailed weather forecast, it is an industry best practice to use the forecast for estimating damages and predicting resource requirements. The CL&P ERP does not specifically address a process/system to predict damage.67 Prior to tropical storm Irene, CL&P reviewed the 63 Audit Request EL-3 Audit Request EL-1 65 Audit Request EL-13 66 A level-three storm event is a serious event affecting less than 40,000 customers. 67 Audit Request Liberty-22 64 April 16, 2012 The Liberty Consulting Group page 48Page 52 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 52 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 historical restoration information from Hurricane Gloria. During the review, CL&P personnel discussed the safety record, damage, resources, duration, and other issues that it had to address during the restoration. Tropical storm Irene and Hurricane Gloria had similar paths and wind speeds. CL&P used Gloria as a gauge to predict the damage from tropical storm Irene. The snowstorm was unprecedented and the lead-time was much shorter. CL&P did not have a prior storm to use as a gauge for damage prediction. 3. 1. Conclusions The CL&P storm team lacks confidence in the present weather vendor. A competent professional weather vendor is critical to the initial storm response. A good forecast allows the utility to prepare properly for the event. CL&P does not have confidence in the present NU weather vendor. 2. CL&P does not have a pre-storm resource prediction process in place. CL&P used past storm history for estimating resource requirements. This process is crude and inaccurate. NU is working with the University of Connecticut’s School of Engineering to develop a predictive weather damage model. The development of this tool is currently in progress. The tool, when completed, will allow NU to better prepare itself for forecasted inclement weather by predicting the amount and area of damage the infrastructure will sustain. 4. Recommendations IV-CL&P-1 Use a weather vendor that has the confidence of the storm team. CL&P and NU should either address and correct the issues causing a lack of confidence or use a vendor that will have the confidence of the CL&P storm team. IV-CL&P-2 Develop a pre-storm resource prediction process. A pre-storm damage and resource prediction model is necessary for proper storm planning and deployment. B. UI 1. Weather Monitoring Western Connecticut State University (WCSU) provided daily weather forecasts to UI.68 They provided a morning and afternoon forecast. UI has used WCSU for several years and is pleased with its performance. UI also used the National Hurricane Center as a source of information as to the potential impact on its service territory and other areas along the eastern seaboard. WCSU 68 Audit Request EL-2 April 16, 2012 The Liberty Consulting Group page 49Page 53 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 53 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 provided an impact warning for Irene to UI six days in advance. UI began weather briefings with the storm team five days in advance. In the snowstorm, UI began weather briefings on Thursday, two days before the storm occurred. The UI Incident Managers held private calls with the weather service vendor. The vendor did not participate on storm team conference calls. Based on early weather forecasts, UI began planning for a level one event (minor) on Thursday, then upgraded to level two event (significant) on Friday, and level three event (extensive) on Saturday. 2. Predicting Resource Requirements UI does not have a predictive resource requirements model.69 UI predicted the level of the storm based on a matrix in the EPP. The matrix listed only basic information on resources such as whether any outside mutual assistance is required and which system processes should be activated. 3. 1. Conclusions UI had a weather-monitoring vendor in place. Western Connecticut State University (WCSU) provided daily weather forecasts to UI. UI has used WCSU for several years and is pleased with its performance. 2. UI does not have a pre-storm resource prediction process in place. UI does not have any process in place for pre-storm estimating of resource requirements. It must therefore make mutual assistance resource decisions based solely on experience and a feel for the storm. This method leads to varying degrees of accuracy. 4. IV-UI-1 Recommendations Develop a pre-storm resource prediction process. A pre-storm damage and resource prediction model is necessary for proper storm planning and deployment. 69 Interview #6, 1/19/12 April 16, 2012 The Liberty Consulting Group page 50Page 54 of 182
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued October 13, 2026 EOE-383 Attachment 2 Page 54 of 182 Report on the Response of CL&P and UI to Storms in August and October 2011 V. Storm Preparations A. CL&P 1. Preparation Actions – Storm Irene Once CL&P receives a weather alert or forecast, it starts the process of pre-storm planning. Prestorm planning activities are numerous and often hectic. Liberty categorized and reviewed the pre-storm planning activities in three overall groups: • Triggering necessary storm plan support functions and processes • Achieving full readiness status of field response personnel • Pre-storm resource deployment and planning CL&P followed the preparation activities70 described in its ERP, Section 1-Basic Plan, page 10: 4.0 Preparedness Activities and Section 2-District Plan, page 10: 3.1 Preparedness Activities. a. Triggering of Storm Plan Support Functions CL&P conducted the following activities involving storm-plan support functions:71 • Developed and updated contact lists for state and municipal officials. • Determined numbers of support personnel necessary to supplement the emergency response positions. Support resources included patrollers, analyzers, wire guards, food/lodging, town/customer liaisons, stores, facilities, transportation, media, crew guides, and satellite teams. • Checked with Stores personnel and verified material availability. Stores reviewed material inventory based on the damage from hurricane Gloria. Stores also notified suppliers that it might need additional “on-demand” deliveries. • Ensured environmental support was available for oil spill response. The NU Environmental Department opened their EOC. • Ensured the Account Executive and communications groups were in place to support external communications to life support customers, state/local governments, priority customers, and media. • Conducted a training course for new wire guards. While CL&P successfully organized on relatively short notice, the substance of the training proved to be less than optimal. • Requested NU EMG to assign CL&P a dedicated project manager from Base Logistics. Base Logistics is the contractor responsible for establishing and maintaining large-scale staging areas and satellite facilities for the Company. • Food & Lodging secured 5,745 hotel rooms and the required meals for incoming mutual aid and contractor crews. • Transportation made a schedule for on-site fueling at each work location. 70 71 Audit Request AG-1 Audit Request AG-95 and EL-1 April 16, 2012 The Liberty Consulting Group page 51
Text of EOE-383 Attachment 3.pdf
Extracted from the file · 55 pages · 132,814 characters
Text of EOE-383 Attachment 4.pdf
Extracted from the file · 2 pages · 4,635 characters
Text of EOE-383 Attachment 5.pdf
Extracted from the file · 7 pages · 11,175 characters
As listed on the current system
Question(s) Answered 379, 380, 381, 382, 383 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 10/27/2026