Platte River Power Authority
Beneficial Buildings Electrification
Forecast
FINAL
Submitted by Apex Analytics, LLC
March 12, 2022
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 2 of 45
Table of Contents
Executive Summary ............................................................................................................................... 4
Decarbonization Context ...................................................................................................................... 4
Study Objectives.................................................................................................................................... 4
Study Findings ....................................................................................................................................... 5
Recommendations ................................................................................................................................ 7
Project Background and Objectives ...................................................................................................... 8
Decarbonization Context ........................................................................................................... 8
Objectives .................................................................................................................................. 8
Definitions ............................................................................................................................... 10
Approach ............................................................................................................................................. 13
Overall approach ..................................................................................................................... 13
Scenario Definitions ................................................................................................................ 15
Forecasting Caveats and Sources of Uncertainty .................................................................... 16
Measure Characterization Results ...................................................................................................... 17
End Use Fossil Fuel Consumption Estimates ........................................................................... 17
Measure Selection ................................................................................................................... 19
Extreme Cold Temperature Frequency ................................................................................... 20
Heat Pump Operating Economics............................................................................................ 22
Measure Unit-Level Impacts ................................................................................................... 24
Measure-level Forecast Impacts ......................................................................................................... 25
Building Electrification Equipment Penetration Forecasts...................................................... 25
Building Electrification Equipment Stock Forecast.................................................................. 29
Building Electrification Impacts by Measure ........................................................................... 32
Forecast Overall Building Electrification Impacts ............................................................................... 34
Energy Forecast ....................................................................................................................... 35
Summer Peak Demand Forecast ............................................................................................. 36
Winter Peak Demand Forecast ................................................................................................ 37
Carbon Reduction Forecast ..................................................................................................... 37
Monthly and Hourly Load Shapes ........................................................................................... 38
Load Flexibility and Demand Response ................................................................................... 40
Load and Temperature Relationship ....................................................................................... 41
Distribution System Impacts ................................................................................................... 42
Conclusions, Recommendations, and Next Steps ............................................................................... 42
Conclusions.............................................................................................................................. 42
Recommendations .................................................................................................................. 43
Future Work ............................................................................................................................ 43
APEX ANALYTICS
Page | 2
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 3 of 45
Appendix A: Spreadsheet Data Appendices ............................................................................................... 44
APEX ANALYTICS
Page | 3
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 4 of 45
Executive Summary
Decarbonization Context
Cities and states across North America, including Fort Collins, Longmont, and the
state of Colorado, have set out ambitious decarbonization goals, which include
these three major elements with large impacts on the electricity grid:
1. Decarbonize the electric grid – increase the share of carbon-free generation.1
2. Electrify transportation – run cars, trucks, and buses on decarbonized
electricity.2
3. Electrify buildings – switch gas heating, hot water, cooking, and other end
uses to using decarbonized electricity.3
Study Objectives
The goal of this study was to provide Platte River decision makers with data- driven
insights to understand the range of impacts of future beneficial building
electrification:
Electricity
Consumption
Increase
Natural Gas
Consumption
Decrease
Winter Peak
Demand
Summer Peak
Demand
Monthly
Energy and
Demand
1
PRPA’s latest IRP includes substantial decarbonization of the electricity system by 2031.
2
Transportation electrification is being forecast under a separate study.
3
Hourly Load
Impact
Shapes
The member cities of Longmont and Fort Collins have started studying building electrification system/customer/
participant impacts along with program design considerations. Report to be made public in spring 2022.
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 5 of 45
Study Findings
Key Finding 1: Only minor impacts on overall electricity consumption are expected
through 2030. Starting in 2030s, building electrification impacts are large.
Forecast Annual Electric Energy Increase
1,000,000
900,000
Annual Electric Energy Inrease (MWh)
800,000
700,000
600,000
500,000
400,000
300,000
200,000
100,000
Low
Mid
2046
2045
2044
2043
2042
2041
2040
2039
2038
2037
2036
2035
2034
2033
2032
2031
2030
2029
2028
2027
2026
2025
2024
2023
2022
0
High
In each of the plots, Low, Mid, High refer to three modeled adoption scenarios:
Low: Assumes significant rebate program and promotion
Medium: Adds code requirements for all new central air conditioners be heat
pumps in 2025 in new construction and 2028 in existing buildings.
High: Adds requirement for all new construction being all electric after 2030.
APEX ANALYTICS
Page | 5
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 6 of 45
Key Finding 2: Summer peak demand impacts are minimal. Load factor improves
until switch to winter peaking occurs.
Summer Demand Increase (MW)
Forecast Summer Demand Increase
1,200
1,000
800
600
400
200
0
Low
Mid
High
Key Finding 3: Full electrification of heating during extreme cold will cause Platte
River to become winter peaking sometime after 2035.
Key Finding 4: Policies requiring all-electric new homes and/or businesses could
push impacts sooner – winter peaking will occur within ~5-10 years of requiring allelectric new homes.
Forecast Winter Demand Increase
Winter Demand Increase (MW)
1,200
1,000
800
600
400
200
0
Low
APEX ANALYTICS
Mid
High
Page | 6
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 7 of 45
Key Finding 5: Electrifying residential space heating with heat pumps is the highest
impact building electrification technology.
Sector
End Use
Residential
Space Heating
Water Heating
Cooking
Whole Building
Space Heating
Cooking
Water Heating
Commercial
2040 Annual
Electricity Impact
(MWh)
296,480
17,300
2,063
45,886
94,508
6,558
4,926
Percent of
Total
63%
4%
0%
11%
20%
1%
1%
While the building electrification forecast scenarios all show substantial grid
impacts, there is also the possibility that program efforts to stimulate market
adoption included in the low case do not occur or do not succeed.
Key Finding 6: Partial electrification of heating improved load factor.
Key Finding 7: Full electrification of heating causes significant cost and reliability
impacts.
Key Finding 8: Without program or policy support, or significant changes to heat
pump technology, efficiency, and economics, only limited building electrification will
occur.
Recommendations
Recommendation 1: Incorporate building electrification into forecasts.
Recommendation 2: Be prepared to advise policy makers on large grid
impacts of electrification of new and existing homes.
Recommendation 3: Revisit forecast during each IRP to incorporate adoption
rate of heat pumps, changes in city codes and policies.
APEX ANALYTICS
Page | 7
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 8 of 45
Project Background and Objectives
Decarbonization Context
States and cities across North America have set ambitious decarbonization goals,
which are now being turned into policy, including decarbonization objectives for the
electric grid, transportation, and buildings. Building decarbonization across the
continent has focused on two parts: energy efficiency4 and electrification. In its
most recent long term Integrated Resource Plan (IRP), Platte River Power Authority
(Platte River) forecasted a dramatically reduced carbon footprint from its generation
portfolio, achieving over 90% decarbonization by 2031. Given the reduced carbon
intensity of its generation portfolio, Platte River and member communities have
identified the opportunity for electrifying buildings to further reduce end-point fossil
fuel consumption and associated greenhouse gas emissions. Further, member
communities are also developing action plans and committing themselves to even
deeper reductions in fossil fuel consumption and have identified building
electrification as one of the key solutions to achieving this goal.
Objectives
Platte River, as part of resource planning efforts, sought to understand the longterm impacts of building electrification on the Platte River electric system. In the
context of this study, building electrification refers to the increased electricity load
in homes/buildings from customers’ conversion from fossil fuels (natural gas,
propane, or other) to electric power for existing and new homes/buildings. The
study covers residential and commercial customers being served by Platte River’s
owner communities of Fort Collins, Longmont, Loveland, and Estes Park, Colorado.
The goal of this study was to provide Platte River decision makers with data driven
insights to understand the range of impacts of future building electrification on
Platte River’s system. Additionally, this study sought to address the impacts of
various policy scenarios that could increase building electrification adoption rates.
This effort was also an extension of the residential building electrification study
Apex conducted for member cities Fort Collins and Longmont.5
Building electrification presents both opportunities and risks to ratepayers, Platte
River Power and its associated utilities as shown in Table 1 below. The risks and
opportunities identified below were one of the primary drivers for Platte River to
conduct this study.
4
Platte River and member communities have successful programs promoting energy efficiency.
5
The study excluded industrial processes.
APEX ANALYTICS
Page | 8
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 9 of 45
Table 1. Building Electrification Opportunities and Risks
Entity
Opportunities
Utility and
Program
Administrator
Ratepayers
and
Participants
•
•
•
•
•
•
•
Risks
Increased electricity sales
New load flexibility grid
benefits
Environmental benefits
Saving money on energy
services
Improved comfort6
Environmental benefits
Jobs
•
•
New peak loads
Customer distrust of new
technologies
•
Increased peak demands
leading to increasing rates7
Failure of critical life/safety
infrastructure8
•
In order to understand the impacts of building electrification, Platte River developed
a detailed list of study objectives. The locations of the results of these study
objectives can be found in Table 2 below.
Table 2. Summary of the Building Electrification Study Objectives and Report Location
Category
Objective
Location
Measure-Level
Electricity Impacts
Measure-Level
Electricity Impacts
Measure-Level
Electricity Impacts
Annual Electricity Impacts
Report Section 4.5
Peak Electricity Impacts
Report Section 4.5
Load shapes in 12x2x24 format
Measure-Level
Electricity Impacts
End Use Load shapes for heating, hot
water, laundry, cooking in 12x2x24
format
Temperature relationship of peak
impacts (e.g., peak load as f(hourly
temp, last 12 hours temp, last 48
hours temp))
Incremental cost of equipment in
different applications (Replace on
burnout (ROB)/Retrofit (RET)/New
Construction (NEW))
Fuel Savings
Data Spreadsheet
Appendix: BE EE Stock
Hourly Forecast
Results_2022-01-18.xlsx
Data spreadsheet Appendix:
Forecast Model Results.xlsx
Measure-Level
Electricity Impacts
Measure-Level
Costs and Benefits
Measure-Level
Costs and Benefits
Report Section 6.7
Data Spreadsheet
Appendix: Forecast Model
Results.xlsx
Report Section 4.5
6
Heat pumps installed for heating in homes without existing central air conditioning receive a significant cooling
comfort benefit.
7
In most of the country, adding central air conditioning loads has increased rates, because they increase peak
demand more than annual energy consumption. The same risk is possible for some electrification measures,
especially when the system peak starts occurring in Winter???.
8
Reliance on electricity alone for heating can be problematic in the event of generation outages or derates which
could result in rolling blackouts and lead to frozen pipes or worse.
APEX ANALYTICS
Page | 9
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 10 of 45
Temperature
Comparison
Forecasted
Adoption Impacts
Comparison of equipment rating,
building design, and utility planning
temperatures
Monthly peak demand (MW) and
monthly energy (MWh)
For each of 5 scenarios
Description of each scenario,
likelihood of local, state, and federal
policy interventions, carbon tax
impacts, and equipment and
installation contractor availability
impacts.
Technical opportunity without grid
constraints
Forecasted
Adoption Impacts
Technical opportunity with grid
constraints
Forecasted
Adoption Impacts
Fraction of transformers requiring
upgrade in each of the high adoption
and technical potential cases
Extreme temperature peak demand
impacts for each forecast and
technical scenario
Short duration and medium duration
impacts
Technical demand response potential
by month by year
Forecasted
Adoption Impacts
Forecasted
Adoption Impacts
Forecasted
Adoption Impacts
Load flexibility
Impacts
Load flexibility
Impacts
Report Section 4.3
Data spreadsheet Appendix:
Forecast Model Results.xlsx
Report Section 3.2
Data Spreadsheet
Appendix: Forecast Model
Results.xlsx
Data Spreadsheet
Appendix: Forecast Model
Results.xlsx
Distribution Equipment
Impacts Tool
Report Section 6.3, Data
Spreadsheet Appendix:
Forecast Model Results.xlsx
Report Section 6.6
Report Section 6.6
Definitions
The following are the definitions for each of the major concepts included throughout
this report.
Equipment stock – the installed stock of equipment present in the study area
as of a specific time, including the mix of equipment characteristics.
Equipment saturation – the fraction of the building stock or a portion of the
building stock that has equipment with a given set of characteristics.
Market penetration or market share – the share of equipment sold for a
particular application at a specific time that has a given set of characteristics.
Building electrification impacts – any change in the demand for electricity or
fuel over any time period (e.g., yearly, monthly, hourly), caused by building
electrification.
Technical opportunity for building electrification – the size of building
electrification impacts that is technically possible if all building fuel end uses
at a given time are converted to electricity.
Stock turnover model – a model that tallies all of the equipment stocks and
flows to forecast the change in the equipment stock over time. Includes three
pathways:
APEX ANALYTICS
Page | 10
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 11 of 45
▪
Replace on Burnout (ROB) – assumes equipment is replaced as it meets
end of life with baseline of alternative code-minimum equipment.
▪ Retrofit (RET) – assumes equipment is replaced before end of life with
some remaining useful life, so uses a dual baseline of existing equipment
and new code-minimum equipment.
▪ New Construction (NEW or NC) – assumes equipment is installed as part
of new construction, assumes code-minimum equipment baseline.
Building electrification measure – a change in the equipment stock from a
fossil-fueled piece of equipment to an electricity-fueled piece of equipment.
Measure characterization – the process of defining the size, efficiency, and
usage of the baseline and efficient pieces of equipment in a building
electrification measure, resulting in estimates of per unit building
electrification impacts and costs.
Measure List - The forecast includes a group of 16 key electrification
measures used in this analysis. The measure characteristics include sector,
measure name, end use, baseline equipment, efficient equipment, the degree
of gas displacement, and market path. Table 3 shows each of these
characteristics.
Table 3. Composition of Key Measures Use in Analysis
Sector
Measure
ResHeatBoilerPartial50
ResHeatBoilerFull
ResHeatFurnPartial50
ResHeatFurnPartial80
Comm
ercial
Residential
ResHeatFurnFull
End Use
Space
Heating
Space
Heating
Space
Heating
Space
Heating
Space
Heating
Base Equipment
EE Equipment
Gas
Displacement
Market Path
Boiler
Ductless HP
50%
ROB/NC/RET
Boiler
Ductless HP
100%
ROB/NC/RET
Furnace / AC
Central HP
50%
ROB/NC/RET
Furnace / AC
Central HP
80%
ROB/NC/RET
Central HP
100%
ROB/NC/RET
100%
ROB/NC/RET
100%
ROB/NC/RET
100%
NC
100%
NC
50%
ROB/NC/RET
Furnace / AC
ResDHW-Gas
Water
Heating
Gas Water
Heater
ResCooking
Cooking
Gas Stove
ResAllElectricNCStd
Whole
Home
IECC 20219
New
construction w
gas service
ResAllElectricNCHE
Whole
Home
IECC 2021 New
construction w
gas service
CIBuiltUpPartial50
Space
Heating
Boiler / Chiller /
Air Handling
Unit
Heat Pump
Water Heater
(HPWH)
Induction
Cooking
New
construction
w/out gas
service
High efficiency
new
construction
w/out gas
service
Variable
refrigerant flow
heat pumps
9
IECC 2021 is likely to be adopted soon by Fort Collins and other communities. The code sets the minimum energy
conservation-related building construction standards for residential new construction. 2021 International Energy
Conservation Code (IECC) - CHAPTER 1 (iccsafe.org)
APEX ANALYTICS
Page | 11
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 12 of 45
CIBuiltUpFull
CIHeatRTUPartial50
CIHeatRTUPartial80
CIHeatRTUFull
CIDHW-Gas
CICooking
APEX ANALYTICS
Space
Heating
Space
Heating
Space
Heating
Space
Heating
Water
Heating
Cooking
Boiler / Chiller /
Air Handling
Unit
Gas Roof Top
Unit
Gas Roof Top
Unit
Gas Roof Top
Unit
Gas Water
Heater
Composite Gas
Cooking
Variable
refrigerant flow
heat pumps
HP Roof Top
Unit
HP Roof Top
Unit
HP Roof Top
Unit
100%
ROB/NC/RET
50%
ROB/NC/RET
80%
ROB/NC/RET
100%
ROB/NC/RET
HPWH
100%
ROB/NC/RET
Composite
Electric Cooking
100%
ROB/NC/RET
Page | 12
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 13 of 45
Approach
This section describes the overall approach, development of forecast scenarios, and
caveats associated with the building electrification forecast.
Overall approach
To estimate the near term and long-range building electrification impacts to
member communities and Platte River’s electric system, Apex forecasted the
building electrification impact based on several key scenarios developed in concert
with the Platte River project team. Figure 1 shows the overall forecasting approach,
with each primary step appearing in the figure. Additional descriptions for each of
the primary steps are found below the figure.
Figure 1. Overall Approach
Monthly Gas Consumption: We relied on actual community-wide natural gas
consumption as the starting point. This data was obtained from member
community 2020 natural gas consumption. Monthly data was available for
Fort Collins and Longmont, while annual data was available for Loveland and
Estes Park.
APEX ANALYTICS
Page | 13
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 14 of 45
End Use Disaggregation: We disaggregated the residential and commercial
natural gas load based on the monthly consumption in Fort Collins and
Longmont, splitting the consumption into heating and non-heating, then
splitting the non-heating consumption up based on RECS10 and CBECS11 end
use shares of non-heating. This is a critical step to estimate the technical
opportunity for each of the end uses (space heating, water heating, cooking,
etc.).
Keep End Uses with over 1% of 2040 Fossil Fuel Consumption: The team
estimated 2040 fossil fuel consumption by end use, assuming a consistent
1.8% annual growth rate in the building stock,12 with efficiency levels fixed at
2020 levels, with baseline consumption estimated using disaggregated 2020
natural gas consumption data at the community level. End uses making up at
least 1% of 2040 fossil fuel consumption were included for further analysis.
Measure Characterization: Apex previously designed electrification measures
via our work for the cities of Fort Collins and Longmont. We limited the
building electrification forecast to aggregate electrification measures
representing each of the most likely equipment types to be installed
(distilling the 143 unique measures in the original residential-only analysis to
a group of 16 composite measures).
Measure Impacts: Similar to characterization, Apex also compiled both
baseline and electrification equipment costs, fuel and electric energy and
demand impacts, and measure life. We used both the measure
characterization and impacts to run cost effectiveness analysis with resulting
measure economics (net benefits and cost per ton of avoided carbon).
Load shapes: Fort Collins provided data to National Renewable Energy
Laboratory (NREL) to support a national load shape development process.
Apex used the resulting NREL load shape database13 and adapted the Fort
Collins shapes for this analysis. For most end uses, the load shapes were
used directly after manipulation to normalize to a unitized load shape. For
residential and commercial heat pumps with varying switchover temperatures
and efficiency, a separate equipment model was used to turn the estimated
heating thermal loads from the NREL study into estimated heat pump
consumption values. These heat pump shapes were then normalized into a
unitized load shape.
Forecast Adoption and Turnover: the final step in the electrification process
was to forecast the anticipated adoption rates for each equipment type
assuming demand derived from replace-on-burnout (ROB), new construction
(NEW), and early replacement (RET) market pathways. We differentiated
adoption across the equipment types and customized for each of the seven
10
Residential End Use Consumption Survey, US Energy Information Agency,
https://www.eia.gov/consumption/residential/data/2015/index.php?view=consumption#undefined
11
Commercial End Use Consumption Survey, US Energy Information Agency,
https://www.eia.gov/consumption/commercial/
12
Housing and Urban Development Fort Collins Comprehensive Housing Market Analysis, Aug 1, 2017.
https://www.huduser.gov/portal/publications/pdf/FortCollins-CO-comp-2017.pdf.
13
End-Use Load Profiles for the U.S. Building Stock | Buildings | NREL
APEX ANALYTICS
Page | 14
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 15 of 45
different scenarios (reviewed below). We based adoption rates on a
combination of naturally occurring demand, program support and incentives,
adoption of code and other regulatory requirements.
Scenario Definitions
Through a series of stakeholder meetings, Apex and Platte River staff settled on
seven different adoption scenarios to model. The seven scenarios span a wide
range of possible policy and market evolution pathways?. The team did not model a
null scenario where no significant building electrification takes place, but there is a
possibility that this scenario may still occur. The scenarios developed for this
analysis include the following:
Low adoption: limited to enhanced utility incentives
Medium adoption: low plus code requirements for heat pumps
High adoption: medium plus carbon tax and all electric new construction code
High adoption + gas phase-out: high plus gas equipment phase out
High adoption + envelope improvements: high plus envelope improvements
Technical adoption – constrained: code limits on electric resistance heat
sizing
Technical adoption – unconstrained: unconstrained full adoption
Table 2 below summarizes the modeled adoption scenarios.14 The top three
scenarios (bordered in red) represented the Low, Medium, and High scenarios used
for all of the results reported throughout this report. The low or medium scenarios
appear to be the most likely median scenario, but all three of these scenarios, plus
the null scenario with zero adoption, constitute plausible future scenarios with a
significant likelihood of occurrence.
Table 4. Modeled Adoption scenarios
Modeled Scenario
1. Low
adoption
2. Medium
adoption
3. High
adoption
Utility Incentive Levels
4. High
adoption +
gas phaseout
Medium
5. High
adoption +
envelope
Medium
Medium
Medium
Medium
Full Electrification
Low
Low
Medium
High
High
Carbon Tax
None
None
2025
2025
2025
None
2025
2025
2025
2025
None
2028
2028
2028
2028
None
None
2030
2030
2030
Code requires heat
pumps in lieu of AC in
NC
Code requires heat
pumps in lieu of AC in
ROB/ Retrofit
All New Construction all
electric
14
Note the two technical potential scenarios are excluded from this table because they rely on a completely
different set of assumptions.
APEX ANALYTICS
Page | 15
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 16 of 45
Full phase out of gas
equipment
Envelope Improvement
None
None
None
2035
None
Low
Low
Low
Low
High
Forecasting Caveats and Sources of Uncertainty
Apex leveraged the most accurate and region-specific data available for this
analysis and decided on a more conservative series of assumptions for the
electrification forecast. However, forecasting carries substantial uncertainty,
especially for new technology applications, like building electrification in Colorado.
While we sought to address this uncertainty by developing seven different
scenarios, there are still several areas that could affect the forecasts that should be
mentioned:
Faster adoption of all-electric new construction codes
Slower market adoption of building electrification technology
The retail rates of natural gas and electricity
The advancement of higher efficiency cold climate heat pumps or other
advanced space heating technologies
Changes in the upfront cost of heat pumps versus gas equipment
Federal or statewide regulation
Though many of the areas of uncertainty for this study are inherent in forecasting,
in the future, additional data may be available to improve the accuracy of the
forecast. These future data collection activities could reduce the uncertainty for this
study:
Collecting baseline residential and commercial building characteristics
Compiling installation cost estimates for baseline and electrification
equipment from a random group of regional contractors
Secondary research on adoption rates among other early adoption locations
APEX ANALYTICS
Page | 16
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 17 of 45
Measure Characterization Results
For the next step in this analysis, the Apex Team estimated measure-level impacts
in terms of fuel savings, electricity increases, load shape of electricity increases and
winter peak demand impacts by extrapolating Fort Collins and Longmont results to
Platte River overall. The team had already screened residential measures for Fort
Collins and Longmont and added on the high impact C&I opportunities. The forecast
of total energy, demand, carbon, and other fuel impacts are based on the product
of (A) the assumed per unit impacts associated with each of the primary equipment
types (which are fixed per unit assumptions) and (B) the forecasted quantity of
units converted to electric end use over the same timeframe. This section covers
important details on the development of the measure level per unit impacts along
with other considerations for electrification technologies (such as frequency of
extreme temperatures and heat pump operating economics).
End Use Fossil Fuel Consumption Estimates
Actual loads are most strongly dependent on the existing heating/hot water/cooking
load, which is a function of the building stock, occupancy, and occupant behavior.
Therefore, starting with fossil fuel end use consumption estimates provides more
accurate results than other methods of extrapolation. Apex staff disaggregated
monthly natural gas consumption data by sector, starting by estimating heating
versus non-heating data from the monthly variability, then using Residential Energy
Consumption Survey (RECS)15 and Commercial Building Energy Consumption
Survey (CBECS)16 data combined with a seasonal hot water load shape tool to
estimate the breakdown of the non-heating consumption into individual end uses.
Monthly disaggregation was completed for Fort Collins and Longmont, with these
disaggregation shares then applied to annual consumption data from Loveland and
Estes Park.
As shown in Figure 2, with natural gas monthly disaggregation, it’s obvious that
space heating makes up the vast majority of residential gas consumption.
15
US Department of Energy, found online at
https://www.eia.gov/consumption/residential/data/2015/index.php?view=consumption#undefined
16
US Department of Energy, found online at https://www.eia.gov/consumption/commercial/
APEX ANALYTICS
Page | 17
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 18 of 45
Figure 2. Fort Collins Residential Gas Consumption Disaggregation
Consumption (therms/day/premise)
4.00
3.50
3.00
2.50
2.00
1.50
1.00
0.50
0.00
Jan
Feb
Mar
Apr
Hot Water
May
Jun
Cooking
Jul
Clothes Dryer
Aug
Sep
Oct
Nov
Dec
Nov
Dec
Heating
The monthly disaggregation also shows a high proportion of heating gas
consumption in commercial accounts, as shown in Figure 3.
Figure 3. Fort Collins Commercial Gas Consumption Disaggregation
20.00
Consumption (therms/day/premise)
18.00
16.00
14.00
12.00
10.00
8.00
6.00
4.00
2.00
0.00
Jan
Feb
Mar
Apr
Hot Water
APEX ANALYTICS
May
Jun
Cooking
Jul
Process
Aug
Sep
Oct
Heating
Page | 18
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 19 of 45
The commercial results are somewhat surprising, showing a higher proportion of
space heating in commercial buildings in Platte River area than observed nationally.
This could be due to a number of factors, including multifamily residential buildings
or small commercial buildings with high building envelope loads making up a
substantial proportion of the commercial building stock.
The process load was estimated and removed from this commercial analysis, as
industrial and large commercial process loads are out of scope for this study. Better
estimates of electrification of industrial and large commercial process loads can be
made using site-specific assessment of industrial facilities in the area.
Apex staff then adjusted residential building consumption up by 5% to account for
potential propane accounts. This proportion is unknown, but likely to be small,
given the availability of gas in most areas of the Platte River communities. Apex
staff estimated end use consumption for non-metered end uses, including forklifts
and lawn and garden equipment, using national data scaled to Platte River
community population. Last, Apex staff estimated 2040 consumption by applying
fixed growth factors consistent with recent growth trends.
Measure Selection
Apex staff worked with Platte River to settle on a final list of end use technology
variants, based on the building electrification technologies that apply to the largest
source of projected 2040 building fossil fuel consumption. As shown in Table 2, the
team removed all end uses with less than 1% of emissions from modeling
consideration, opting to focus more attention on the most impactful end uses.
Electrification of space heating alone represents approximately three-quarters of
the high level technical potential for 2040 GHG reduction, driven primarily by
residential space heating.
APEX ANALYTICS
Page | 19
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 20 of 45
Table 5. Projected 2040 Fossil Fuel Emissions by Sector and End Use
Sector
End Use
Percent of 2040 Fossil
Fuel GHG Emissions
Included in
PRPA Forecast
Residential
Space Heating
51.8%
Yes
Residential
Water Heating
12.5%
Yes
Residential
Cooking
1.7%
Yes
Residential
Lawn and Garden
0.9%
No
Residential
Clothes Dryer
0.5%
No
Commercial
Space Heating
23.6%
Yes
Commercial
Cooking
4.7%
Yes
Commercial
Water Heating
2.9%
Yes
Commercial
Forklifts
0.8%
No
Commercial
Lawn and Garden
0.6%
No
There was significant benefit in focusing the more in-depth analysis on the
measures that are likely to have the largest technical opportunity in terms of
increased electricity loads. For example, residential space heating represents more
than half of the projected 2040 building fossil fuel consumption, while residential
cooking represents less than 1%. As a result, Apex began the process by screening
down to the prioritzied list of measures based on the technical opportunity. We
determined only those measures contributing at least 1% of total technical
opportunity to be included in further analysis.
Extreme Cold Temperature Frequency
Apex conducted a review of Fort Collins weather records from the last 130 years to
estimate the frequency of extreme weather events that have been observed.
Knowing the extent and duration of extreme cold weather events is an important
consideration for building electrification efforts, as it drives the need for backup
heat, beyond performance at the ASHRAE(?) design temperature of 0 degrees,
which corresponds with the lowest temperature that get exceeded almost every
year. Apex analyzed the occurrence of three different kinds of extreme cold
weather events:
Short duration: Lowest temperature observed each year
Medium duration: Lowest average temperature over a two-day period
Long duration: Lowest average temperature over a five-day period
The minimum temperature observed during the February 2021 extreme cold event
was -11degree F. As shown in Table 4, the temperature has reached -10 or colder,
APEX ANALYTICS
Page | 20
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 21 of 45
17 years since 1980. Even colder temperatures have been observed in the past.
Since regular heat pumps cease to work below ~0 degrees and even cold climate
heat pumps currently cease to work below -15 degrees, this shows that backup
systems are likely to be required, even for cold climate heat pumps.
Table 6. Frequency of Absolute Minimum Temperature Occurrence in Fort Collins
Percentile (year
frequency)
95% (19 in 20)
90% (9 in 10)
75% (3 in 4)
50% (1 in 2)
25% (1 in 4)
10% (1 in 10)
5% (1 in 20)
Temperature
(degrees F)
-3
-5
-10
-15
-22
-30
-31
Last Year of
Occurrence
2021
2021
2021
2017
1990
1962
1962
Number of years since
1980
33
32
17
8
2
0
0
Over the last 130 years, the 1-year-in-10 extreme 2-day cold weather event has
had an average temperature of -12 degrees, which has also occurred twice since
1980, as shown in Table 5. This is much colder than the coldest 2-day average
temperature observed in February 2021, which was -1 degree.
Table 7. Frequency of Lowest 2-day Average Temperature in Fort Collins
Percentile (year
frequency)
Temperature
(degrees F)
Last Year of
Occurrence
Number of years
since 1980
95% (19 in 20)
90% (9 in 10)
75% (3 in 4)
50% (1 in 2)
25% (1 in 4)
10% (1 in 10)
5% (1 in 20)
12
11
7
1
-5
-12
-14
2021
2021
2021
2021
1990
1990
1989
36
33
25
13
3
2
1
Likewise, the 1-year-in-10 extreme 5-day cold weather event had an average
temperature of -3 degrees, which has occurred 3 times since 1980. This is also
colder than the coldest 5-day average temperature observed in February 2021,
which was 4 degrees.
Table 8. Frequency of Lowest 5-day Average Temperature in Fort Collins
Percentile (year
frequency)
95% (19 in 20)
90% (9 in 10)
75% (3 in 4)
50% (1 in 2)
25% (1 in 4)
10% (1 in 10)
5% (1 in 20)
APEX ANALYTICS
Temperature
19
17
14
9
3
-3
-7
Last Year of
Occurrence
2021
2021
2021
2021
1998
1990
1989
Number of years since
1980
36
33
23
15
8
3
2
Page | 21
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 22 of 45
Heat Pump Operating Economics
As identified in the measure screen, residential space heating with heat pumps
represents the largest opportunity for building electrification. The operation of heat
pumps has three key features:
1. As the temperature drops, the heating capacity drops. Cold climate heat
pumps maintain rated capacity much better than standard heat pumps, but
they still lose capacity at the coldest temperatures.
2. Below a certain temperature, heat pumps do not work at all. For standard
heat pumps, this occurs around 0 degrees, while some cold climate heat
pumps keep running down to -15 degrees.
3. The efficiency of heat pumps declines as the temperature drops, meaning it
takes more electricity to provide the same amount of heat as the
temperature drops.
As a result of the efficiency drop, the economics of operating a heat pump also
declines as the temperature declines. The other key driver of heat pump operating
economics is the price of electricity relative to the price of gas – the lower the ratio
of electricity to natural gas rates the better the heat pump operating economics.
In Figure 4 below, the gold line shows the temperature and fuel price ratio
(expressed as cents/kWh for electricity divided by $/MMBtu for fuel) that results in
the same cost to heat with a standard furnace or a standard heat pump. At all
temperatures above that line, it’s more economical to heat with a heat pump than
with a furnace. At all temperatures below that line, it’s more economical to heat
with the furnace. For Fort Collins and Longmont, as of August, 2021, the green
dashed line down the middle shows the current ratio of electricity price to gas price.
These utilities both have favorable economics for operating standard heat pumps
above 27 degrees. This is known as the optimal switchover temperature.
APEX ANALYTICS
Page | 22
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 23 of 45
Figure 4. Standard Central Heat Pump Operating Economics as a Function of Temperature
and Fuel Price Ratio
65
60
55
Outdoor Temperature (degrees F)
50
Heat Pump
Operating
Cost Savings
+30%
0%
45
40
-25%
35
30
25
20
15
Heat Pump Operating
Cost Increases
10
5
0
-5 0.4
-10
-15
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
Longmont Tier 2, Fort Collins
Average vs Gas
-20
Ratio of Electricity Price (cents/kWh) to Fuel Price ($/MMBtu)
A map of operating economics for a high efficiency heat pump would look very
similar, except that by using ~10% less electricity per unit of heat delivered, the
economics are improved, resulting in a lower optimal switchover temperature of 20
degrees. Changing gas and electricity rates will cause the optimal switchover
temperature to change over time – rates are critical to the economics of heat pump
displacement of fossil-fueled heating.
The results of the Fort Collins and Longmont Building Electrification Study showed
that partial displacement heat pumps had the strongest customer and societal costbenefit results. In addition, partial displacement heat pumps delivered significant
benefits to non-participant ratepayers who did not purchase heat pumps by
increasing sales of electricity during off-peak times.17
The forecast assumes a mix of standard heat pumps with a 30-degree switchover
temperature (50% of gas heat displaced), high efficiency heat pumps with a 20degree switchover temperature (80% of gas heat displaced), and cold climate heat
17
The utility costs of supplying electricity to a given end use are driven by the required capacity (driven by usage
during peak times) and the overall energy consumption. End uses that have high energy consumption without any
capacity impacts (like partial displacement heat pumps) have lower utility costs of supply, pushing rates down and
benefiting non-participating customers.
APEX ANALYTICS
Page | 23
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 24 of 45
pumps with full electrification (100% of gas heat displaced). The actual attainment
of switchover temperatures depends on contractor installation practices and
customer behavior to a lesser extent. The forecasts assumed significant contractor
and customer education on the benefits of optimal switchover temperatures, but
still assume a mixture of 30-degree switchover and 20-degree switchovers into the
2030s and 2040s.
Measure Unit-Level Impacts
We developed unit-level measure impacts for each measure shown in Table 9,
based on current (2020) operating characteristics and assumptions. These
measures are an aggregation of more than 140 unique measures modeled for the
Fort Collins/Longmont Study. While the units of the residential sector measures are
per home, the commercial units are not directly linked to a physical unit outside of
baseline gas consumption, because the most recent baseline gas consumption for
2020 is the only measure of the size of the commercial building stock that we have
accurate data for. This ensures that the forecast commercial gas consumption is
properly calibrated to the baseline consumption, but this comes at the expense of
having a physical measure definition that can be used in program design. Additional
input details can be found in the spreadsheet appendix: Forecast Model
Results.xlsx.
Table 9. Measure Unit-Level Impacts
Residential
Sector
Measure
Annual Energy
Use (kWh)
Summer
Demand (kW)
Winter
Demand (kW)
ResHeatBoilerPartial50
263
1,662
0.00
0.00
ResHeatBoilerFull
543
4,067
0.00
10.00
ResHeatFurnPartial50
263
1,907
0.00
0.00
ResHeatFurnPartial80
438
3,007
0.00
0.00
ResHeatFurnFull
543
4,067
0.00
10.00
ResDHW-Gas
125
756
0.11
0.12
ResCooking
9
126
0.03
0.06
677
5,309
0.17
8.70
6.70
ResAllElectricNCStd
Commercial
Natural Gas
Savings
(therms)
ResAllElectricNCHE
419
4,109
0.13
CIBuiltUpPartial50
5,000
31,550
0.00
0.00
CIBuiltUpFull
10,000
74,900
0.00
184.17
CIHeatRTUPartial50
5,000
36,200
0.00
0.00
CIHeatRTUPartial80
8,000
54,960
0.00
0.00
CIHeatRTUFull
10,000
74,900
0.00
184.17
CIDHW-Gas
7,351
44,541
6.62
7.04
CICooking
10,000
137,126
36.75
67.79
APEX ANALYTICS
Page | 24
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 25 of 45
Measure-level Forecast Impacts
This section focuses on the assumptions and processes used to develop the
forecasted quantity of converted equipment units through assumed adoption rates
and the resulting energy and demand impacts by measure. First, we review the
adoption rates (penetration forecasts) for a selection of adoption pathways (replace
on burnout versus end of life retrofit) for a selection of the major equipment types.
Then, we review the equipment stock forecast, showing how this results in a
growing electric equipment stock substituting for a natural gas equipment stock.
The final step in presenting the measure results include the relative measure-level
annual energy impacts across two distinct periods (2030 and 2040) reported for
each of the sectors.
Building Electrification Equipment Penetration
Forecasts
The starting point for estimating the forecasted quantity is the market share or
market penetration of equipment over time across each market pathway. The total
market for each piece of equipment is composed of three pathways, ordered by
their contribution to the forecasted electrification stock:
•
Replace-on-Burnout (ROB), e.g., when a central air conditioner fails, is it
replaced with an central air conditioner or heat pump?
•
New Construction (NC), e.g., when a new home is built, does a central air
conditioner or heat pump get installed? OR when an existing home is adding
central air conditioning for the first time does a central air conditioner or heat
pump get installed?
•
Retrofit/Early Retirement (RET), e.g., when somebody replaces their central
air conditioner while it still works.
The participant cost-effectiveness has substantial differences across equipment
installations in these three market pathways. In general, participant costeffectiveness is much better for replace-on-burnout and new construction
installations than for retrofit or early retirement applications. Consequently, most
installations are forecast to happen through replace-on-burnout or new
construction.
For heat pumps in residential applications, the most important pathway is
replacement on-burn-out of central air conditioners with heat pumps, rather than
replacement of furnaces with heat pumps. Replacing a burned out central air
conditioner with a heat pump has very low incremental costs, while replacing a
furnace costs more money. The furnaces can almost be treated independent of the
central air conditioner to central heat pump conversions, except when going to a
full electrification scenario.
APEX ANALYTICS
Page | 25
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 26 of 45
While all of the equipment adoption rates are included in the spreadsheet appendix,
we have presented results for the most important groups of measures across the
primary scenarios (low, mid, high) below.
In all cases, the market share (or market adoption) is defined by the efficient
market size divided by the baseline market size, which includes both base
equipment and efficient equipment. The following chart (Figure 5) shows the
residential heat pump adoption whereby heat pumps (efficient market size) replace
burned out or retired central air conditioning systems (the base market size). The
charts demonstrate the forecasted market share across the three adoption
scenarios. The low case shows a relatively rapid adoption, comparable to the
recent market adoption curve for LEDs, without code requirements. The medium
and high cases include a code requirement for all central air conditioners to be heat
pumps, starting in 2028, but then include some amount of non-compliance. The
medium and high cases are largely consistent and are therefore overlapping in this
chart.18
Figure 5. Residential Central Air Conditioning ROB Heat Pump Market Share
100%
90%
HP Market Share
80%
70%
60%
50%
40%
30%
20%
10%
0%
Furn_AC Low
Furn_AC Medium
Furn_AC High_w_carbon
The following chart (Figure 6Error! Not a valid bookmark self-reference.) shows the
residential heat pump adoption whereby heat pumps (efficient market size) are
installed in new construction in lieu of central air conditioning systems (base market
size). The chart demonstrates forecasted market share across the three adoption
scenarios. Again, the medium and high cases are largely consistent and are
therefore overlapping in this chart. The low case again shows an adoption curve
consistent with other low incremental cost efficiency measures receiving program
18
The only difference between the medium and high cases is the requirement for all-electric new construction
after 2030. This does not change the adoption of heat pumps, only the adoption of full-displacement heat pumps.
APEX ANALYTICS
Page | 26
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 27 of 45
support, like LEDs, while the medium and high cases include a code requirement
that all new construction with central air conditioning have a heat pump, starting in
2025, with declining non-compliance after that date.
Figure 6. Residential Central Air Conditioning New Construction Heat Pump Market Share
100%
90%
HP Market Share
80%
70%
60%
50%
40%
30%
20%
10%
0%
Low
Medium
High_w_carbon
The following chart (Figure 7) shows the market share of residential all-electric new
construction (homes with no gas lines present vs all homes). The chart
demonstrates the forecasted market share across the three adoption scenarios and
the role of codes requiring heat pumps (medium and high) and then requiring all
electric new construction (high). Even the low case assumes high adoption of allelectric new construction by 2040.
APEX ANALYTICS
Page | 27
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 28 of 45
All Electric New Construction Market
Share
Figure 7. Forecast Market Share for Residential All-Electric New Construction
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
New Construction Low
New Construction Medium
New Construction High_w_carbon
The following chart (Figure 8) shows the residential heat pump water heater
adoption whereby heat pumps (efficient market size) are installed in lieu of natural
gas water heating systems after a gas water heater has failed (base market size).
The chart demonstrates the forecasted market share across the three adoption
scenarios. Heat pump water heaters have been promoted by energy efficiency
programs for many years, with little impact. As a result, the forecast assumed a
slower adoption rate for heat pump hot water heaters relative to space heating
electrification.
Figure 8. Market Share of Heat Pump Water Heaters in Residential Gas Water Heater ROB
Applications
100%
DHW HP Market Share
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
DHW Low
APEX ANALYTICS
DHW Medium
DHW High_w_carbon
Page | 28
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 29 of 45
Though commercial and industrial buildings represent a smaller share of the
forecasted electrification impacts, commercial space heating will still have a
substantial impact on Platte River’s system. The following chart (Figure 9) shows
the commercial heat pump roof top units (RTU) adoption whereby heat pumps
(efficient market size) are installed in lieu air conditioner/furnace RTU systems
(base market size). The low case shows an adoption curve similar to the residential
heat pump low case, but delayed a few years. The medium and high cases are
overlapping and include a requirement for heat pumps in ROB applications as of
2028. The only difference between high and medium is the inclusion of a
requirement for all electric new construction, starting in 2030, which does not have
an impact on this part of the market.
Figure 9. Commercial RTU ROB Heat Pump Market Share
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
Low
Medium
High
Building Electrification Equipment Stock Forecast
Using the stock turnover model and the market penetrations calculated above,
Apex calculated the size of the increased building electrification equipment stock
over time for each scenario and equipment stock. While all of the equipment stock
forecasts are included in the spreadsheet appendix, we have presented results for
the most important groups of measures in the low scenario below.
APEX ANALYTICS
Page | 29
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 30 of 45
Figure 10. Forecasted Low Scenario Residential Furnace/AC and Heat Pump Stock
120,000
Total Units in Use
100,000
80,000
60,000
40,000
20,000
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
2040
2041
2042
2043
2044
2045
2046
-
Heat Pump
Furnace AC
The forecast includes consistent increases in the residential building stock over
time, with all electric new construction becoming more prevalent after 2030, as
shown in Figure 11.
Figure 11. Forecasted Residential New Construction and Low Scenario All-Electric New
Construction Homes
70,000
Total New Homes
60,000
50,000
40,000
30,000
20,000
10,000
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
2040
2041
2042
2043
2044
2045
2046
-
All Electric NC
New Homes
The forecast projects very little heat pump water heater adoption in the low
scenario until after 2030, with the total installed stock of natural gas water heaters
rising into the 2030s, after which time the heat pump water heater starts rising
more rapidly, as shown in Figure 12.
APEX ANALYTICS
Page | 30
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 31 of 45
Figure 12. Forecasted Residential Natural Gas Domestic Hot Water and Heat Pump Hot
Water Heaters
140,000
Total Units in Use
120,000
100,000
80,000
60,000
40,000
20,000
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
2040
2041
2042
2043
2044
2045
2046
-
HP DWH
Gas DHW
For commercial space heating applications, the number of units does not mean as
much, so we instead modeled the share of the market consumption over time,
which is equivalent to the saturation. Figure 13 shows the saturation of heat pumps
(EE Equipment) vs furnace/AC RTUs (standard equipment) over time. The forecast
shows increasing saturation of heat pumps after 2030.
Figure 13. Commercial RTU Saturation Forecast - Low Adoption
100%
RTU Conversion to HP
90%
80%
70%
60%
50%
40%
30%
20%
10%
HP RTU
APEX ANALYTICS
2046
2045
2044
2043
2042
2041
2040
2039
2038
2037
2036
2035
2034
2033
2032
2031
2030
2029
2028
2027
2026
2025
2024
2023
2022
0%
Gas RTU
Page | 31
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 32 of 45
Building Electrification Impacts by Measure
The team applied the impacts and load shapes19 by measure to estimate the
unitized impact of a given technology. To develop the total impacts for each
scenario, we then applied the results of the stock model of the uptake of the
technologies within Platte River territory over time (e.g. codes requiring heat pump
capability for new air conditioners, new hot water heater standards, carbon tax,
etc.). As a final step in the forecast process, we applied differing adoption rates
with forecasts out to 2046, by measure.
Figure 14 and Figure 15 show the low, medium, and high scenario incremental
electric energy consumption by measure for 2030 and 2040, respectively..
Key Finding: Partial electrification of residential furnaces, all-electric residential new
construction, and commercial RTUs cause the largest electric energy increases.
The results show that the partial electrification of residential furnaces
(ResHeatFurnPartial50 and ResHeatFurnPartial80), building of all-electric new
homes (ResAllElectricNCStd) and partial electrification of commercial RTUs
(CIHeatRTUPartial50 and CIHeatRTUPartial80) have the largest impacts across all
three scenarios.
Figure 14. 2030 Annual Measure-Level Electric Energy Increases
Annual Energy Increases (MWh)
250,000
200,000
150,000
100,000
50,000
-
Low
Medium
High_w_carbon
19
We have good residential and commercial building load shapes available from an ongoing NREL study that we
participate in.
APEX ANALYTICS
Page | 32
The Connecticut Light and Power Company
d/b/a Eversource Energy
Docket No. 26-05-10
Date Issued August 13, 2026
CLF-011 Attachment 4
Page 33 of 45
Figure 15. 2040 Annual Measure-Level Electric Energy Increases
Annual Enegy Increases (MWh)
250,000
200,000
150,000
100,000
50,000
-
Low
Medium
High
Figure 16 and Figure 17 show the forecast winter peak demand increases by
measure.
Key finding: Full electrification of residential space heating, commercial space
heating, and residential new construction will cause large increases in winter peak
demand.
Partial electrification of residentia