Interrogatory responses
Answers to questions 45, 54, 57, 60
Files10
NECTA-045_Final.pdf
PDF · 87 KB · 1 pageText searchable
Download NECTA-045_Final.pdfRead the text of NECTA-045_Final.pdf
NECTA-045 Attachment 1 REDACTED.pdf
PDF · 200 KB · 2 pagesNo text in this file
NECTA-045 Attachment 2 REDACTED.pdf
PDF · 200 KB · 2 pagesNo text in this file
NECTA-045 Attachment 3 REDACTED.pdf
PDF · 201 KB · 2 pagesNo text in this file
NECTA-054_Final.pdf
PDF · 265 KB · 4 pagesText searchable
Download NECTA-054_Final.pdfRead the text of NECTA-054_Final.pdf
NECTA-057_Final.pdf
PDF · 114 KB · 1 pageText searchable
Download NECTA-057_Final.pdfRead the text of NECTA-057_Final.pdf
NECTA-057 Attachment 1.pdf
PDF · 1.5 MB · 39 pagesText searchable
Download NECTA-057 Attachment 1.pdfRead the text of NECTA-057 Attachment 1.pdf
NECTA-057 Attachment 1.xlsx
Excel · 191 KBText searchable
Download NECTA-057 Attachment 1.xlsxRead the text of NECTA-057 Attachment 1.xlsx
NECTA-060_Final.pdf
PDF · 86 KB · 1 pageText searchable
Download NECTA-060_Final.pdfRead the text of NECTA-060_Final.pdf
NECTA-060 Attachment 1.pdf
PDF · 1.4 MB · 15 pagesText searchable
Download NECTA-060 Attachment 1.pdfRead the text of NECTA-060 Attachment 1.pdf
Text of NECTA-057 Attachment 1.pdf
Extracted from the file · 39 pages · 452,743 characters
This spreadsheet is large. Its searchable text keeps the sheet names, column headings and text cells and stops at 300,000 characters, so search may miss words further in. Download the file for every cell and figure.
Part 41 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | LIBERTY HWY | Putnam | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 30/4Install: 40/2Replace due to clearances at pole & over road; Attach secondary 82" from pole top; Replace secondary down guy with 14M to new ES-set 1"TT anchor LL=10', P=DE | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | FLAX HILL RD | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES Inst. 55' class 1 (E15) / Abdn 50' class 2.Attach top bolt of FG x-arm at 90".Attach bolt of 1PH tap at 113".Attach top bolt of bottom spacer cable bracket at 146".Attach Sec./Sec. tap at 228".Attach aerial cable at 244".Inst. (1) 78" FG ins. at 130", transfer existing tree guy to other end of FG ins..Transfer cutout, spare fuse holder & streetlight.Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | JACKSON DR | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Inst. (1) anc. at a lead of 11' for corner bisector.Attach Sec. at 82".Inst. (1) 14M ins. anc. guy at 22", attach to the 11' lead bisector anc..Inst. (1) 14M ins. span guy at 24", run to pole 10570 (attach at 18' from ground at pole 10570).Inst. cutout & zap shield.Transfer Xfrmr & street light.Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | GEORGE AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Attach Sec. at 82".Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | GEORGE AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 35' class 4 pole.Pole in sidewalk.Inst. (1) anc. at a lead of 13' for DE (install new anc. near same location as old).Attach Sec. at 107"/109".Inst. (1) 14M non-ins. anc. guy at 107", attach to 13' lead DE anc.Inst. (1) 14M non-ins. span guy at 109", run to pole 3227 (attach at 6" below Sec. at pole 3227).Transfer street light.Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | GEORGE AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Inst. (1) anc. at a lead of 11' for corner bisector.Attach Sec. DE at 82".Attach other end of span guy from pole 3228 (WO 20412612) at 70".Inst. (1) 14M non-ins. anc. guy at 76", attach to the 11' lead bisector anc..Inst. (1) 14M ins. span guy at 70", run to pole 8463 (attach ins. end at 22" at pole 8463).Note: Pole replaced at phones request, due to comms clearances in midspan. | Existing Attachment auto-added. | YPart 42 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | TIERNEY ST | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 1 pole (JO) / Abdn. 40' class 3 pole.Cut & kick pole for Comms. riser.Attach Sec./Neut. at 109".Inst. (1) 14M ins. span guy at 22", run to pole 3230 (attach at existing location at pole 3230).Transfer street light.Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | CORY LN | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 1 pole (JO) / Abdn. 35' class 4 pole.Attach Sec./Neut. at 82".Inst. (1) 14M ins. span guy at 22", run to pole 24786 (attach at existing guy height at pole 24786).Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | KATY LN | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Attach Sec./Neut. at 82".Transfer street light, cutout & Xfrmr (inst. zap shield).Note: Pole replaced at phones request, due to comms clearances in midspan for new attacher. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | EASTON RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | REQUESTING ES TO REPLACE POLE WITH 40/2 DUE TO COMM MDISPAN CLEARANCE TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Payments Received | Precision Valley Communications | Complete | MARION CT | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 35' class 2 pole (JO) / Abdn. 35' class 4 pole.Cut & kick pole for service riser.Inst. (1) anc. at a lead of 12' for DE.Rebuild service riser for new pole. Attach Sec. at 52".Inst. (1) 14M non-ins. anc. guy at 52", attach to 12'L DE anc. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Payments Received | Precision Valley Communications | Complete | BOSTON POST RD W | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 50' class 1 pole (JO) / Abdn. 45' class 1 pole.Inst. (2) anc.s at leads of 12' & 16' for DE tap.Attach x-arm for 3PH Pri. tap at 30".Attach Sec. at 120".Attach AC. at 136".Inst. (1) 18M ins. anc. guy at 46", attach to 16'L DE tap anc.Inst. (1) 18M non-ins. anc. guy at 136", attach to 16'L DE tap anc.Replace (3) cutouts.Transfer street light. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready | Precision Valley Communications | Complete | DORCHESTER DR | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 35/4Install: 40/2Cut & kick due to secondary riser; Replace due to comms midspan clearance issues; Attach secondary 82" from pole top; Transfer 37.5 KVA XFMR, XFRM is fused, zap shield exists; Replace 14M primary down guy to new ES set 1" TT anchor LL=20', P=DE; Extend (2) 3" Secondary Risers 28" with 4" PVC Shield; Maintain service on pole | Existing Attachment auto-added. | YPart 43 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | PORTER ST | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 1 pole (JO) / Abdn. 35' class 4 pole.Attach DE Sec. at 109".Inst. (1) 14M non-ins. span guy opposite DE Sec., run to pole 5945. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | NetSpeed LLC | Complete | GRISWOLD ST | Glastonbury | FRONTIER/CONNECTICUT LIGHT&POWER | FRONTIER | MAKE-READY | Shift Raise | null | null | null | raise secondary 7" | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | NetSpeed LLC | Complete | GRISWOLD ST | Glastonbury | CONNECTICUT LIGHT&POWER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | FTR TO REPLACE POLE WITH 40/2 POLE DUE TO 5' RULE TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | OHIO AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | EL TO REPLACE POLE WITH 45-1 DUE TO 5' RULE TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | OHIO AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | EL TO REPLACE POLE WITH 45-1 DUE TO MIDSPAN CLEARANCE ISSUES TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise Pri. to top of pole. Raise tangent Sec. 29". Inst. (1) 14M ins. span guy at 36", replacing existing span guy, run to pole 23233 (attach at existing location at pole 23233). Raise streetlight (road-side)12". Raise area light (field-side) 29". Note: Phone requested/required raises to accommodate new attacher. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise Sec. 29". Extend Pri. riser up to raised Sec. level. Raise streetlight 12". The 3PH riser install and xfrmr bank removal (pole 23231), was done under WO 20449565, mapping prereq not completed. Note: Phone requested/required raises to accommodate new attacher. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise Pri. to top of pole, transfer road-side line current sensor. Raise capacitor bank 36". Raise Sec. 36". Extend cap. control cable riser up to raised Sec. level (cable coiled up). Transfer cutouts. Note: Phone requested/required raises to accommodate new attacher. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise top Pri. to top of pole. Raise Pri. tap 36". Raise Sec./Sec. tap 36". Raise streetlight 24". Transfer cutouts. Note: Phone requested/required raises to accommodate new attacher. | YPart 44 of 80
CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise top Pri. to top of pole. Raise Pri. tap 36". Raise Sec./Sec. tap 34". Raise streetlight 34". Transfer cutouts. Note: Phone requested/required raises to accommodate new attacher. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CONNECTICUT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Raise top Pri. to top of pole. Raise Pri. tap 36". Raise Sec./Neut. tap 25". Raise streetlight 25". Replace cutouts. Note: Phone requested/required raises to accommodate new attacher. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | MATHER ST | Wilton | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 45/3Install: 45/2Cut + Kick due to Primary Riser; Replace due to new attachment load failure; Attach neutral 136" from pole top; Replace 20K fuse with 15K; Extend 3" Primary Riser 12" with 4" PVC Shield | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | STRAWBERRY HILL AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 35' class 4 pole.Inst. (1) anc. at a lead of 24' for bisector.Attach 1PH Pri. tap at 30".Attach DDE Neut./Sec. taps at 107".Attach DDE Neut./Sec. at 109".Inst. (1) 18M ins. anc. guy at 22", attach to 24'L bisector anc.Transfer cutout.Transfer street light. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | ALROWOOD DR | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 35' class 2 pole (JO) / Abdn. 30' class 4 pole.Inst. (1) anc. at a lead of 15' for DE.Transfer OWS bracket and attach bottom of bracket at 52".Pull slack in DE OWS to pole 6678.Inst. (1) 14M ins. anc. guy at 52", attach to 15'L DE anc. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | STRAWBERRY HILL AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 35' class 4 pole.Inst. (1) anc. at a lead of 17' for DE Sec. tap.Attach Sec.s/Neut. at 109".Inst. (1) 14M non-ins. anc. guy at 109", attach to 17'L DE Sec. tap anc. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | STRAWBERRY HILL AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 35' class 4 pole.Attach Sec. at 109".Pull slack in Sec. to pole 16737Transfer Xfrmr & cutout, inst. zap shield.Transfer street light. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | STRAWBERRY HILL AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 35' class 3 pole.Attach Sec. at 109".Pull slack in Sec./Neut. to pole 3274 (adjust midspan service).Pull slack in DE Sec. to pole 11032.Inst. (1) 14M ins. stub guy at 22", attach other end to pole 24507S at existing guy height.Transfer street light & area flood light. | Existing Attachment auto-added. | YPart 45 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | STRAWBERRY HILL AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 2 pole (JO) / Abdn. 40' class 2 pole.Attach Neut./Sec. at 109". Pull slack in Neut./Sec. to poles 3278 & 17981.Inst. (1) 14M ins. stub guy at 22", attach other end to pole 3277S at existing guy height.Transfer street light & area flood. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | COMPO RD S | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 1 pole (JO) / Abdn. 40' class 4.Attach Sec. & Sec./Neut. taps at 109".Inst. (1) 14M ins. span guy at 46", run to pole 25196 (attach at existing guy height at pole 25196.).Transfer cutout & streetlight (cutout & arrester for western tap at pole 25196).Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | COMPO RD S | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 1 pole (JO) / Abdn. 40' class 4.Attach Sec. at 107" & 109".Transfer (2) cutouts & streetlight.Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | COMPO RD S | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 2 pole (JO) / Abdn. 35' class 4.Attach Sec. at 109".Repl. ¼ mile arresters.Transfer streetlight.Note: Pole replaced due to 5' step rule with adjacent billable replacement pole.. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | DRUMLIN RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | TREE TRIMMING REQUIRED (NONBILLABLE) | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | HILLSPOINT RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Inst 45' class 1 pole (JO) / Abdn 40' class 4 pole.Cut and kick for Comm. risers, pole behind sidewalk.Inst. (1) anc. at a lead of 4' sidewalk style for DE (place as close to stone wall as feasible). Attach Sec.s at 109".Inst. (1) 18M ins. sidewalk anc. guy at 46", attach to the 4' lead DE anc..Transfer cutout & street light.Note: Pole replaced due to Comm. midspan clearance with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | ALLEN RD | Norwalk | CONNECTICUT LIGHT&POWER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 45-1 DUE TO ROAD CLERANCE (POLE REPLACEMENT ON PC 1617178) TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Make-Ready Overdue | Precision Valley Communications | Complete | ALLEN RD | Norwalk | CONNECTICUT LIGHT&POWER | CONNECTICUT LIGHT&POWER | MAKE-READY | Shift Raise | null | null | null | Raise DE Sec. by 4". (adjust midspan svcs.) | YPart 46 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | WESTPORT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 1 pole (JO) / Abdn. 40' pole.Pole in grass.Maintain 3PH slack span off all cables to pole N.N.Attach Neut. at 103"Attach Sec./Neut. tap at 109".Notes:Pole replaced at phones request, due to clearances to ground level with new attachment. | null | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | LOIS ST | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 2 pole (JO) / Abdn. 35' pole.Cut and kick for Comm. risers, pole in sidewalk.Attach Neut. at 101"Attach DE Sec. at 107".Attach Sec. DE tap at 109".Remove abandoned power Svc riser (cut/ground abandoned cables).Transfer streetlight.Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | null | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | WESTPORT AVE | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 50' class 1 pole (E5) / Abdn. 45' class 2 (E5).Set pole at least 18" behind curb face (in grass strip).Attach cross under spacer cable messenger at 74".Attach x-arm top bolt for cross under spacer cable at 76".Attach Neut. at 141". Attach Sec./Sec. taps at 147".Attach aerial cable. at 163". Inst. (1) 14M ins. span guy at 15", run to pole 29571 (attach another ins at existing location at pole 29571).Transfer streetlight.Notes:Pole replaced at phones request, due to clearances to ground level with new attachment. | null | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | GRAND ST | Thomaston | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 45/2 POLE DUE TO COMM MIDSPAN CLEARANCE | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | GRAND ST | Thomaston | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPL POLE WITH 45/2 POLE DUE TO COMM MIDSPAN CLEARANCE. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready | Precision Valley Communications | Complete | POST RD E | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES Install: 45/2, Remove: 35/4; Due to comms clearance issues; Attach secondary 109" from pole top | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready | Precision Valley Communications | Complete | POST RD E | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES Install: 50/1, Remove: 40/3; Due to comms clearance issues; Attach secondary 163" from pole top; Replace cutouts and 6 fuses (confirm fuse size - not listed in records) | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | WARD ST | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 45/2 DUE TO COMM MIDSPAN CLEARANCE - TRANSFER EXISTING POWER. | Existing Attachment auto-added. | YPart 47 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | CENTER AVE EXT | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 35/2 DUE TO COMM MIDSPAN CLEARANCE, ES TO REPLACE ANCHOR AT (L=10', B=15) - TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | RUDOLPH LN | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 40/2 DUE TO COMM MIDSPAN CLEARANCE, ES TO SET ANCHOR AT (L=11', B=178) - TRANSFER EXISTING POWER. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | RUDOLPH LN | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 40/2 DUE TO COMM MIDSPAN CLEARANCE, ES TO REPLACE ANCHOR AT (L=11', B=144) - TRANSFER EXISTING POWER. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | AIKEN ST | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 45/2 AT ES REQUEST DUE TO REPLACEMENT OF P.23157 - TRANSFER EXISTING POWER. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | AIKEN ST | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES TO REPLACE POLE WITH 45/1 DUE TO COMM MIDSPAN CLEARANCE, ES TO SET ANCHOR AT (L=12', B=342) & (L=10', B=217) & (L=15', B=272) & (L=11', B=272) - TRANSFER EXISTING POWER. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | STONY LN | Norwalk | FRONTIER/CONNECTICUT LIGHT&POWER | FRONTIER | MAKE-READY | Other | null | null | FTR TO REPLACE EXISTING ANCHOR WITH 1" TER AT B=257 L=16' | Replace secondary down guy with 14M to new FTR-set 1"TT anchor LL=16', P=DE | Y Non CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | GREEN HILL RD | Norwalk | FRONTIER/CONNECTICUT LIGHT&POWER | FRONTIER | null | Transfer To New Pole | REPLACE | null | FTR TO REPLACE POLE WITH 40/2 AT EL REQUEST DUE TO LARGE CRACKS | Shift ES facilities to FTR set: 40/2 Remove: 35/4 Replace due to cracking; Attach secondary 24" from pole top; Replace secondary down guy with 14M to existing anchor LL=15', P=15'; Shift service mid-span | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CAMPVILLE RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Extend 3" secondary riser with 4" PVC shield 24"; Replace primary down guy with 14M to new ES-set 1"TT anchor LL=13', P=31' | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CAMPVILLE RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Replace primary down guy with 14M to new ES-set 1"TT anchor LL=16', P=15' | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | SCENIC VIEW DR | Litchfield | FRONTIER/CONNECTICUT LIGHT&POWER | FRONTIER | MAKE-READY | Other | null | null | null | Replace secondary down guy with 14M to new ES-set 1"TT anchor LL=12', P=DE | YPart 48 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | FENN RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 35/5Install: 40/2Replace due to phone clearances above ground with new attachment; Attach secondary 82" from pole top | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | FENN RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 35/4Install: 40/2Replace due to phone clearances above ground with new attachment; Attach secondary 82" from pole top; Transfer 25 KVA XFMR, install C/O and fuse; Replace secondary span guy with 14M to P.2902 | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CAMPVILLE RD | Litchfield | FRONTIER/CONNECTICUT LIGHT&POWER | FRONTIER | MAKE-READY | Other | null | null | null | Due to separation of facilities & driveway clearances, raise primary & primary tap 24", raise neutral 18"; Transfer C/O | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | CAMPVILLE RD | Litchfield | CONNECTICUT LIGHT&POWER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 30/4Install: 40/2Replace due to phone clearances above ground with new attachment; Cut & kick due to riser; Attach secondary 82" from pole top; Replace LA; Replace primary down guy with 14M to new ES-set 1"TT anchor LL=11', P=DE | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | CAMPVILLE RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Replace DG with 14M to new 1"TT anchor LL=12', P=9' | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | HALLS HILL RD | Killingly | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Remove: 35/4Install: 40/2Replace due to undersized, defective pole tag; Attach Secondary Clamp 82" from pole top; Replace 14M primary down guy to existing anchor LL=12', P=10' | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | STONYBROOK RD | Norwalk | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | NO ROOM TO LOWER COMMS DUE TO CLEARANCE OVER ROAD. ES TO REPLACE POLE WITH 40/2 TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | NEWTON RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | 110042(42) ES TO REPLACE POLE WITH 40-2 DUE TO LOADING ISSUES TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | NEWTON RD | Litchfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | 110041(E41) ES TO REPLACE POLE WITH 40-2 DUE TO LOADING ISSUES TRANSFER EXISTING POWER | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Make-Ready Overdue | Precision Valley Communications | Complete | E6 | ISAIAH SMITH LN | Morris | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Replace secondary down guy with 14M to new ES-set 1"TT anchor LL=14', P=12' | YPart 49 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | HILLSPOINT RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES inst 45' class 2 pole (JO) / Abdn 40' class 4.ES inst. (1) swamp anc. at a lead of 20' for corner bisector.ES inst. (1) anc. at a lead of 16' for DE.Attach Neut./Sec. at 109".Inst. (1) 14M ins. span guy at 97", run to pole 2459 (attach ins. end at 6" below FG cutout bracket, at pole 2459).Inst. (1) 18M ins. anc. guy at 15", attach to the 16' lead DE anc..Transfer streetlight.Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | HILLSPOINT RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | Attach other end of span guy at 12" above Sec., ran from pole 2467. Inst. (1) 14M non-ins. span guy at 12" above Sec., run to pole 2465. Note: Anchor/Guying upgrades due to billable pole replacement with resiliency standards. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | HILLSPOINT RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | ES inst. (1) anc. at a lead of 20' for DE (North, behind/field-side of sidewalk). Attach other end of span guy at 14' from the ground, ran from pole 2465. Inst. (1) 18M non-ins. anc. guy opposite new span guy, attach to the 20' lead DE anc.. Note: Anchor/Guying upgrades due to billable pole replacement with resiliency standards. Pull slack in Sec. to pole 2466, adjust midspan Sec. tap to pole 13910. Install zap shield. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | GREENS FARMS RD | Westport | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES inst 50' class 1 pole (E5) / Abdn 45' class 4.Set new pole to field side edge of sidewalk (behind sidewalk), out of sidewalk.Attach bottom crossover x-arm at 46".Attach Neut.(Greens Farms Rd) at 129"Attach Sec.(Hills Point Rd), Sec. tap at 131".Attach top aerial cable at 147".Attach bottom aerial cable at 163".Attach other ins. end of span guy at 54", ran from pole 13165.Inst. (1) 14M ins. span guy at 66", run to pole 2466.Transfer streetlight.Note: Pole replaced at phones request, due to clearances to ground level with new attachment. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER Make-Ready Attachments | Awaiting MR Payment | Precision Valley Communications | Complete | GREENS FARMS RD | Westport | CONNECTICUT LIGHT&POWER | CONNECTICUT LIGHT&POWER | MAKE-READY | Other | null | null | null | ES inst. (1) anc. at a lead of 18' for DE (in-line with pole 2467, at replacement). Inst. (1) 14M ins. span guy at 6" above top aerial cable, run ins. end to pole 2467. Inst. (1) 18M non-ins. anc. guy opposite new span guy, attach to the 18' lead DE anc.. Note: Anchor/Guying upgrades due to billable pole replacement with resiliency standards. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | THOMASTON RD | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Inst 40' class 2 pole (JO) / Abdn 35' class 4 pole.Attach Sec./Neut. at 82".Inst. zap shield.Transfer Xfrmr, cutout & flood light. | Existing Attachment auto-added. | YPart 50 of 80
CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | THOMASTON RD | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Inst 40' class 2 pole (JO) / Abdn 35' class 4 pole.Inst. (1) anc. at a lead of 12' for DE Sec.Attach Sec. & DE Sec. at 82".Inst. (1) 14M non-ins. anc. guy at 82", attach to 12'L DE anc.Transfer Xfrmr & cutout. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | F3585 | THOMASTON RD | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Inst 45' class 2 pole (JO) / Abdn 40' class 4 pole.Attach Sec. & DE Sec. at 109".Inst. (1) 14M ins. stub guy at 46", run to Pole 65005.Transfer cutout, arrester & street light. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | THOMASTON RD | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Inst 40' class 2 pole (JO) / Abdn 35' class 4 pole.Inst. (1) anc. at a lead of 14' for DE Sec.Attach Sec./Neut. & DE Sec. at 82".Inst. (1) 14M non-ins. anc. guy at 82", attach to 14'L DE anc. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | BETHEL RD | Griswold | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Inst. (1) anc. at a lead of 11' for DE.Attach DE Neut. at 82".Inst. (1) 14M ins. anc guy at 48", attach to 11' lead DE anc..Inst. (1) 14M non-ins. anc guy at 82", attach to 11' lead DE anc..Transfer (2) cutouts. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | G-1892 | WARWICK RD | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 30' class 4 pole.Cut & kick pole for service riser.Inst. (1) anc. at a lead of 12' for DE.Attach DE Neut. at 82".Replace service riser conduit/cable & extend to new pole height.Inst. (1) 14M ins. anc. guy at 22", attach to 12'L DE anc.Transfer Xfrmr & cutout. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Make-Ready Overdue | Precision Valley Communications | Complete | TAFT CIR | Watertown | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 40' class 2 pole (JO) / Abdn. 35' class 4 pole.Attach Neut. at 82".Inst. zap shield.Transfer Xfrmr & cutout. | Existing Attachment auto-added. | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | ALL HOLLOWS RD | Plainfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | ES set 45' class 1 pole (T5) / Abdn 40' class 4 pole.Inst. (1) anc. at a lead of 13' for corner bisector.Attach Neut./Sec. at 82".Inst. 14M ins. anc. guy at 22", attach to the 13' lead bisector anc.Install cutout & zap shield.Transfer xfrmr. | null | Y CONNECTICUT LIGHT&POWER New or Replace Poles | Awaiting MR Payment | Precision Valley Communications | Complete | ALL HOLLOWS RD | Plainfield | CONNECTICUT LIGHT&POWER/FRONTIER | CONNECTICUT LIGHT&POWER | null | null | REPLACE | null | Set 45' class 1 pole (JO) / Abdn 35' class 4 pole.Attach Neut. at 109". | null | Y
Text of NECTA-060_Final.pdf
Extracted from the file · 1 page · 1,114 characters
Text of NECTA-060 Attachment 1.pdf
Extracted from the file · 15 pages · 67,516 characters
As listed on the current system
Question(s) Answered 45, 54, 57, 60 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 09/23/2026