Interrogatory responses
Answers to questions 1, 2, 4, 10, 18, 20
Files13
ICC-001_Final.pdf
PDF · 114 KB · 1 pageText searchable
Download ICC-001_Final.pdfRead the text of ICC-001_Final.pdf
ICC-001 Attachment 1.pdf
PDF · 3.4 MB · 28 pagesText searchable
Download ICC-001 Attachment 1.pdfRead the text of ICC-001 Attachment 1.pdf
ICC 001 Attachment 2.pdf
PDF · 4.0 MB · 68 pagesText searchable
Download ICC 001 Attachment 2.pdfRead the text of ICC 001 Attachment 2.pdf
ICC-001 Attachment 3.pdf
PDF · 1.1 MB · 34 pagesText searchable
Download ICC-001 Attachment 3.pdfRead the text of ICC-001 Attachment 3.pdf
ICC-001 Attachment 4.pdf
PDF · 1.3 MB · 34 pagesText searchable
Download ICC-001 Attachment 4.pdfRead the text of ICC-001 Attachment 4.pdf
ICC-001 Attachment 5.pdf
PDF · 3.5 MB · 67 pagesText searchable
Download ICC-001 Attachment 5.pdfRead the text of ICC-001 Attachment 5.pdf
ICC-002_Final.pdf
PDF · 143 KB · 2 pagesText searchable
Download ICC-002_Final.pdfRead the text of ICC-002_Final.pdf
ICC-002 Attachment 1.pdf
PDF · 1.1 MB · 29 pagesText searchable
Download ICC-002 Attachment 1.pdfRead the text of ICC-002 Attachment 1.pdf
ICC-002 Attachment 2.pdf
PDF · 1.5 MB · 74 pagesText searchable
Download ICC-002 Attachment 2.pdfRead the text of ICC-002 Attachment 2.pdf
ICC-002 Attachment 3.pdf
PDF · 2.5 MB · 27 pagesText searchable
Download ICC-002 Attachment 3.pdfRead the text of ICC-002 Attachment 3.pdf
ICC-004_Final.pdf
PDF · 127 KB · 1 pageText searchable
Download ICC-004_Final.pdfRead the text of ICC-004_Final.pdf
ICC-010_Final.pdf
PDF · 168 KB · 4 pagesText searchable
Download ICC-010_Final.pdfRead the text of ICC-010_Final.pdf
ICC-018_Final.pdf
PDF · 135 KB · 2 pagesText searchable
Download ICC-018_Final.pdfRead the text of ICC-018_Final.pdf
Text of ICC-001 Attachment 3.pdf
Extracted from the file · 34 pages · 76,972 characters
Page 15 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 15 of 34 3.10 Design Changes or Additions Contact the Company prior to designing any changes to existing interconnected DER facilities. Express authorization by the Company is required for the interconnection of any DER. Once a design is approved for interconnection, no changes may be made without a subsequent approval by the Company of those changes. Failure to notify the Company of changes to approved designs may result in disconnection of the DER. The document describing steps to make the design changes and their impact can be found on Eversource website (https://www.eversource.com/content/docs/default-source/builders-contractors/inverterdesign-changes-table.pdf?sfvrsn=496ad09f_3) 3.11 Utility Accessible Disconnect Switch The Company shall require a utility accessible disconnect switch (UADS), or comparable device agreed to by Company, at the PCC or at another mutually agreeable point that is accessible to Company personnel at all hours of every day and that can be opened for isolation if required. The Company shall have access to the DER isolation device. Any DER-owned isolating device should be located within ten feet and visible sight of the revenue meter or at another mutually agreeable point that is accessible to Eversource personnel at all hours of all days. The device must have proper placards and signage indicating that it is for the DER facility. Signage must be of a permanent nature. Use UV stable materials and adhesive, suitable for outdoor environmental life cycle. The Company shall have the right to open this UADS in accordance with any Interconnection Tariff or agreements as applicable. An externally accessible UADS is required for all DERs unless waived due to State requirements or extenuating circumstances, as determined on a case-by-case basis. The Company requirements and specifications for an UADS are as follows. A UADS shall: • • • • • Be gang operated Have a visible break when open Be rated to interrupt the maximum DER facility output Be capable of being locked open Be easily accessible to Company personnel at all times In NH, the state requirement is set by PUC 905.01, which does not allow the utility to require a UADS for generators less than 10 kW, unless specific conditions are not met by the interconnecting DER. In CT, certified inverter generators less than or equal to 1 kW are exempt from the UADS requirement. - 14 -Page 16 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 16 of 34 3.12 Adverse Impact of Unintentional Islanding Unintentional Islanding by the DER of all or part of the EPS (meaning a part of the EPS is kept energized by the generating facility after the area has been de-energized) is prohibited as it may result in unsafe conditions on the EPS. Eversource performs risk of islanding (ROI) screening during initial review based on the SANDIA suggested Guidelines for anti-Islanding screening. An EMT ROI study is required to further assess the ROI when a project fails the applicable screens. To pass an ROI study, generator must trip within two (2) seconds of a loss of source event to meet the IEEE 1547-2018 Section 8.1 requirements. If a violation is detected after the dynamic study completion, mitigations such as DTT will be required. 3.13 Transient Overvoltage (TOV) Transient overvoltage is of concern due to potential load rejection overvoltage (LROV) by inverter-based DER. There is concern that during step changes in load (such as tripping of an upstream device), the proposed inverters may cause transient over voltages in excess of 1.2pu, which can potentially cause damage to the customer’s equipment, utility equipment, and/or nearby customer equipment. Due to this concern, Eversource requires that the customer demonstrate that the inverters limit their cumulative overvoltage according to the transient overvoltage curve in IEEE Std. 1547-2018 clause 7.4.2. If the EMT study is required and analysis determines that a TOV condition is caused by the DER, mitigation or combination of mitigations, such as, but not limited to, Self-Protection Overvoltage (SPOV) enabling in the inverter, revising grounding system, and Surge Arrestors at POI or substation, may be required. The analysis shall also screen for pre-existing transient overvoltage issues. NOTE: Please note that compliance with IEEE Std. 1547-2018 cannot guarantee that the transient analysis is not required. 3.14 Fault Interrupting Devices The DER owner shall install an interrupting device that has the capability to safely isolate the DER from the Company’s EPS. This device shall be capable of interrupting the full nameplate fault current of the DER system with consideration of X/R ratio including all AC and DC offsets at that point in the system. Such device may be subject to approval by the Company, but such approval will be limited to the suitability of protecting the Company’s EPS. 3.15 Service Requirements All DER interconnections must be consistent with each State’s applicable Information and Requirements for Electric Supply. These documents are available at www.eversource.com. - 15 -Page 17 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 17 of 34 3.16 Clearances If installing solar panels on the roof of a building, then the DER solar Facility must maintain a minimum of three feet from the service point of attachment and service must. 3.17 Rights of Way (ROW) 3.17.1 Distribution and Transmission ROW’s Customers are not permitted to install equipment in Distribution or Transmission Rights of Way (ROW). Please contact Eversource prior to designing a project near a ROW. Please note that if your project requires you to access a ROW (such as by vehicle), you will be required to pay for a study to determine proper access to the site and modifications required for safe access and clearances. Services and equipment cannot be interconnected in or across a ROW. 3.17.2 Wind Turbine Setback from Distribution and Transmission ROW’s Each wind turbine proposed to be located near any Eversource Distribution or Transmission Right of Way (ROW) shall have a setback distance from the edge of the ROW that is the greater of the following: (1) a minimum of 1.5 times the wind turbine’s maximum tip height (MTH)*; or (2) the minimum distance recommended by the applicable Ice Drop and Throw Evaluation Report during turbine operation; or (3) the minimum distance recommended by the wind turbine manufacturer for a turbine located in proximity to Eversource infrastructure on an ROW. *Maximum Tip Height (MTH) is defined as the height of the wind turbine measured from natural grade to the tip of the rotor blade at its highest point. 3.18 Communication Protocol The new IEEE 1547-2018 standard specifies that “a DER shall have provisions for a local DER interface capable of communicating to support the information exchange requirements specified in this standard for all applicable functions that are supported in the DER”. The standard requires communications such that the utility can send control commands and receive status and information back from the smart inverters. In section 10.1, IEEE 1547-2018 also specifically says that “the decision to use the local DER communication interface or to deploy a communication system shall be determined by the Area EPS operator”. Eversource Energy, as the area electrical power system (EPS) operator, can specify which communication protocols to use from the list of the eligible protocols as specified in Table 41 of IEEE 1547-2018 or whether to require the use of DER communications interface. - 16 -Page 18 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 18 of 34 Table 41 —List of eligible protocols 1. IEEE Std 2030.5 (SEP2) TCP/IP Ethernet 2. IEEE Std 1815 (DNP3) TCP/IP Ethernet 3. SunSpec Modbus TCP/IP Ethernet 3.19 Communication Medium Evaluation Eversource will evaluate the system requirements to select the most reliable communication path for the interface with customer owned RTAC. The Eversource system has existing communication paths for the distribution system that will vary depending on location. The communication medium will be selected based on the existing infrastructure and the goal will be to integrate the new devices into the existing network and only interconnect the new devices into the network. The communication medium to be used is listed below and will take priority in the order listed. 1. Fiber The use of optic fiber is highly recommended in those cases where there is a previous installation and fiber is already available. While the cost of fiber installation and maintenance is high in comparison to Cellular or Radio, the design team will evaluate the application requirements and use fiber optic only if it is strictly required. 2. Radio This method is one of the Eversource preferred methods since it is being currently used for the Distribution SCADA communication and has been a reliable solution and provides the advantage of having the infrastructure available and installed. 3. Cellular Cellular communication is being installed in implementation of DTT schemes and has offers a redundant communication path and reliable operation. The use of Cellular technology will be evaluated by Network Engineering, DSCADA and P&C teams to be used as the primary communication medium in DTT implementations. Once a communication mean has been determined, the Customer will be responsible for all construction back to the point of interconnect. DNP3 is the Eversource Energy’s specified communication protocol. Eversource Energy as the area EPS operator has established the following DER communications interface requirements: 1. Small to mid-size behind the meter residential and commercial systems with nameplate capacity of less than or equal to 500 kW have no specific requirements for DER communications interface currently. 2. Large DER systems with nameplate capacity greater than or equal to 500 kW are required to have and provide evidence of a DNP3 communications interface. - 17 -Page 19 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 19 of 34 3. Emergency and standby DER systems are exempt as specified in 4.13 of IEEE 1547-2018 from the interoperability requirements specified in this standard. 4 Protection and Control Requirements 4.1 Classifications of Interconnections 4.1.1 Purely Exporting A Purely Exporting Generator (figure 1) or stand-alone DER within the context of these requirements shall mean any DER that is installed with the purpose of providing power onto the Company EPS and has little or no on-site customer load. The PCC will be defined in an Agreement between the DER owner and the Company. Under the context of this type of interconnection, the Company will regard the PCC Utility owned switch as the means to isolate the generator during times when the Company considers it unacceptable for parallel generation to operate. The Company owned disconnecting device may be operated during off normal system configurations or any number of adverse conditions that may be brought to light in an Impact Study. This device may be operated manually, remotely or through the operation of a Company direct transfer trip scheme. When deemed necessary, the DER owner shall install and maintain a protection and control system. The Company disconnecting device shall not be considered as part of the DER’s protection scheme. - 18 -Page 20 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 20 of 34 - 19 -Page 21 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 21 of 34 4.1.2 Behind the Meter Exporting A Behind the Meter and Exporting Generator (refer to figure 2) within the context of these requirements shall be defined as any DER Facility that is installed with the purpose of providing power onto the Company EPS while there is also significant on-site customer load. For this type of installation, the Company will consider the PCC as the metering location, when the Company owns the transformer and cable up to that point. For primary metered customers, the same logic is applicable, but the PCC becomes the primary metered location per the PCC definition as defined in an agreement between the Company and the DER owner. The Company owned disconnecting device at the PCC may not be required in this case because the Customer load is present and may not be easily isolated along with the generator when the generator is tripped offline. In these cases, when the Company requires the Facility be isolated from the EPS, it will be necessary for the Company to trip and block close a protection device to be specified by the Company which may be owned by the Company or the DER owner to disconnect the generator for the duration of that condition. The device may need to be operated during off normal system configurations or any number of adverse conditions the DER may cause on the Company EPS. This device may be operated manually, remotely or through the operation of a Company direct transfer trip scheme. This would require a communication interface between the Company and specified equipment. - 20 -Page 22 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 22 of 34 - 21 -Page 23 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 23 of 34 4.1.3 Behind the Meter Non-Exporting For Facilities connected in parallel with the Company EPS which are only intended to supplement onsite customer load (no power export to Company EPS) standard antiIslanding protection in addition to minimum import protection shall be required. Minimum import protection (32 relay functionality) shall be set to trip a dedicated generator breaker and isolate the generator from the rest of the EPS any time power import at the metering location drops to 5% of the generator name plate MW value. For Facilities with multiple DERs in parallel on site, the ‘DER name plate’ value will be considered the cumulative sum of all DER name plates on site. 4.2 Protection Requirements per Technology Size and Type Relay requirements will vary according to size and technology type. The designations below organize protection requirements according to these considerations. The Company reserves the right to amend any of the following requirements if deemed necessary. Note – All DER interconnections shall also be required to have both Phase and Ground Overcurrent protection designed to isolate the generator from the Company EPS during any single/multiple phase(s)-to-ground, phase-to-phase, or three-phase faults on the Company EPS. Where applicable, the Company may require the DER owner to also coordinate their Facility’s Overcurrent protection scheme with the Company’s upstream system protection. In this case the Company shall provide the DER owner with the upstream relay settings. The Company may also require the DER owner to submit an applicable State Licensed Professional Engineer (“PE”) Stamped coordination study of the Customer’s facility to ensure coordination with the Company’s upstream settings. Inverter settings must be shown in a table on the applicable State PE stamped one-line diagram. When relays are required, relay settings must be shown in a table in definitive values on the applicable State PE stamped one line. 4.2.1 Inverter Based DERs less than 500kW: The DER’s relay system shall consist of UL1741 listed inverters with 27, 59, 81U and 81O relay functionality. Relay contactors may be used as the disconnecting means. A Company owned/maintained isolation device at the PCC may be required however the final determination of need will be at the sole discretion of the Company. Inverter based systems smaller than 500kW may be allowed to utilize the inverter contactor to isolate during over/under voltage and over/under frequency. However, isolation for inverter overcurrent may require fuses or a dedicated breaker if inverter contactors are not designed and rated to isolate during a nameplate fault current event. - 22 -Page 24 of 34
The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-001 Attachment 4 Page 24 of 34 The Company may require additional relay protection for systems 500 kW and smaller based on the Facility design, EPS and/or other factors determined during the review of the project. This is required when multiple inverters are installed. 4.2.2 Inverter Based DERs 500 kW or greater: The DER’s relay system shall consist of UL1741 listed inverters and include one additional ‘utility grade’ relay (as defined by listed requirements in Appendix A) with 27, 59, 59N, 81U and 81O relay functionality. A Company owned/maintained isolation device may be required at the PCC The Company may require additional relay protection based on the Facility design, EPS and/or other factors determined during the review of the project. 4.2.3 Asynchronous (Induction’) DGs under 300kW The DER’s relay system shall consist of at least one utility grade relay with 27, 59, 81U and 81O relay functionality. Induction DGs with built-in ‘utility grade’ relays with the functionality above may be adequate if UL1741 and IEEE1547 listed. A Company owned/maintained isolation device at the PCC may not be required; however, the final determination of need will be at the sole discretion of the Company. In MA, for all induction generators greater than 1/15 of on-site minimum verifiable load that are not equipped with on-site capacitors or that are greater than 200 kW, and for all synchronous generators, protective relays utilized by the Facility shall be sufficiently redundant and functionally separate so as to provide adequate protection, consistent with Company practices and standards, upon the failure of any one component 4.2.4 Asynchronous (Induction) DGs, 300kW or greater or Synchronous of any size: The DER’s relay system shall consist of at least two utility grade relays with 27, 59, 59N, 81U and 81O relay functionality. Induction DGs with built-in utility grade relays with the functionality above may be adequate for primary protection. A Company owned/maintained isolation device at the PCC may be required. In some cases, the Company isolation device may eliminate the redundant utility-grade relay requirement noted above. In MA, for all synchronous generators, protective relays utilized by the Facility shall be sufficiently redundant and functionally separate to provide adequate protection, consistent with Company practices and standards, upon the failure of any one component. - 23 -
Text of ICC-001 Attachment 5.pdf
Extracted from the file · 67 pages · 136,480 characters
Text of ICC-002_Final.pdf
Extracted from the file · 2 pages · 2,788 characters
Text of ICC-002 Attachment 1.pdf
Extracted from the file · 29 pages · 46,015 characters
Text of ICC-002 Attachment 2.pdf
Extracted from the file · 74 pages · 148,550 characters
Text of ICC-002 Attachment 3.pdf
Extracted from the file · 27 pages · 91,051 characters
Text of ICC-004_Final.pdf
Extracted from the file · 1 page · 983 characters
Text of ICC-010_Final.pdf
Extracted from the file · 4 pages · 11,507 characters
Text of ICC-018_Final.pdf
Extracted from the file · 2 pages · 2,628 characters
As listed on the current system
Question(s) Answered 1, 2, 4, 10, 18, 20 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 09/22/2026