Skip to main content

A prototype public docket site for the Connecticut Public Utilities Regulatory Authority

Utility Dockets and Filings

Interrogatory responses

Answers to questions 1, 2, 4, 10, 18, 20

ResponseFiled by Connecticut Light and Power Company dba Eversource Energy13 files
Part of docket 26-05-10Open
  • Electric
Application of The Connecticut Light and Power Company d/b/a Eversource Energy to Amend its Rate Schedules

Files13

Text of ICC-001 Attachment 3.pdf

Extracted from the file · 34 pages · 76,972 characters

Text of ICC-001 Attachment 4.pdf

Extracted from the file · 34 pages · 72,650 characters

Text of ICC-001 Attachment 5.pdf

Extracted from the file · 67 pages · 136,480 characters

Text of ICC-002_Final.pdf

Extracted from the file · 2 pages · 2,788 characters

  1. Page 10 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 10 of 29 3.2.3 PURA Dispute Resolution: If the Parties cannot resolve their dispute through negotiation or mediation within 30 days, either Party may commence an action at PURA for resolution of the dispute. All timeframes in this process and the Dispute Resolution Process itself may be modified by mutual written agreement of the Parties. 3.3 Confidentiality The EDC shall maintain the confidentiality of all information so designated by the Customer if clearly marked and labeled “Confidential” except as otherwise required by system operators, applicable laws and regulations, and regulatory and judicial requests or requirements. In the event a third party requests that the EDC produce confidential information, the EDC shall provide advance notice to the Customer, if possible, to give the Customer an opportunity to seek protective treatment of such information. If such information is requested or required by PURA, the EDC will seek protective treatment of such information. Confidential information does not include information previously in the public domain or that becomes generally available to the public without violation of these Guidelines. 3.4 Comparability The EDC shall process and analyze all Interconnection Applications in a timely manner as set forth in this document. The EDC shall use the same reasonable efforts in processing and analyzing Interconnection Applications from all Customers. 3.5 Record Retention The EDC shall maintain, for three (3) years, records, subject to audit, of all Interconnection Applications received under these procedures, the times required to complete Interconnection Application approvals and disapprovals, and justification for the actions taken on the Interconnection Applications. 3.6 Acceptance of Guideline Requirements The Customer shall sign and return the Application which indicates the Customer’s acceptance of the terms, conditions, and requirements included in the Guidelines. After the EDC receives the Application signed by the Customer acknowledging acceptance of all terms and conditions contained 10 Eversource - Internal Use
  2. Page 11 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 11 of 29 in the Guidelines, the Interconnection of the Generating Facility shall proceed under the provisions of the Guidelines. 3.7 Capacity of Generating Facility The Capacity of a Generating Facility, for the purpose of analysis, shall be determined as follows: 3.7.1 if the Application pertains to an increase in capacity for an existing Generating Facility, the Application shall be evaluated on the basis of the new total capacity of the Generating Facility; 3.7.2 if the Application is for a Generating Facility that includes multiple energy production devices at a site for which the Customer seeks a single Point of Interconnection, the Interconnection Application shall be evaluated on the basis of the aggregate capacity of the multiple devices; and, 3.7.3 the Application shall be evaluated using the maximum nameplate rated capacity of the Generating Facility in kW AC. 3.8 Construction of the Facility It is recommended that the Customer construct the Generating Facility after the EDC approves the Application for installation and returns the “Contingent Approval to Interconnect” to the Customer. 3.9 Interconnection and Operation The Customer may operate the Generating Facility and Interconnect with the EDC electric system in accordance with these Guidelines once all of the following have occurred: 11 Eversource - Internal Use
  3. Page 12 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 12 of 29 3.9.1 Upon completing construction, the Generating Facility has been inspected or otherwise certified by the appropriate local electrical wiring inspector with jurisdiction; 3.9.2 The EDC has either: 3.9.2.1 completed its inspection, and witnessed the Commissioning Test of the Generating Facility to ensure that all equipment has been appropriately installed and that all electrical connections have been made in accordance with applicable codes and standards provided to the Generating Facility with an “Approval to Energize” document; or 3.9.2.2 the EDC waived the right to inspect the Generating Facility by providing written notice of its waiver to the Customer; 3.9.3 The EDC has the right to disconnect the Generating Facility in the event that, in its sole discretion, it believes that the Generating Facility is not operating in a safe and reliable manner. 3.10 Safe Operations and Maintenance The Customer shall be fully responsible to operate, maintain, and repair the Generating Facility or to cause the operation, maintenance and repair of the Generating Facility as required to ensure that it complies at all times with these Guidelines and the interconnection standards to which it has been certified. 3.11 Access The EDC shall have access to the AC Isolation Device (if an AC Isolation Device is required by the EDC) and metering equipment of the Generating Facility at all times. The EDC shall provide reasonable notice to the Customer when possible prior to using its right of access. The Customer is solely responsible for obtaining any and all permits and easements necessary to allow EDC to gain access to the AC Isolation Device. 3.12 Disconnection The EDC may temporarily disconnect the Certified Inverter-Based Generating Facility upon the following conditions: 12 Eversource - Internal Use
  4. Page 13 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 13 of 29 3.12.1 for scheduled outages upon reasonable notice; 3.12.2 for unscheduled outages or when the EDC believes that there is an emergency situation which includes the Generating Facility adversely affecting the EPS, any equipment owned or operated by the EDC, or other customers of the EDC; or 3.12.3 if the Generating Facility does not operate in the manner consistent with these Guidelines. 3.12.4 The EDC shall inform the Customer in advance of any scheduled disconnection, or within a reasonable time after an unscheduled disconnection. 3.13 Indemnification Each Party shall at all times indemnify, defend, and hold harmless the other Party, its current or former affiliates, agents, servants, officers, directors, employees, managers, contractors, shareholders, principals, predecessors, partners, representatives, attorneys, insurers, reinsurers, sureties, heirs, executors, administrators, successors and assigns from, any and all damages, losses, claims, including claims and actions relating to injury to or death of any person or damage to property, demand, suits, recoveries, costs and expenses, court costs, attorney fees, and all other obligations by or to third parties, arising out of or resulting from the indemnifying Party's actions or inactions under this agreement, except in cases of negligence or intentional wrongdoing by the indemnified Party. 3.14 Insurance. Each Customer, the Site Owner and the Generator shall be solely responsible for independently maintaining adequate and appropriate liability insurance. The EDC does not require the Customer, Site Owner and the Generator to obtain insurance. However, the Customer shall (and shall cause the Site Owner and Generator to) fully release and hold the EDC harmless with respect to any failure of Customer, Site Owner or Generator to adequately and appropriately maintain such insurance. In no event shall the EDC be liable whatsoever for any damages (including to person or property) in connection with the Interconnection that is (or would have been) covered by such insurance. The EDC’s sole liability in 13 Eversource - Internal Use
  5. Page 14 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 14 of 29 connection with the Interconnection is set forth in Section 3.15 of these Guidelines. 3.15 Limitation of Liability Each Party’s liability to the other Party for any loss, cost, claim, injury, liability, or expense, including reasonable attorney’s fees, relating to or arising from any act or omission in its performance of its obligations pursuant to these Guidelines, shall be limited to the amount of direct damage actually incurred. In no event shall either party be liable to the other party for any indirect, incidental, special, consequential, or punitive damages of any kind whatsoever. 3.16 Termination The Interconnection may be terminated under the following conditions: 3.16.1 by the Customer with 30 days advance written notice to the EDC; 3.16.2 by the EDC, if the Generating Facility fails to operate for any consecutive 12 month period; or, 3.16.3 by the EDC if the Customer fails to remedy or cause to have remedied a violation of these Guidelines within 30 days of receiving written notice of said violation from the EDC. 3.17 Survival Rights The provisions within these Guidelines shall continue in effect after termination to the extent necessary to allow or require any Party to fulfill rights or obligations that arose under the Guidelines. 3.18 Assignment/Transfer of Ownership of the Facility The Customer shall notify the EDC of its intent to transfer the Generating Facility no less than 30 days prior to the transfer, or, within five (5) Business Days of the formation of the intent to transfer if the intent forms less than 30 days before transfer. These Guidelines shall survive the transfer of 14 Eversource - Internal Use
  6. Page 15 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 15 of 29 ownership of the Generating Facility to a new owner only provided that the new owner agrees in writing to comply with the terms of the Guidelines and so notifies the EDC. Absent acceptance by the new owner, within 30 days of the transfer, the Interconnection is no longer authorized and the EDC reserves the right to terminate the Interconnection at its own discretion. The EDC will provide the new owner with notice of its intent to terminate at least 30 days in advance of said termination. 3.19 Withdrawal The Customer may withdraw its Interconnection Application at any time by written notice of such withdrawal to the EDC. 3.19.1 In addition, if the Customer fails to adhere to all requirements of these Guidelines, the EDC shall deem the Interconnection Application withdrawn and shall provide written notice to the Customer of the deemed withdrawal and an explanation of the reasons for such deemed withdrawal. 3.19.2 Upon receipt of such written notice, if the Customer wishes to dispute the withdrawal notice, the Customer shall have fifteen (15) Business Days to respond with information or actions that cure the deficiency or to notify the EDC of its intent to pursue dispute resolution in accordance with Section 3.2. 3.20 Withdrawal of an Interconnection Application shall result in the loss of queue position assigned to such Interconnection Application. 3.21 If a Customer disputes such withdrawal and loss of queue position, then the Customer’s Application shall be removed from the queue until such time that the outcome of the dispute restores its queue position. 3.22 A Customer who fails to pay all monies due shall not be eligible to submit subsequent Interconnection Applications 15 Eversource - Internal Use
  7. Page 16 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 16 of 29 4 Technical Requirements 4.1 All Interconnection Applications must provide a scheme which ensures protection against Islanding. All exporting entities, including inadvertent export and all net metering projects, interconnecting to the EPS with existing synchronous generators, on the same Distribution Feeder, will be reviewed on a case-by-case basis to ensure there is adequate protection against Islanding. If screening criteria are not met, the project will be reviewed using the Fast Track/Study Process. 4.2 All steady-state and transient operating limits for voltage, flicker voltage, frequency, harmonic contents, etc. must comply with the latest versions of IEEE1547, the NEC and other relevant IEEE standards and all other applicable local, state, or federal regulations. 4.3 Subsequent to the occurrence of events which causes the inverter to trip, the utility line voltage must remain stable in voltage and frequency for a minimum of five (5) minutes prior to permitting the Inverter to conduct again. 4.4 Equipment and Material: 4.4.1 Approved Inverter(s): An Inverter is considered approved if it is certified to the latest version of UL 1741 and compliant with the authorities having jurisdiction. Proof of certification may be required by EDC. 4.4.2 AC Isolation Device: Unless otherwise approved in writing by the EDC, the Customer is required to provide a manual AC Isolation Device, to be located outside and accessible to the EDC for Generating Facilities larger than 1 kW. 4.4.3 The AC Isolation Device must be appropriately labeled “Generator Isolation Device.” 4.4.4 The AC Isolation Device should be visible and in close proximity (10 feet or less) to the main utility meter panel, unless otherwise approved in writing by the EDC. 4.4.5 The switch shall be gang operated, have a visible break when open, be rated to interrupt the maximum generator output and be capable of being locked open by EDC personnel. 16 Eversource - Internal Use
  8. Page 17 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 17 of 29 4.5 Revenue Metering Requirements: In the event metering replacement or installation is required, the meter will be replaced or installed by the EDC in compliance with the applicable EDC’s Rates and Tariffs, Service Requirement and Terms and Conditions. 4.6 Generation Metering Requirement: Additional generating metering may be required by the EDC or to comply with applicable program requirements. Such requirements are not part of these Guidelines. 4.7 Emergency generators and systems with energy storage devices in closed transition configuration must comply with these Guidelines. 4.8 Inverter voltage trip settings Shall Trip Function OV2 OV1 UV1 UV2 Required Settings Voltage (p.u. of nominal voltage) 1.20 1.10 0.88 0.50 Clearing Time(s) 0.16 2.0 2.0 1.1 4.9 Inverter frequency trip settings Shall Trip Required Settings Function Frequency Clearing (Hz) Time(s) OF2 62.0 0.16 OF1 61.2 300.0 UF1 58.5 300.0 UF2 56.5 0.16 4.10 Inverter Voltage Ride-through Capability and Operational Requirements Voltage Range (p.u.) Operating Mode/ Response Minimum Ride-through Time(s) (design criteria) V > 1.20 1.175<V≤1.20 1.15<V≤1.175 1.10<V≤1.15 0.88≤V≤1.10 0.65≤V<0.88 Cease to Energize Permissive Operation Permissive Operation Permissive Operation Continuous Operation Mandatory Operation N/A 0.2 0.5 1 infinite Linear slope of 8.7 s/1 p.u. voltage starting at 3 s @ 0.65 p.u.: 17 Eversource - Internal Use Maximum Response Time(s) (design criteria) 0.16 N/A N/A N/A N/A N/A
  9. Page 18 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 18 of 29 𝑇𝑉𝑅𝑇 = 3 𝑠 + 0.45≤V<0.65 0.30≤V<0.45 V<0.30 8.7 (𝑉 − 0.65 𝑝. 𝑢. ) 1 𝑝. 𝑢. Permissive Operationab Permissive Operationb Cease to Energize 0.32 N/A 0.16 N/A N/A 0.16 4.11 Inverter frequency ride-thru capability Frequency Range Minimum Time(s) (Hz) Operating Mode (Design Criteria) f > 62.0 No ride-through requirements apply to this range 61.2<f≤61.8 Mandatory Operation 299 58.8≤f≤61.2 Continuous Operation Infinite 57.0≤f≤58.8 Mandatory Operation 299 f<57.0 No ride-through requirements apply to this range 4.12 Grid support utility interactive inverter function status Function Default Activation State SPF, Specified Power Factor Off Q(V), Volt-Var Function Off with Watt or Var Priority Default value: 2% of maximum current output per second SS, Soft-Start Ramp Rate On FW, Freq-Watt Function Off OFF a In the Permissive Operation region above 0.5 p.u., inverters shall ride-through in Mandatory Operation mode, and b In the Permissive Operation region below 0.5 p.u., inverters shall ride-through in Mandatory Cessation mode with a maximum response time of 0.083 seconds. 18 Eversource - Internal Use
  10. Page 19 of 29

    The Connecticut Light and Power Company d/b/a Eversource Energy Docket No. 26-05-10 Date Issued September 08, 2026 ICC-002 Attachment 1 Page 19 of 29 1) Instructions to File an Application Refer to web page link below Eversource: https://www.eversource.com/content/ct-c/about/about-us/doingbusiness-with-us/builders-contractors/interconnections UI: https://www.uinet.com 19 Eversource - Internal Use

Text of ICC-002 Attachment 2.pdf

Extracted from the file · 74 pages · 148,550 characters

Text of ICC-002 Attachment 3.pdf

Extracted from the file · 27 pages · 91,051 characters

Text of ICC-004_Final.pdf

Extracted from the file · 1 page · 983 characters

Text of ICC-010_Final.pdf

Extracted from the file · 4 pages · 11,507 characters

Text of ICC-018_Final.pdf

Extracted from the file · 2 pages · 2,628 characters

As listed on the current system

Question(s) Answered 1, 2, 4, 10, 18, 20 (Connecticut Light and Power Company dba Eversource Energy) Date Filed: 09/22/2026

This filing on the current system (opens in a new tab)